4.1.2 The
equipment used in HVAC systems is to be provided with local control
and monitoring arrangements.
4.1.3 Where
isolation of equipment or systems can be carried out, means of indicating
the status of isolation is to be provided at positions where the equipment
and system can be operated and monitored.
4.1.4 Instrumentation
to indicate the operational status of running and any standby equipment
is to be provided locally and at any control station.
4.1.5 All
pumps are to be provided with an indication of discharge pressure
and a low discharge pressure alarm at each control station.
4.1.6 The
power to all independently driven ventilation fans is to be capable
of being stopped from position(s) outside the fire boundary which
will always be readily accessible in the event of fire occurring in
any space, as well as from the local control panel.
4.1.8 Ventilation
air heating/cooling plants are to be provided with the following instrumentation
and alarms as applicable:
-
Indication of
heating/cooling medium temperature.
-
Indication of
delivery air temperature.
4.1.9 Filter
units for ventilation systems for crew and embarked personnel installations
are to be provided with the following instrumentation and alarms:
-
Indication of
differential air pressure across the filter unit.
-
High differential
air pressure alarm.