Doors in Watertight Bulkheads of Passenger Ships and Cargo
Ships
Interpretation
This interpretation pertains to doorsfootnote located in way of the internal watertight
subdivision boundaries and the external watertight boundaries necessary
to ensure compliance with the relevant subdivision and damage stability
regulations.
This interpretation does not apply to doors located in external
boundaries above equilibrium or intermediate waterplanes.
The design and testing requirements for watertight doors
vary according to their location relative to the equilibrium waterplane
or intermediate waterplane at any stage of assumed flooding.
1
Definitions
For the purpose of this interpretation the following definitions
apply:
1.1
Watertight:
Capable
of preventing the passage of water in any direction under a design
head. The design head for any part of a structure should be determined
by reference to its location relative to the bulkhead deck or freeboard
deck, as applicable, or to the most unfavourable equilibrium/intermediate
waterplane, in accordance with the applicable subdivision and damage
stability regulations, whichever is the greater. A watertight door
is thus one that will maintain the watertight integrity of the subdivision
bulkhead in which it is located.
1.2
Equilibrium waterplane:
The
waterplane in still water when, taking account of flooding due to
an assumed damage, the weight and buoyancy forces acting on a ship
are in balance. This relates to the final condition when no further
flooding takes place or after cross flooding is completed.
1.3
Intermediate waterplane:
The
waterplane in still water, which represents the instantaneous floating
position of a ship at some intermediate stage between commencement
and completion of flooding when, taking account of the assumed instantaneous
state of flooding, the weight and buoyancy forces acting on a ship
are in balance.
1.4
Sliding door or rolling door:
A
door having a horizontal or vertical motion generally parallel to
the plane of the door.
1.5
Hinged door:
A door
having a pivoting motion about one vertical or horizontal edge.
2
Structural Design
Doors and their frames should be of approved design and
substantial construction in accordance with the requirements of the
Administration and should preserve the strength of the subdivision
bulkheads in which they are fitted.
3
Operation Mode,
Location and Outfitting
Doors should be fitted in accordance with all requirements
regarding their operation mode, location and outfitting, i.e. provision
of controls, means of indication, etc., as shown in table 1 below.
This table should be read in conjunction with paragraphs 3.1 to 5.4
below.
3.1
Frequency
of use whilst at sea
3.1.1
Normally closed: Kept closed
at sea but may be used if authorized. To be closed again after use.
3.1.2
Permanently closed: The time
of opening such doors in port and of closing them before the ship
leaves port should be entered in the logbook. Should such doors be
accessible during the voyage, they should be fitted with a device
to prevent unauthorized opening.
3.1.3
Normally open: May be left
open provided it is always ready to be immediately closed.
3.1.4
Used: In regular use, may be
left open provided it is ready to be immediately closed.
Power operated, sliding or
rollingfootnote
|
POS
|
Power operated, hinged
|
POH
|
Sliding or rolling
|
S
|
Hinged
|
H
|
3.3.1.1 All doors, except those which should be
permanently closed at sea, should be capable of being opened and closed
by hand locallyfootnote, from both sides
of the doors, with the ship listed to either side.
3.3.1.2 For passenger ships, the angle of list
at which operation by hand should be possible is 15º or 20º
if the ship is allowed to heel up to 20º during intermediate
stages of flooding.
3.3.1.3 For cargo ships, the angle of list at
which operation by hand should be possible is 30º.
Where indicated in table 1, doors should be capable of being remotely
closed by power from the bridgefootnote. Where it is necessary to start the power unit for operation of
the watertight door, means to start the power unit is also to be provided at
remote control stations. The operation of such remote control should be in
accordance with SOLAS regulations II-1/13.8.1 to 13.8.3.
3.4.1 Where shown in table 1, position indicators
should be provided at all remote operating positionsfootnote as well as locally, on both sides of the
doorsfootnote, to show whether the doors
are open or closed and, if applicable, with all dogs/cleats fully
and properly engaged.
3.4.2 The door position indicating system should
be of self-monitoring type and the means for testing of the indicating
system should be provided at the position where the indicators are
fitted.
3.4.3 An indication (i.e. red light) should be
placed locally showing that the door is in remote control mode ("doors
closed mode"). Refer also to SOLAS regulation
II-1/15-8.1. Special care should be taken in order to avoid
potential danger when passing through the door. Signboard/instructions
should be placed in way of the door advising how to act when the door
is in "doors closed" mode.
3.5.1 Doors which should be capable of being remotely
closed should be provided with an audible alarm, distinct from any
other alarm in the area, which will sound whenever such a door is
remotely closed. For passenger ships the alarm should sound for at
least 5 s but not more than 10 s before the door begins to move and
should continue sounding until the door is completely closed. In the
case of remote closure by hand operation, an alarm is required to
sound only while the door is actually moving.
3.5.2 In passenger areas and areas of high ambient
noise, the audible alarms should be supplemented by visual signals
at both sides of the doors.
As shown in table 1, doors which are normally closed at
sea, but are not provided with means of remote closure, should have
notices fixed to both sides of the doors stating: "To be kept closed
at sea". Doors which should be permanently closed at sea should have
notices fixed to both sides stating: "Not to be opened at sea".
4
Fire Doors
4.1 Watertight doors may also serve as fire doors but
need not be fire tested when intended for use below the bulkhead deck. Where such
doors are used at locations above the bulkhead deck they should, in addition to
complying with the provisions applicable to fire doors at the same locations, also
comply with means of escape provisions of SOLAS regulation
II-2/13.
