9.13.1 A fixed automatic hydrogen sulphide gas detection
and alarm system should be provided to the satisfaction of the Administration so
arranged as to monitor continuously the drilling area, mud processing area and well
fluid test area of the unit and capable of giving audible and visual alarm at the main
control points. If the alarm at the main control point is unanswered within 2 min, the
toxic gas (hydrogen sulphide) alarm and the helideck status light under paragraph
13.5.25 should be automatically activated.
9.13.2 At least two portable hydrogen sulphide gas
monitoring devices should be provided on the unit.