10.3.1 The requirements for uninterruptible power systems are given in IEC
61892-3:2012, Mobile and fixed offshore units – Electrical installations – Part
3: Equipment, Sections 8 and 9, and Pt 6, Ch 2, 10.3 Uninterruptible power systems of the Rules for Ships, which are to be complied
with. Additions or amendments to these requirements are given in the following
paragraph(s) of this sub-Section.
10.3.2 UPS units are to comply with the requirements of IEC 62040,
Uninterruptible power systems (UPS) – Part 1: General and safety requirements
for UPS, or alternative relevant International or National Standard amended
where necessary for ambient temperature, see
Pt 6, Ch 2, 1.9 Ambient reference and operating conditions.
10.3.4 An external bypass, that is hardwired and manually operated, is to be
provided to the UPS system, to allow for isolation of the UPS for safety during
maintenance and maintain continuity of load power. When the UPS is operating in
either normal or by-pass mode it must be ensured that there are no multiple system
earths.