5.7.1 Air pipes serving fuel and other tanks should
be of efficient construction and provided with permanently attached
means of weathertight closure. Means of closure may be omitted if
it can be shown that the open end of an air pipe is afforded adequate
protection by other structure(s) which will prevent the ingress of
water.
5.7.2 Where located on the weather deck, air pipes
should be kept as far inboard as practicable and be fitted with a
coaming of sufficient height to prevent inadvertent flooding. Generally,
air pipes to tanks should have a minimum coaming height of:
Location
|
Unrestricted Yachts
|
Short Range Yachts
|
On weather deck
|
760mm
|
380mm
|
Elsewhere
|
450mm
|
225mm
|
5.7.3 Air pipes to fuel tanks should terminate
at a height of not less than 760mm above either, the top of the filler
pipe for a gravity filling tank or, the top of the overflow tank for
a pressure filling tank.