3.9.1 For the carriage of flammable liquids identified
in appendix 1, the requirements
for tankers in chapter II-2 of the
1974 SOLAS Convention, as amended, should apply to vessels covered
by the Guidelines, irrespective of tonnage, including vessels of less
than 500 tons gross tonnage, except that:
-
.1 Regulations 4.5.5, 10.8 and 10.9 should not
be applied;
-
.2 Regulation 4.5.1.1 (i.e., positioning of machinery
spaces aft of cargo tanks, slop tanks, cargo pump-rooms and cofferdams),
Regulation 4.5.1.2 (i.e., the requirements for location of the main
cargo control station), Regulations 4.5.1.4, 4.5.2.1 to 4.5.2.3 need
not be applied. Additionally, Regulation 9.2.4.2.5 need not be applied
provided that the exterior boundaries of superstructures and deckhouses
enclosing accommodation and including any overhanging decks which
support such accommodation are spaced at least 7 m away from the cargo
area. The insulation of such boundaries should however be to the satisfaction
of the Administration;
-
.3 with regard to Regulation 9.2.4.1, the Administration
may permit use of a method other than IC as defined in Regulation
9.2.3.1.1.1 where considered appropriate;
-
.4 the requirements of Regulation 9.2.3 may be
applied in lieu of those in Regulation 9.2.4.2, where considered appropriate
by the Administration;
-
.5 the provisions of Regulations 4.5.3, 4.5.4
and 4.5.6 to 4.5.8 need be applied only where considered appropriate
by the Administration, taking into account the requirement in 3.6.2 of the Guidelines that cargo
tank vent systems should meet the relevant requirements of the International
Bulk Chemical Code;
-
.6 regulations 10.2, 10.4 and 10.5, except regulation
10.5.6, should apply as they would apply to tankers of 2,000 gross
tonnage and over;
-
.7 the provisions of 3.9.2.3 should be applied
in lieu of Regulation 10.8; and
-
.8 the provisions of 3.9.2.5 should be applied
in lieu of Regulation 10.9.
3.9.2 The following provisions also apply for
the carriage of flammable liquids identified in appendix 1:
-
.1 During cargo transfer, water pressure should
be maintained on the fire main system.
-
.2 Fire hoses, fitted with approved dual-purpose
nozzles (i.e. spray/jet type with a shutoff), should be attached to
each fire hydrant in the vicinity of the flammable liquid to be carried.
-
.3 Either a fixed deck foam system or a fixed
fire-extinguishing system of the dry chemical type complying with
the following:
-
.3.1 the system should be located to protect the
deck within the cargo area;
-
.3.2 the system should be capable of covering
the deck within the cargo area without being moved;
-
.3.3 when a fixed deck foam system is provided,
it should comply with the requirements of 11.3.3
to 11.3.12 of the International Bulk Chemical Code. Only foam
suitable for the products carried should be used.
-
.3.4 Administrations may approve a fixed fire-extinguishing
system provided that:
-
.3.4.1 on a deck area of 45 m2 or less,
there are two or more dry chemical extinguishers whose total capacity
is not less than 135 kg;
-
.3.4.2 on a deck areas of more than 45 m2,
there are three or more dry chemical extinguishers whose total capacity
of extinguishing agent is not less than:
where A is the deck area (in square metres);
-
.3.4.3 the minimum rate of supply of the extinguishing
agent is not less than 3 kg/min.
-
.4 An alternative to the systems required in 3.9.2.3
above may be approved in accordance with the procedures contained
in SOLAS regulation II-2/17.
-
.5 The cargo pump-room where flammable liquids
are handled should be provided with a fixed fire-extinguishing system
in accordance with 11.2 of the International
Bulk Chemical Code.
3.9.3 For vessels which carry only liquids identified
as non-flammable in appendix 1,
the fire-fighting requirements should be to the satisfaction of the
Administration.