Section 6 Instrumentation, control, alarm and monitoring
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules and Regulations for the Classification of Offshore Units, July 2022 - Part 11 Production, Storage and Offloading of Liquefied Gases in Bulk - Chapter 20 Barges and Offshore Units Equipped with Regasification - Section 6 Instrumentation, control, alarm and monitoring

Section 6 Instrumentation, control, alarm and monitoring

6.1 Functional objectives

6.1.1  The regasification plant and sub-systems shall be provided with appropriate controls for safe operation of the regasification system with adequate alerts and safeguards.

6.2 Performance requirements

6.2.1  Instrumentation, control, alarm and monitoring systems shall comply with the requirements of this Section and Pt 6 Control and Electrical Engineering.

6.2.2  The system shall be provided with automatic and/or remote controls to ensure the system operates within its design parameters.

6.2.3  A system for monitoring and indicating alerts shall be provided.

6.2.4  The system shall be provided with safeguards such as a high pressure trip, which will operate to prevent a hazard occurring or to reduce an existing hazard to persons, machinery, the barge or offshore unit or the environment.

6.2.5  Locations at which the regasification system is controlled shall be provided with a means of communication with the gas-receiving terminal.

6.2.6  The regasification system shall be provided with control, monitoring, alert and safety systems that will maintain the system throughout all normal and reasonably foreseeable abnormal conditions.

6.2.7  The system shall be provided with the alarms and shutdowns as identified by the system designer or equipment manufacturer. In the absence of such guidance, the alarms and shutdowns indicated in these Rules may be used.

6.3 Control station

6.3.1  A control station for the regasification system and barge or offshore unit-to-ship operations shall be arranged within a non-hazardous area. Emergency procedures, as defined in Pt 11, Ch 20, 3 Risk based analysis, concerning regasification and barge or offshore unit-to-ship transfer operations shall be capable of being performed from this station.

6.4 Communications

6.4.1  At least two means of communication shall be provided between the control station and the receiving terminal; one of these systems shall be independent of the main electrical supply.

6.4.2  Internal communication cables shall comply with the applicable requirements of these Rules.

6.4.3  The cable installation shall provide adequate protection against mechanical damage and electromagnetic interference.

6.4.4  Components shall be located with appropriate segregation such that the risk of mechanical damage or electromagnetic interference resulting in the loss of both active and stand-by components is minimised. Duplicated communication links and equipment shall be routed to give as much physical separation as is practicable.

6.5 Equipment and systems – Alarms, shutdowns and safeguards

6.5.1  Suitable interlocks shall be provided to prevent start-up of the regasification system under conditions which could hazard the system or its equipment and components.

6.5.2  The system designer or equipment manufacturer shall identify the required alarms, shutdowns and safeguards for the design of vaporiser. The minimum shutdown requirements are indicated in Table 20.6.1 Alarms, shutdowns and safeguards for vaporisers.

6.5.3  The system designer or equipment manufacturer shall identify required alarms, shutdowns and safeguards for the suction drum. The minimum shutdowns requirements are indicated in Table 20.6.2 Alarms, shutdowns and safeguards for suction drums.

6.5.4  The control and monitoring arrangements shall be appropriate to enable the system to be controlled within the design parameters specified by the system designer or equipment manufacturer.

Table 20.6.1 Alarms, shutdowns and safeguards for vaporisers

Item Alarm Note
Gas discharge temperature Very Low Automatic shutdown
Sea-water (or heating medium) supply pressure Very Low Automatic shutdown
Indication of supply gas pressure to burner (SCV type) Very Low Automatic shutdown
Flame failure (SCV type) Failure Automatic shutdown
Indication of sump water level (SCV type) Very Low Automatic shutdown
Combustion air pressure (SCV type) Low Automatic shutdown
High Automatic shutdown
Flue gas temperature (SCV type) High Automatic shutdown
Gas leak detected   ESD operation (programmed)

NOTES

1. SCV type means submerged combustion vaporiser type.

2. Any additional alarms and shutdowns identified during the Risk Assessment required in Section Pt 11, Ch 20, 3 Risk based analysis are also to be provided.

3. The Table contains the minimum list of alarms and shutdowns for a regasification plant; additional alarms and shutdowns may be necessary as determined through risk-mitigating activities in response to a completed Risk Assessment as required by Section Pt 11, Ch 20, 3 Risk based analysis.

4. If certain alarms and shutdowns are not applicable for the regasification system, sufficient evidence shall be produced to support the claim and shall form part of the Risk Assessment required by Pt 11, Ch 20, 3 Risk based analysis.

Table 20.6.2 Alarms, shutdowns and safeguards for suction drums

Item Alarm Note
Suction drum pressure Low Automatic shutdown
Suction drum level Very low Automatic shutdown
Suction drum level Very high Automatic shutdown

NOTES

1. Any additional alarms and shutdowns identified during the Risk Assessment required by Pt 11, Ch 20, 3 Risk based analysis are also to be provided.

2. The Table contains the minimum list of alarms and shutdowns for a regasification plant; additional alarms and shutdowns may be necessary, as determined through risk-mitigating activities in response to a completed Risk Assessment as required by Pt 11, Ch 20, 3 Risk based analysis.

3. If certain alarms and shutdowns are not applicable for the regasification system, sufficient evidence shall be produced and is to form part of the Risk Assessment required by Pt 11, Ch 20, 3 Risk based analysis.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.