Both fire scenarios include hidden fires that burn intensely
throughout the tests. The suppression tests as defined in paragraph
3.6.1 can be applied in establishing the area of operation of wet
pipe, dry pipe and pre-action systems. The evaluation is based on
the test with the largest number of nozzles activating.
The ceiling area of 100 m2 as defined in paragraph
3.3.1 most likely is not sufficient for defining the area of operation.
The ceiling should be large enough to allow installation of a sufficient
number of nozzles so that it is unambiguous that the nozzles activating
truly represent the maximum number of active nozzles.
The area of operation is determined by multiplying the largest
number of nozzles activating in the tests by two and defining the
corresponding coverage area.