10.1 Subject to V/10.2, the following
spaces shall be equipped with a fixed gas or other fixed fire extinguishing
system approved by the Administration.
-
.1 a space containing an internal combustion engine
of more than 37 kW (50 hp);
-
.2 a space containing an oil fired boiler;
-
.3 a space containing machinery powered by gasoline
or other fuels having a flash point of 43 °C (110 °F) or lower;
-
.4 a space containing a fuel tank for gasoline
or any other fuel having a flash point of 43 °C (110 ° F)
or lower;
-
.5 a space containing a combustible cargo or vessel’s
stores inaccessible during the voyage;
-
.6 a paint locker; and
-
.7 a storeroom containing flammable liquids, including
liquors of 80 proof or higher where liquor is packaged in individual
containers of 9.5 liters (2.5 gallons) capacity or greater.
10.2 A fixed fire extinguishing system in accordance
with regulation V/10.1 is not required in a space where:-
-
.1 the space is open to the atmosphere and the
Administration determines that a fixed gas fire extinguishing system
would be ineffective; or
-
.2 the amount of carbon dioxide gas required in
a fixed fire extinguishing system can be supplied by one portable
extinguisher or a semi-portable extinguisher meeting the following
requirements:
-
.1 cylinders shall be installed in a fixed position
outside the space protected;
-
.2 the applicator shall be installed in a fixed
position so as to discharge into the space protected;
-
.3 controls shall be installed in an accessible
location outside the space protected.
10.3 Except where the space is manned, the following
spaces shall be equipped with a fire detecting system of an approved
type that is installed to the satisfaction of the Administration:
-
.1 a space containing propulsion machinery;
-
.2 a space containing an internal combustion engine
of more than 37 kW (50 hp);
-
.3 a space containing an oil fired boiler;
-
.4 a space containing machinery powered by gasoline
or any other fuels having a flash point of 43 °C (110 °F)
or lower;
-
.5 a space containing a fuel tank for gasoline
or any other fuel having a flash point of 43 °C (110 °F) or
lower; and
-
.6 each overnight accommodation space on a vessel
with overnight accommodation for passengers.
10.4 When a fixed fire extinguishing system, which
is not a portable extinguisher, is installed in a machinery space,
it shall be of a type approved by the Administration or equivalent
and appropriate to the space to be protected.
Such fixed installation systems in machinery spaces include:-
10.5 All grills, broilers, and deep fat fryers
shall be fitted with a grease extraction hood to the satisfaction
of the Administration.
10.6 A fixed gas fire extinguishing system may
protect more than one space. The quantity of extinguishing agent
shall be at least sufficient for the space requiring the greatest
quantity.