4.1 Surface materials on bulkheads, wall and ceiling
linings including their supporting structure are considered to be
a "fire-restricting material" if during testing time of 20 min according
to the standard ISO 9705 as qualified in paragraph
2.1, the following six criteria are met:
-
.1 the time average of heat release rate (HRR)
excluding the HRR from the ignition source does not exceed 100 kW;
-
.2 the maximum HRR excluding the HRR from the
ignition source does not exceed 500 kW averaged over any 30 s period
of time during the test;
-
.3 the time average of the smoke production rate
does not exceed 1.4 m2 /s;
-
.4 the maximum value of the smoke production rate
does not exceed 8.3 m2 /s averaged over any period of 60
s during the test;
-
.5 flame spread should not reach any further down
the walls of the test room than 0.5 m from the floor excluding the
area which is within 1.2 m from the corner where the ignition source
is located; and
-
.6 no flaming drops or debris of the test sample
may reach the floor of the test room outside the area which is within
1.2 m from the corner where the ignition source is located.
4.2 Materials used for furniture and other components
are considered to be "fire-restricting material" if during testing
to the standard ISO 5660 as described in paragraph
2.2, the following four criteria are fulfilled:
-
.1 the time to ignition (tig ) is greater
than 20 s;
-
.2 the maximum 30-second sliding average heat
release rate (HRR30,max) does not exceed 60 kW/m2 ;
-
.3 the total heat release (THR) does not exceed
20 MJ/m2 ;
-
.4 the time average smoke production rate (SPRavg ) does not exceed 0.005 m2 /s.
4.3 Materials which qualify as "fire-restricting
materials" using the standard ISO 9705 test method described in this
annex may be used for furniture or other components if the material
closely represents the configuration tested as a room lining in it's
actual end use (i.e. similar thickness and surface finish)."