Section
4 Requirements for section analyses
4.1 General
4.1.1 Although recognising that the selected concrete Code or Standard will
have requirements for acceptance of design and detailing for the various limit
states, the additional items outlined in this Section should also be complied
with.
4.2 Analysis of sections for ULS
4.2.1 The material partial factor, , for reinforcement and pre-stressing strand should not be less
than 1,15, irrespective of the Code or Standard selected.
4.2.2 In assessing panel members for buckling, adequate allowance is to be
made for local and global geometric tolerances. Panels are to be assessed for a
hydrostatic head based on the maximum still water draught together with the maximum
wave pressures.
4.2.3 When considering shear close to supports, favourable arch effects are to
be ignored when fluid pressure is acting in the cracks.
4.2.4 Where the shear failure mechanism is not well defined, the design is to
be based on principal tensile stresses.
4.2.5 It is acceptable to include the positive effects of both compressive
axial load and pre-stress when calculating shear resistance. However, it is
considered that shear cracking prior to the ULS should be avoided and the
appropriate method of calculation is to be adopted.
4.2.6 Where in-plane deformation forces (excluding pre-stressing) enhance the
transverse shear capacity, they should be neglected. This may necessitate performing
shear checks both with and without certain deformation loads, e.g. temperature.
4.2.7 Where temperature effects are significant and/or where lightweight
concrete is used, the coefficient of temperature expansion, ∝, should be obtained by
testing.
4.2.8 If the loading pattern of the cargo can result in significant torsion,
these effects should be considered in the design.
4.3 Analysis of sections for SLS
4.3.1 Particular attention is to be given to design, detailing and
construction of the large concrete areas in the splash zone.
4.3.2 The following crack width limits assume a formula similar to CEB/FIP
recommendations. Equivalence should be demonstrated where the method of calculating
crack widths is significantly different from that assumed.
4.3.3 Based on the normal serviceability condition (as defined in Table 2.3.1 Load factors and combinations
for use with characteristics loads in Pt 9, Ch 2 Loads and Load Combinations) the calculated crack widths should satisfy
the requirements in Table 3.4.1 Zonal crack width
limits. External to
the hull, the splash zone should be considered to extend from 3,0 m below the
lightship draught up to the deck level. For units subject to green seas on deck and
frequent sea spray, the top deck surface should also be considered as the splash
zone. The interior of ballast tanks are also to be designed on the same basis as the
splash zone.
Table 3.4.1 Zonal crack width
limits
|
Crack width
|
Submerged zone
|
0,4 mm
|
Splash zone
|
0,2 mm
|
Atmospheric zone
|
0,4 mm
|
4.3.4 Allowance is to be made in the crack width calculations for deformation
strains (temperature) to be concentrated at the cracked face of sections and
increase the concrete crack width. The practice of using a strain twice the
elastically calculated strain is acceptable.
4.3.5 For construction, transportation and installation, the crack widths
shall not exceed 0,6 mm.
4.3.6 The minimum reinforcement quantities required to control cracking should
be as given below, irrespective of the requirements of the selected Code or
Standard. The calculations are for the area of reinforcement to be provided in each
face and each direction:
- for concrete sections required to be watertight or oiltight:
ftm, fy, w, b and de
as defined in Pt 9, Ch 3, 1.2 Symbols
0,2 < < 0,5 (h – x)
- for other sections:
k = 0,4 for h ≤ 0,3 m
k = 0,25 for h ≥ 0,8 m
linear
interpolation for 0,3 m < h < 0,8 m.
4.3.7 In areas of the structure adjacent to the sea which are intended to be
watertight/oiltight, through thickness cracks are to be avoided under normal
serviceability conditions. In general, this is to be achieved by strictly
maintaining a ‘no tension’ criterion for in-plane membrane forces for this
condition.
4.3.8 A ‘modified’ serviceability condition shall be analysed for the extreme
environmental condition as detailed in Note 1(b) of Table 2.2.1 Basis for selection of return
periods for environmental loads in Pt 9, Ch 2 Loads and Load Combinations. This is to ensure that:
- the hull in contact with either sea-water and/or oil is to be
designed so that, under any combination of loading, no tensile membrane
stresses of a magnitude sufficient to cause cracking across the full
thickness of the section can occur. Some flexural tensile stresses, however,
may be unavoidable, but these are acceptable providing a compression zone of
at least 200 mm is maintained;
- for the extreme environmental condition, the stress in the
reinforcement is to be restricted to 0,85
and the compressive stress in the concrete to 0,5 .
4.4 Analysis of sections for FLS
4.4.1 All stress variations imposed on the structure during its design life
are to be considered in the fatigue evaluation. Account should be taken of the range
of operating draughts and cargo filling/emptying cycles if significant.
4.4.2 A fatigue evaluation is to be carried out for the critical areas of the
structure. It is expected this will be based on linear cumulative damage (Palmgren –
Miner’s Rule). The material partial factors and characteristic fatigue strength
relationships (S-N curves) are to be appropriate for the selected Code or Standard,
and should account for air and water locations, stress state and reinforcement
diameter.
4.4.3 The dynamic behaviour of the unit is to be investigated to determine
whether the increase in load effects due to dynamic amplification is important. If
dynamic effects are considered significant then a response analysis is to be carried
out.
4.4.5 Where large compression or compression/tension stress ranges occur (e.g.
hull bottom), consideration is to be given to appropriate design and detailing.
Confinement reinforcement is to be provided to ensure ductile behaviour. As far as
practicably possible, cycling into the tension range should be avoided.
4.4.6 It should be demonstrated that the design and detailing of penetrations,
openings and access ways consider the increased cyclic nature of loading on floating
concrete units compared to fixed offshore structures.
4.5 Analysis of sections for PCLS
4.5.1 In general, for accidental or abnormal loads, it should be documented
that the strength or the ductility of the structure is sufficient for the applied
loads.
4.5.2 For impact and explosive loads, account can be taken of increased
material strength and modulus in accordance with the selected Code or Standard.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
![](LR-FooterLogo.png) |
|