4.2 Where a watertight door is located adjacent
to a fire door, both doors should be capable of independent operation,
remotely if required by SOLAS regulations
II-1/15.8.1 to 15.8.3 and from both sides of each door.
5
Testing
5.1 Doors which become immersed by an equilibrium
or intermediate waterplane or are below the freeboard or bulkhead
deck should be subjected to a hydrostatic pressure test.
5.2 For large doors intended for use in the watertight
subdivision boundaries of cargo spaces, structural analysis may be
accepted in lieu of pressure testing. Where such doors utilize gasket
seals, a prototype pressure test to confirm that the compression of
the gasket material is capable of accommodating any deflection, revealed
by the structural analysis, should be carried out.
5.3 Doors above freeboard or bulkhead deck, which
are not immersed by an equilibrium or intermediate waterplane but
become intermittently immersed at angles of heel in the required range
of positive stability beyond the equilibrium position should be hose
tested.
5.4.1 The head of water used for the pressure
test should correspond at least to the head measured from the lower
edge of the door opening, at the location in which the door should
be fitted in the ship, to the bulkhead deck or freeboard deck, as
applicable, or to the most unfavourable damage waterplane, if that
be greater. Testing may be carried out at the factory or other shore-based
testing facility prior to installation in the ship.
5.4.2.1 The following acceptable leakage criteria
should apply:
Doors
with gaskets
|
No leakage
|
Doors with
metallic sealing
|
Maximum leakage
1 l/min
|
5.4.2.2 Limited leakage may be accepted for pressure
tests on large doors located in cargo spaces employing gasket seals
or guillotine doors located in conveyor tunnels, in accordance with
the followingfootnote:
Leakage rate
(l/min)
|
=
|
|
where:
|
P = perimeter
of door opening (metres)
|
|
h = test head of water (metres)
|
5.4.2.3 However, in the case of doors where the
water head taken for the determination of the scantling does not exceed
6.1 m, the leakage rate may be taken equal to 0.375 l/min
if this value is greater than that calculated by the above-mentioned
formula.
5.4.3 For doors of passenger ships which are normally
open and used at sea and which become submerged by the equilibrium
or intermediate waterplane, a prototype test should be conducted,
on each side of the door, to check the satisfactory closing of the
door against a force equivalent to a water height of at least 1 m
above the sill on the centre line of the doorfootnote.
5.5
Hose
testing after installation
All watertight doors should be subject to a hose testfootnote after installation in a ship. Hose testing
should be carried out from each side of a door unless, for a specific
application, exposure to floodwater is anticipated only from one side.
Where a hose test is not practicable because of possible damage to
machinery, electrical equipment insulation, or outfitting items, it
may be replaced by means such as an ultrasonic leak test or an equivalent
test.
Table 1 - Internal doors in
watertight bulkheads in cargo ships and passenger ships
Position relative to equilibrium or intermediate waterplane
|
1 Frequency of use whilst at sea
|
2 Type
|
3 Remote control6
|
4 Indication locally and on bridge6
|
5 Audible alarm6
|
6 Notice
|
7 Comments
|
8 Regulation
|
I. Passenger ships
|
A. At or below
|
Normally
closed
|
POS
|
Yes
|
Yes
|
Yes
|
No
|
Certain doors may be left open,
see regulation II-1 /22.4
|
II-1/22.1 to II-1/22.4
|
Permanently
closed
|
S, H
|
No
|
No
|
No
|
Yes
|
See Notes 1 +
4
|
II-1/13.9.1 and II-1/13.9.2
|
B. Above
|
Normally
open
|
POS, POH
|
Yes
|
Yes
|
Yes
|
No
|
|
II-1/22.4 II-1/17.1 MSC/Circ.541
|
Normally closed
|
S, H
|
No
|
Yes
|
No
|
Yes
|
See Note
2
|
S, H
|
No
|
Yes
|
No
|
Yes
|
Doors giving
access to ro-ro deck
|
II-1/17-1
|
II. Cargo ships
|
A. At or below
|
Used
|
POS
|
Yes
|
Yes
|
Yes
|
No
|
|
II-1/13-1.2
|
Normally
closed
|
S, H
|
No
|
Yes
|
No
|
Yes
|
see Notes 2 + 3
+ 5
|
II-1/13-1.3
|
Permanently
closed
|
S, H
|
No
|
No
|
No
|
Yes
|
see Notes 1 +
4
|
II-1/13-1.4 II-1/15-1
|
B. Above
|
Used
|
POS
|
Yes
|
Yes
|
Yes
|
No
|
|
II-1/13-1.2
|
Normally
closed
|
S, H
|
No
|
Yes
|
No
|
Yes
|
See Notes 2 +
5
|
II-1/13-1.3 II-1/15-1
|
Notes:
|
1
|
Doors in watertight bulkheads subdividing cargo
spaces.
|
2
|
If hinged, this door should be of quick-acting or
single-action type.
|
3
|
SOLAS requires remotely operated watertight doors to be
sliding doors.
|
4
|
The time of opening such doors in port and closing them
before the ship leaves port should be entered in the logbook.
|
5
|
The use of such doors should be authorized by the officer
of the watch.
|
6
|
Cables for control and power systems to power-operated
watertight doors and their status indication should comply with the
requirements of IACS UR E15.
|
|