7.3.1 The electrical power for the regasification system shall be provided by
an individual dedicated circuit from the main switchboard.
7.3.2 Where the ✠Lloyd’s RGP+ Notation is assigned, the system shall be
provided by two individual circuits separated in the main switchboard or section
board and throughout its length and without the use of common feeders. Where a
stand-by unit is provided, it shall be supplied from a separate section of the main
switchboard to ensure a single point equipment failure does not render both systems
inoperable.
7.3.3 Electrical equipment for the regasification system shall be suitable for
use in the environmental conditions envisaged during regasification mode. It is also
to be appropriately installed to prevent any adverse effects due to environmental
conditions encountered when not in use.