General
1 The definitions below are intended to be used for the application of part B-1 only.
2 In regulation 7-1, the words "compartment" and "group of compartments" should be
understood to mean "zone" and "adjacent zones".
3 Zone – a longitudinal interval of the ship within the subdivision length.
4 Room – a part of the ship, limited by bulkheads and decks, having a specific
permeability.
5 Space – a combination of rooms.
6 Compartment – a space within watertight boundaries.
7 Damage – the three-dimensional extent of the breach in the ship.
8 For the calculation of p, v, r and b only the
damage should be considered, for the calculation of the s-value the flooded space
should be considered. The figures below illustrate the difference.

Regulation 7-1.1.1
1 The coefficients b11, b12, b21
and b22 are coefficients in the bi-linear probability density function
on normalized damage length (J). The coefficient b12 is
dependent on whether Ls is greater or less than L* (i.e. 260
m); the other coefficients are valid irrespective of Ls.
Longitudinal subdivision
2 In order to prepare for the calculation of index A, the ship's subdivision
length Ls is divided into a fixed discrete number of damage zones.
These damage zones will determine the damage stability investigation in the way of
specific damages to be calculated.
3 There are no specific rules for longitudinally subdividing the ship, except
that the length Ls defines the extremities of the zones. Zone
boundaries need not coincide with physical watertight boundaries. However, it is
important to consider a strategy carefully to obtain a good result (that is a large
attained index A). All zones and combination of adjacent zones may contribute to
the index A. In general it is expected that the more zone boundaries the ship is
divided into the higher the attained index will be, but this benefit should be balanced
against extra computing time. The figure below shows different longitudinal zone
divisions of the length Ls.

4 The first example is a very rough division into three zones of
approximately the same size with limits where longitudinal subdivision is established.
The probability that the ship will survive a damage in one of the three zones is
expected to be low (i.e. the s-factor is low or zero) and, therefore, the total
attained index A will be correspondingly low.
5 In the second example the zones have been placed in accordance with the watertight
arrangement, including minor subdivision (as in double bottom, etc.). In this case there
is a much better chance of obtaining higher s-factors.
6 Where transverse corrugated bulkheads are fitted, they may be treated as equivalent
plane bulkheads, provided the corrugation depth is of the same order as the stiffening
structure.
7 This explanatory note only applies to ships for which the building
contract is placed on or after 1 January 2020 and which are constructed before 1
January 2024. Pipes and valves directly adjacent or situated as close as
practicable to a transverse bulkhead can be considered to be part of the bulkhead, or
deck, provided the separation distance on either side of the bulkhead is of the same
order as the bulkhead stiffening structure. The same applies for small recesses, drain
wells, etc.
8 This explanatory note only applies to ships constructed on or after 1
January 2024. Pipes and valves directly adjacent or situated as close as
practicable to a transverse bulkhead can be considered to be part of the bulkhead,
provided the separation distance on either side of the bulkhead is of the same order as
the bulkhead stiffening structure. The same applies for small recesses, drain wells,
etc. In no case should the separation distance on either side of the bulkhead or deck be
more than 450 mm measured from the valve's near end to the bulkhead or deck.

9 For cases where the pipes and valves cannot be considered as being part of
the transverse bulkhead, when they present a risk of progressive flooding to other
watertight compartments that will have influence on the overall attained index A,
they should be handled either by introducing a new damage zone and accounting for the
progressive flooding to associated compartments or by introducing a gap.
10 The triangle in the figure below illustrates the possible single and
multiple zone damages in a ship with a watertight arrangement suitable for a seven-zone
division. The triangles at the bottom line indicate single zone damages and the
parallelograms indicate adjacent zones damages.

11 As an example, the triangle illustrates a damage opening the rooms in
zone 2 to the sea and the parallelogram illustrates a damage where rooms in zones 4, 5
and 6 are flooded simultaneously.
12 The shaded area illustrates the effect of the maximum absolute damage
length. The p-factor for a combination of three or more adjacent zones equals
zero if the length of the combined adjacent damage zones minus the length of the
foremost and the aft most damage zones in the combined damage zone is greater than the
maximum damage length. Having this in mind when subdividing Ls could
limit the number of zones defined to maximize the attained index A.
13 As the p-factor is related to the watertight arrangement by the
longitudinal limits of damage zones and the transverse distance from the ship side to
any longitudinal barrier in the zone, the following indices are introduced:
j: the damage zone number starting with
No.1 at the stern;
n: the number of adjacent damage
zones in question where j is the aft zone;
k: the number of a particular longitudinal bulkhead as a
barrier for transverse penetration in a damage zone counted from
shell towards the centreline. The shell has No.0;
K: total number of transverse penetration
boundaries;
pj,n,k: the
p-factor for a damage in zone j and next (n-1) zones
forward of j damaged to the longitudinal bulkhead
k.
|
|
Pure longitudinal subdivision
Single damage
zone, pure longitudinal subdivision:
|
|
Two adjacent
zones, pure longitudinal subdivision:
- pj,2 =
p(x1j,x2j+1) -
p(x1j,x2j) -
p(x1j+1,x2j+1)
|
|
Three or more
adjacent zones, pure longitudinal subdivision:
- pj,n =
p(x1j,x2j+n-1) -
p(x1j,x2j+n-2) -
p(x1j+1,x2j+n-1) +
p(x1j+1,x2j+n-2)
|
|
Regulation 7-1.1.2
Transverse subdivision in a damage zone
1 Damage to the hull in a specific damage zone may just penetrate the ship's
watertight hull or penetrate further towards the centreline. To describe the probability
of penetrating only a wing compartment, a probability factor r is used, based
mainly on the penetration depth b. The value of r is equal to 1, if the
penetration depth is B/2 where B is the maximum breadth of the ship at the
deepest subdivision draught ds, and r = 0 if b = 0.
2 The penetration depth b is measured at level deepest subdivision draught
ds as a transverse distance from the ship side right-angled to
the centreline to a longitudinal barrier.
3 Where the actual watertight bulkhead is not a plane parallel to the shell,
b should be determined by means of an assumed line, dividing the zone to the
shell in a relationship b1/b2 with 1/2 ≤
b1 /b2 ≤ 2 .
4 Examples of such assumed division lines are illustrated in the figure below. Each
sketch represents a single damage zone at a water line plane level ds
and the longitudinal bulkhead represents the outermost bulkhead position below
ds + 12.5 m.

