Principal requirements
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC/Circular.848 – Revised Guidelines for the Approval of Equivalent Fixed Gas Fire-Extinguishing Systems, as Referred to in SOLAS 74, for Machinery Spaces and Cargo Pump-Rooms – (Adopted on 8 June 1998)Amended by MSC.1/Circular.1267 - Annex - Revised Guidelines for the Approval of Equivalent Fixed Gas Fire-Extinguishing Systems, as Referred to in SOLAS 74, for Machinery Spaces and Cargo Pump-Rooms - Principal requirements

Principal requirements

  2 All requirements of the FSS Code, chapter 5, regulation 2.1 footnote, except as modified by these guidelines, should apply.

  3 The minimum extinguishing concentration should be determined by a cup burner test acceptable to the Administration. The design concentration should be at least 30% above the minimum extinguishing concentration. These concentrations should be verified by full-scale testing described in the test method, as set out in the appendix.

  4 For systems using halocarbon clean agents, 95% of the design concentration should be discharged in 10 s or less. For inert gas systems, the discharge time should not exceed 120 s for 85% of the design concentration.

  5 The quantity of extinguishing agent for the protected space should be calculated at the minimum expected ambient temperature using the design concentration based on the net volume of the protected space, including the casing.

  • 5.1 The net volume of a protected space is that part of the gross volume of the space which is accessible to the free extinguishing agent gas.

  • 5.2 When calculating the net volume of a protected space, the net volume should include the volume of the bilge, the volume of the casing and the volume of free air contained in air receivers that in the event of a fire is released into the protected space.

  • 5.3 The objects that occupy volume in the protected space should be subtracted from the gross volume of the space. They include, but are not necessarily limited to:

    • auxiliary machinery;
    • boilers;
    • condensers;
    • evaporators;
    • main engines;
    • reduction gears;
    • tanks; and
    • trunks.
  • 5.4 Subsequent modifications to the protected space that alter the net volume of the space shall require the quantity of extinguishing agent to be adjusted to meet the requirements of this paragraph and paragraph 6.

  6 All systems should be designed to allow evacuation of the protected spaces prior to discharge. Means should also be provided for automatically giving audible and visual warning of the release of fire-extinguishing medium into any space in which personnel normally work or to which they have access. The alarm should operate for the period of time necessary to evacuate the space, but not less than 20 s before the medium is released. Unnecessary exposure, even at concentrations below an adverse effect level, should be avoided.

  • 6.1 Even at concentrations below an adverse effect level, exposure to gaseous fire extinguishing agents should not exceed 5 min Halocarbon agents may be used up to the No Observed Adverse Effect Level (NOAEL) calculated on the net volume of the protected space at the maximum expected ambient temperature without additional safety measures. If a halocarbon agent is to be used above its NOAEL, means should be provided to limit exposure to no longer than the time specified according to a scientifically accepted physiologically based pharmacokineticfootnote (PBPK) model or its equivalent which clearly establishes safe exposure limits both in terms of extinguishing media concentration and human exposure time.

  • 6.2 For inert gas systems, means should be provided to limit exposure to no longer than 5 min for inert gas systems designed to concentrations below 43% (corresponding to an oxygen concentration of 12%, sea level equivalent of oxygen) or to limit exposure to no longer than 3 min for inert gas systems designed to concentrations between 43% and 52% (corresponding to between 12% and 10% oxygen, sea level equivalent of oxygen) calculated on the net volume of the protected space at the maximum expected ambient temperature.

  • 6.3 In no case should a halocarbon agent be used at concentrations above the Lowest Observed Adverse Effect Level (LOAEL) nor the Approximate Lethal Concentration (ALC) nor should an inert gas be used at gas concentrations above 52% calculated on the net volume of the protected space at the maximum expected ambient temperature.

  7 The system and its components should be suitably designed to withstand ambient temperature changes, vibration, humidity, shock, impact, clogging, and corrosion normally encountered in machinery spaces or cargo pump-rooms in ships.

