Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC/Circular.1165 – Revised Guidelines for the Approval of Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces and Cargo Pump-Rooms – (10 June 2005)Amended by MSC.1/Circular.1237Amended by MSC.1/Circular.1269Amended by MSC.1/Circular.1386 - Annex - Revised Guidelines for the Approval of Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces and Cargo Pump-Rooms - Appendix B - Test Method for Fire Testing Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms - 5 Classification Criteria

5 Classification Criteria

5.1 Fire-extinguishing tests

 All fires in the fire-extinguishing tests should be extinguished within 15 minutes of system activation and there should be no re-ignition or fire spread.

5.2 Thermal management tests

 The 60 s time-weighted average temperature should be kept below 100°C, no later than 300 s after activation of the system for the thermal management test in 4.3.2.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.