1.2.2 Units complying with the requirements of this Chapter and the relevant
Parts of the Rules will be eligible for the assignment of one of the following class
notations as applicable:
-
Fire-fighting unit 1 (total monitor discharge capacity in brackets).
-
Fire-fighting unit 2 (total monitor discharge capacity in brackets).
-
Fire-fighting unit 3 (total monitor discharge capacity in brackets).
-
Fire-fighting unit 1 (total monitor discharge capacity in brackets)
with water spray.
-
Fire-fighting unit 2 (total monitor discharge capacity in brackets)
with water spray.
-
Fire-fighting unit 3 (total monitor discharge capacity in brackets)
with water spray.
1.2.3 The notation
Fire-fighting unit 1 or
Fire-fighting unit 2
or
Fire-fighting unit 3 signifies that a unit complies with these Rules and
is provided with the appropriate firefighting equipment described in
Pt 3, Ch 5, 1.2 Class notations 1.2.3, with the total discharge capacity of
monitors in m
3/h shown in brackets.
Table 5.1.1 Fire-fighting
equipment
Equipment
|
Fire-fighting unit
|
1
|
2
|
3
|
Minimum total pump
capacity, m3/h
|
2400
|
7200
|
10000
|
Minimum number of water
monitors
|
2
|
3
|
4
|
Minimum discharge rate per
monitor, m3/h
|
1200
|
1800
|
1800
|
Minimum height of
trajectory of jets of monitors above sea level, metres
|
45
|
70
|
70
|
Minimum range of monitor
jets, metres
|
120
|
150
|
150
|
Minimum fuel capacity for
monitors, hours
|
24
|
96
|
96
|
Number of hose connections
each side of unit
|
4
|
8
|
8
|
Number of fireman’s outfits
|
4
|
8
|
8
|
1.2.4 The addition of the words with water spray to the notations
referred to in Pt 3, Ch 5, 1.2 Class notations 1.2.3 signifies that a unit is provided with a water
spray system which will provide an effective cooling spray of water over the
vertical surfaces of the unit to enable it to approach a burning installation for
firefighting purposes. The requirements for such a system are set out in Pt 3, Ch 5, 4 Fire protection.