The fire tests should be conducted inside a well-ventilated
fire test hall as described in item 4.4 under a suspended rectangular
ceiling of at least 80 m2 in area with no dimensions less
than 8 m. There should be at least 1 m space between the perimeters
of the ceiling and any wall of the test hall. The ceiling height should
be set at 2.5 m and 5 m, respectively.
The ceiling should be horizontal and smooth to allow an
unobstructed horizontal flow of gases across the whole ceiling. No
lintel is allowed around the perimeter of the ceiling and no opening
is permitted in the ceiling. In order to be considered as smooth,
the surface structure of the suspended ceiling should not have obstructions
deeper than 15 mm.
The volume above the suspended ceiling, should be large
enough, or be fitted with a natural or mechanical ventilation system,
to vent the combustion gases away from the fire test area.
Details of the ceiling structure and its location in the
fire test hall should be given in the fire test report.
Two different tests should be conducted as per paragraphs
6.1.1 and 6.1.2.