8.1.2 Mounting
                                 arrangements are to take account of forces and moments generated at
                                 the supports. Mounting arrangements are to take account of thermal
                                 expansion and contraction.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.3 Access
                                 is to be provided for inspection and checking of mountings, fittings,
                                 controls and pressure-relief devices.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.4 Arrangements
                                 are to allow the pressure settings of pressure-relief devices to be
                                 checked.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.5 Where
                                 provision is made to isolate pressure-relief devices from pressure
                                 vessels for maintenance purposes, at least two such pressure-relief
                                 devices are to be fitted. The isolating or blocking valves are to
                                 be arranged such that at least one pressure-relief device remains
                                 operational at all times.