  8 The system and its components should be designed and installed in accordance with international standards acceptable to the Organizationfootnote and manufactured and tested to the satisfaction of the Administration. As a minimum, the design and installation standards should cover the following elements:

  • .1 safety:

    • toxicity;
    • noise, nozzle discharge; and
    • decomposition products;
  • .2 storage container design and arrangement:

    • strength requirements;
    • maximum/minimum fill density, operating temperature range;
    • pressure and weight indication;
    • pressure relief; and
    • agent identification and lethal requirements;
  • .3 agent supply, quantity, quality standards;

  • .4 pipe and fittings:

    • strength, material, properties, fire resistance; and
    • cleaning requirements;
  • .5 valves:

    • testing requirements;
    • corrosion resistance; and
    • elastomer compatibility;
  • .6 nozzles:

    • height and area testing requirements; and
    • corrosion and elevated temperature resistance;
  • .7 actuation and control systems:

    • testing requirements; and
    • backup power requirements;
  • .8 alarms and indicators:

    • predischarge alarm, agent discharge alarms as time delays;
    • abort switches;
    • supervisory circuit requirements; and
    • warning signs and audible and visual alarms should be located outside each entry to the relevant space as appropriate;
  • .9 agent flow calculation:

    • approval and testing of design calculation method; and
    • fitting losses and/or equivalent length;
  • .10 enclosure integrity and leakage requirements:

    • enclosure leakage;
    • openings; and
    • mechanical ventilation interlocks;
  • .11 design concentration requirements, total flooding quantity;

  • .12 discharge time; and

  • .13 inspection, maintenance, and testing requirements.

  9 The nozzle type, maximum nozzle spacing, maximum height and minimum nozzle pressure should be within limits tested to provide fire extinction per the proposed test method.

  10 Provisions should be made to ensure that escape routes which are exposed to leakage from the protected space are not rendered hazardous during or after discharge of the agent in the event of a fire. In particular, hydrogen fluoride (HF) vapour can be produced in fires as a breakdown product of the fluorocarbon fire extinguishing agents and cause health effects such as upper respiratory tract and eye irritation to the point of impairing escape. Control stations and other locations that require manning during a fire situation should have provisions to keep HF and HCl below 5 ppm at that location. The concentrations of other products should be kept below concentrations considered hazardous for the required duration of exposure.

  11 Where agent containers are stored within a protected space, the containers should be evenly distributed throughout the space and meet the following provisions:

  • .1 a manually initiated power release, located outside the protected space, should be provided. Duplicate sources of power should be provided for this release and should be located outside the protected space, and be immediately available;

  • .2 electric power circuits connecting the containers should be monitored for fault conditions and loss of power. Visual and audible alarms should be provided to indicate this;

  • .3 pneumatic, electric or hydraulic power circuits connecting the containers should be duplicated and widely separated. The sources of pneumatic or hydraulic pressure should be monitored for loss of pressure. Visual and audible alarms should be provided to indicate this;

  • .4 within the protected space, electrical circuits essential for the release of the system should be fire resistant according to standard IEC 60331 or other equivalent standards. Piping systems essential for the release of systems designed to be operated hydraulically or pneumatically should be of steel or other equivalent heat-resisting material to the satisfaction of the Administration;

  • .5 each pressure container should be fitted with an automatic overpressure release device which, in the event of the container being exposed to the effects of fire and the system not being operated, will safely vent the contents of the container into the protected space;

  • .6 the arrangement of containers and the electrical circuits and piping essential for the release of any system should be such that in the event of damage to any one power release line or container valve through mechanical damage, fire or explosion in a protected space, i.e. a single fault concept, at least the amount of agent needed to achieve the minimum extinguishing concentration can still be discharged having regard to the requirement for uniform distribution of medium throughout the space; and

  • .7 the containers should be monitored for decrease in pressure due to leakage and discharge. Visual and audible alarms in the protected area and on the navigation bridge or in the space where the fire control equipment is centralized should be provided to indicate this condition.

  12 A minimum agent hold time of 15 min should be provided.

  13 The release of an extinguishing agent may produce significant over and under pressurization in the protected space. Measures to limit the induced pressures to acceptable limits should be provided.

  14 For all ships, the fire-extinguishing system design manual should address recommended procedures for the control of products of agent decomposition, including HF vapour generated from fluorocarbon extinguishing agents which could impair escape. Clearly, longer exposure of the agent to high temperatures would produce greater concentrations of these types of gases. The type and sensitivity of detection, coupled with the rate of discharge, should be selected to minimize the exposure time of the agent to the elevated temperature. The performance of fire-extinguishing arrangements on passenger ships should not present health hazards from decomposed extinguishing agents, for example on passenger ships, the decomposition products should not be discharged in the vicinity of muster (assembly) stations. Other mitigating steps include evacuation, and donning masks.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.