The test method is applicable for water-based fire-extinguishing
systems which will be used as alternative fire-extinguishing systems
as required by SOLAS regulation II-2/10.4.1 and II-2/10.9.1. For the
installation of the system, nozzles shall be installed to protect
the entire hazard volume (total flooding). The installation specification
provided by the manufacturer should include maximum horizontal and
vertical nozzle spacing, maximum enclosure height, and distance of
nozzles below the ceiling and maximum enclosure volume which, as a
principle, should not exceed the values used in approval fire test.
However, when based on the scientific methods developed by the Organizationfootnote, scaling from the maximum tested volume
to a larger volume may be permitted. The scaling should not exceed
twice the tested volume.