11.3.1 On ships carrying
flammable or toxic products or both, a water spray system for cooling,
fire prevention and crew protection should be installed to cover:
-
.1 exposed cargo tank domes and any exposed parts of
cargo tanks;
-
.2 exposed on-deck storage vessels for flammable or
toxic products;
-
.3 cargo liquid and vapour discharge and loading
manifolds and the area of their control valves and any other areas where essential
control valves are situated and which should be at least equal to the area of the
drip trays provided; and
-
.4 boundaries of superstructures and deckhouses
normally manned, cargo compressor rooms, cargo pump rooms, store-rooms containing
high fire risk items and cargo control rooms, all facing the cargo area.
Boundaries of unmanned forecastle structures not containing high fire risk items
or equipment do not require water spray protection.
11.3.2 The system should
be capable of covering all areas mentioned in 11.3.1 with a uniformly distributed water spray of at least
10l/m2 per minute for horizontal projected
surfaces and 4l/m2 per minute for vertical
surfaces. For structures having no clearly defined horizontal or vertical
surfaces, the capacity of the water spray system should be the greater
of the following:
On vertical surfaces, spacing of nozzles protecting lower areas may take
account of anticipated rundown from higher areas. Stop valves should be fitted at
intervals in the spray main for the purpose of isolating damaged sections.
Alternatively, the system may be divided into two or more sections which may be operated
independently provided the necessary controls are located together, aft of the cargo
area. A section protecting any area included in 11.3.1.1 and .2 should cover the whole of the athwartship tank grouping which
includes that area.
11.3.3 The capacity of the water spray pumps should be
sufficient to deliver the required amount of water to all areas simultaneously or where
the system is divided into sections, the arrangements and capacity should be such as to
supply water simultaneously to any one section and to the surfaces specified in 11.3.1.3 and .4. Alternatively, the main fire pumps may be used for this
service provided that their total capacity is increased by the amount needed for the
spray system. In either case, a connection, through a stop valve, should be made between
the fire main and water spray main outside the cargo area.
11.3.4 Subject to the approval
of the Administration, water pumps normally used for other services
may be arranged to supply the water spray main.
11.3.5 All pipes, valves,
nozzles and other fittings in the water spray systems should be resistant
to corrosion by seawater, for which purpose galvanized pipe, for example,
may be used, and to the effect of fire.
11.3.6 Remote starting of
pumps supplying the water spray system and remote operation of any
normally closed valves in the system should be arranged in suitable
locations outside the cargo area, adjacent to the accommodation spaces
and readily accessible and operable in the event of fire in the areas
protected.