4.1 If a transverse subdivision intercepts the deepest subdivision draught
waterline within the extent of the zone, b is equal to zero in that zone for that
transverse subdivision [see figure 1]. A non-zero b can be obtained by including
an additional zone, see figure 2.

4.2 If the deepest subdivision draught waterline on the side of a single
hull ship includes a part where multiple transverse (y) coordinates occur for a
longitudinal (x) location, a straightened reference waterline can be used for the
calculation of b. If this approach is chosen, the original waterline is replaced
by an envelope curve including straight parts perpendicular to the centreline where
multiple transverse coordinates occur [see figures 1 to 4]. The maximum transverse
damage extent B/2 should then be calculated from waterline or the reference
waterline, if applicable, at the deepest subdivision draught.

5 In calculating r-values for a group of two or more adjacent compartments, the
b-value is common for all compartments in that group, and equal to the
smallest b-value in that group:
Accumulating p
6 The accumulated value of p for one zone or a group of adjacent
zones is determined by:

7 The figure above illustrates b's for adjacent zones. The zone j has two
penetration limits and one to the centre, the zone j+1 has one b
and the zone j+n-1 has one value for b. The multiple zones will
have (2+1+1) four values of b, and sorted in increasing order they are:
-
(bj,1 ; bj+1,1 ; bj+n-1,1
; bj,2 ; bK)
8 Because of the expression for r(x1, x2, b) only one bK should
be considered. To minimize the number of calculations, b's of the same value may
be deleted.
-
As bj,1 = bj+1,1 the final b's
will be (bj,1 ; bj+n-1,1 ; bj,2 ;
bK)
Examples of multiple zones having a different b
9 Examples of combined damage zones and damage definitions are given in the figures
below. Compartments are identified by R10, R12, etc.

- Figure: Combined damage of zones 1 + 2 + 3 includes a limited
penetration to b3, taken into account generating two damages:
- 1) to b3
with R10, R20 and R31 damaged;
- 2) to B/2 with R10,
R20, R31 and R32 damaged.

- Figure: Combined damage of zones 1 + 2 + 3 includes 3 different
limited damage penetrations generating four damages:
- 1) to b3 with R11, R21 and R31
damaged;
- 2) to b2 with R11, R21, R31 and
R32 damaged;
- 3) to b1 with R11, R21, R31, R32,
and R22 damaged;
- 4) to B/2 with R11, R21, R31, R32, R22 and
R12 damaged.

- Figure: Combined damage of zone 1 + 2 + 3 including 2 different
limited damage penetrations (b1 < b2 =
b3) generating three damages:
- 1) to b1 with R11, R21 and R31
damaged;
- 2) to b2 with R11, R21, R31 and R12
damaged;
- 3) to B/2 with R11, R21, R31, R12, R22 and R32
damaged.
10 A damage having a transverse extent b and a vertical extent
H2 leads to the flooding of both wing compartment and hold;
for b and H1 only the wing compartment is flooded. The figure
below illustrates a partial subdivision draught dp damage.

11 The same is valid if b-values are calculated for arrangements with
sloped walls.
12 This explanatory note only applies to ships for which the building
contract is placed on or after 1 January 2020 and which are constructed before 1
January 2024. Pipes and valves directly adjacent or situated as close as
practicable to a longitudinal bulkhead can be considered to be part of the bulkhead,
provided the separation distance on either side of the bulkhead is of the same order as
the bulkhead stiffening structure. The same applies for small recesses, drain wells,
etc.
13 This explanatory note only applies to ships constructed on or after 1
January 2024. Pipes and valves directly adjacent or situated as close as
practicable to a longitudinal bulkhead can be considered to be part of the bulkhead,
provided the separation distance on either side of the bulkhead is of the same order as
the bulkhead stiffening structure. The same applies for small recesses, drain wells,
etc. In no case should the separation distance on either side of the bulkhead or deck be
more than 450 mm measured from the valve's near end to the bulkhead or deck.
