In addition to the requirements in section 3, systems designed
with this approach should comply with paragraphs 5.1 to 5.6.
5.1 The system should be capable of fire suppression
and control and be tested to the satisfaction of the Administration
in accordance with the appendix to these Guidelines.
5.2 The nozzle location, type of nozzle and nozzle
characteristics should be within the limits tested to provide fire
suppression and control as referred to in paragraph 5.1.
5.3 System designs should be limited to the use
of the maximum and minimum temperature ratings of the thermally sensitive
fire detection devices tested to provide fire suppression and control
as referred to in paragraph 5.1.
5.4 The capacity of the system water supply should
be sufficient for the total simultaneous coverage of the minimum coverage
area of table 5-1 and the vertically applicable area as defined in
paragraph 3.22, and the requirements of paragraph 5.5.
Table 5-1 Minimum coverage area
per type of system
Type of system (Definition number)
|
Minimum coverage area
|
A. Wet pipe, automatic sprinkler heads
(2.18)
|
280 m2 or area of operation as
defined in the fire tests – whichever is larger
|
B. Deluge system, automatic1 and
manual release (2.4)
|
280 m2 and the overlapping or adjacent
section as defined by paragraph 5.5 2
|
C. Deluge system, manual release (2.5)
|
2 sections each of min 20 m x B 2,3
|
D. Other systems (2.6, 2.15)
|
Equivalent to the above systems and to the
satisfaction of the Administration
|
1
The automatic release should comply
with the requirements of paragraph 5.6.
2
The pump should be sized to cover
the largest section for type B systems and the two largest horizontally
adjacent sections for type C systems.
3
B = full breadth of the protected
space.
5.5 The section arrangement for a deluge system
with automatic and manual release (system B) should be such that a
fire in any location of the border zone between two or more sections
would be completely surrounded by activated spray heads, either by
activating more than one section or by overlapping sections (whereby
two or more sections cover the same area in the vicinity of the border
between sections). In case of overlapping sections, such overlap should
be a minimum of two times the required spray head spacing of the section
in question or five metres, whichever is larger. These overlapping
sections need not comply with the minimum width and length requirements
of paragraph 3.24.
5.6 For systems of type B (see table 5-1) an efficient
fire detection and fire confirmation system covering all parts of
the ro-ro or special category spaces should be provided as follows:
-
.1 the fire detection system shall consist of
flame detectors and smoke detectors of approved types. The flame detectors
shall be installed under fixed continuous decks according to the limitation
and application defined by the maker and the approval certificate.
The smoke detector arrangement shall comply with the FSS
Code. Additional smoke detectors with a spacing not exceeding
11 m shall be installed under hoistable ramps;
-
.2 a colour TV monitoring system should cover
all parts of the ro-ro or special category spaces. Cameras need not
be installed below hoistable decks if the camera arrangement can identify
smoke (confirm fire) based on positions under a fixed continuous deck;
and
-
.3 the relevant section of the deluge system should
be automatically released when two detectors covering this area activate.
Systems being released when only one detector activates may also be
accepted. Automatically released systems should also be capable of
manual operation (both opening and closing) of the section valves.
The automatic release may be disconnected during on- and off-loading
operations, provided that this function is automatically reconnected
after a preset time being appropriate for the operations in question.