Clasification Society Rules and Regulations - Rules and Regulations for the Classification of Offshore Units, January 2016 - Part 6 CONTROL AND ELECTRICAL ENGINEERING - Chapter 2 Electrical Engineering - Section 7 Switchgear and control gear assemblies |
||
![]() Section 7 Switchgear and control gear assemblies7.1 General requirements7.1.1 The general requirements for switchgear and control gear assemblies and their components are given in IEC 61892-3:2012, Mobile and fixed offshore units – Electrical installations – Part 3: Equipment, Section 7 and Pt 6, Ch 2, 7.1 General requirements of the Rules for Ships, which are to be complied with where applicable. Special consideration shall be given for voltages above 35 kV a.c. and 1,5 kV d.c., Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.1.2 Switchgear and control gear assemblies and their components are to
comply with one of the following Standards amended where necessary for ambient
temperature and other environmental conditions:
7.2 Busbars7.2.1 The requirements for busbars and their connections are given in Pt 6, Ch 2, 7.2 Busbars of the Rules for Ships, which are to be complied with where applicable. 7.3 Circuit-breakers7.3.1 The requirements for circuit-breakers are given in Pt 6, Ch 2, 7.3 Circuit-breakers of the Rules for Ships, which are to be complied with. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.3.2 Circuit-breakers are to comply with one of the following standards
amended where necessary for ambient temperature:
7.4 Contactors7.4.1 The requirements for contactors are given in Pt 6, Ch 2, 7.4 Contactors of the Rules for Ships, which are to be complied with where applicable. 7.5 Creepage and clearance distances7.5.1 The requirements for creepage and clearance distances are given in Pt 6, Ch 2, 7.5 Creepage and clearance distances of the Rules for Ships, which are to be complied with where applicable. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.5.2 For assemblies with a rated voltage of up to and including 1kV, the
requirement of Pt 6, Ch 2, 7.5 Creepage and clearance distances 7.5.1 may met by complying with IEC 60092-302,
Electrical installations in ships – Part 302: Low-voltage switchgear and
controlgear assemblies.
7.5.3 For assemblies with a rated voltage above 1kV, the requirement ofPt 6, Ch 2, 7.5 Creepage and clearance distances 7.5.1 of the Rules of Ships may be met by
complying with IEC 60092-503, Electrical installations in ships – Part 503:
Special features – AC supply systems with voltages in the range of above 1 kV up
to and including 15 kV.
An alternative relevant National or International Standard may be used when an acceptable justification is submitted as part of the documentation required by Pt 6, Ch 2, 1.3 Documentation required for supporting evidence 1.3.3. For voltage levels above 15 kV a.c., creepage distances are to comply with manufacturer's recommendations and alternative relevant International or National Standards. 7.5.4 Suitable shrouding or barriers are to be provided in way of connections to equipment, where necessary, to maintain the minimum distances in Pt 6, Ch 2, 7.5 Creepage and clearance distances 7.5.1 in Pt 6, Ch 2, 7.5 Creepage and clearance distances of the Rules for Ships. Suitable bushing is to be provided in way of connections to equipment, where necessary, to comply with IEC 60137, Insulated bushings for alternating voltages above 1 000 V. 7.6 Degree of protection7.6.1 The requirements for the degree of protection are given in Pt 6, Ch 2, 7.6 Degree of protection of the Rules for Ships, which are to be complied with where applicable. 7.7 Distribution boards7.7.1 The requirements for the distribution boards are given in Pt 6, Ch 2, 7.7 Distribution boards of the Rules for Ships, which are to be complied with where applicable. 7.8 Earthing of high-voltage switchboards7.8.1 The requirements for earthing of high-voltage switchboards are given in Pt 6, Ch 2, 7.8 Earthing of high-voltage switchboards of the Rules for Ships, which are to be complied with where applicable. 7.9 Fuses7.9.1 The requirements for fuses are given in Pt 6, Ch 2, 7.9 Fuses of the Rules for Ships, which are to be complied with where applicable. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.9.2 Fuses are to comply with one of the following Standards amended where
necessary for ambient temperature:
Type test reports to verify the characteristics of a fuse are to be submitted for consideration when required. 7.10 Handrails or handles7.10.1 The requirements for handrails or handles are given in Pt 6, Ch 2, 7.10 Handrails or handles of the Rules for Ships, which are to be complied with where applicable. 7.11 Instruments for alternating current generators7.11.1 The requirements for instruments of the alternating current generators are given in Pt 6, Ch 2, 7.11 Instruments for alternating current generators of the Rules for Ships, which are to be complied with where applicable. 7.12 Instrument scales7.12.1 The requirements for instrument scales are given in Pt 6, Ch 2, 7.12 Instrument scales of the Rules for Ships, which are to be complied with where applicable. 7.13 Labels7.13.1 The requirements for labels are given in Pt 6, Ch 2, 7.13 Labels of the Rules for Ships, which are to be complied with where applicable. 7.14 Protection7.14.1 The requirements for protection are given in Pt 6, Ch 2, 6 System design – Protection, which are to be complied with. 7.15 Wiring7.15.1 The requirements for wiring are given in Pt 6, Ch 2, 7.15 Wiring of the Rules for Ships, which are to be complied with where applicable. 7.16 Position of switchboards7.16.1 The requirements for position of switchboards are given in Pt 6, Ch 2, 7.16 Position of switchboards of the Rules for Ships, which are to be complied with where applicable. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.16.2 When switchboards and section boards contain withdrawable equipment, an unobstructed space as defined by the manufacturer but not less than 1 m wide is to be provided in front of switchboards and section boards. When switchboards and section boards contain withdrawable equipment the unobstructed space is to be not less than 0,4 m wide with this equipment in its fully withdrawn position. Adequate space for operation and maintenance is to be provided around and above the switchboards and section boards. 7.16.3 So far as possible, pipes should not be installed directly above or in front of or behind switchboards, section boards and distribution boards. If such placing is unavoidable, suitable protection is to be provided in these positions, see Pt 5, Ch 13, 2 Construction and installation of the Rules for Ships and Pt 5, Ch 13, 2 Construction and installation. 7.16.4 For switchgear and controlgear assemblies, for rated voltages above 1 kV a.c., arrangements are to be made to protect personnel in the event of gases or vapours escaping under pressure as the result of arcing due to an internal fault. Where personnel may be in the vicinity of the equipment when it is energised, this may be achieved by an assembly that has been tested in accordance with Annex A of IEC 62271-200:2011, High-voltage switchgear and controlgear – Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kVor Annex B of IEC 62271-203:2011, High-voltage switchgear and controlgear – Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV and qualified for classification IAC (internal arc classification). 7.17 Switchboard auxiliary power supplies7.17.1 The requirements for switchboard auxiliary power supplies are given in Pt 6, Ch 2, 7.17 Switchboard auxiliary power supplies of the Rules for Ships, which are to be complied with where applicable. 7.18 Testing7.18.1 The requirements for testing are given in Pt 6, Ch 2, 7.18 Testing of the Rules for Ships, which are to be complied with where applicable. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.18.2 For switchgear and control gear assemblies, for rated voltages above 1 kV a.c., type tests are to be carried out in accordance with Annex A of IEC 62271-200:2011, High-voltage switchgear and controlgear – Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV or Annex B of IEC 62271-203:2011, High-voltage switchgear and controlgear – Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV and IAC (internal arc classification) assigned, to verify that the assembly will withstand the effects of an internal arc occurring within the enclosure at a prospective fault level equal to, or in excess of, that of the installation. 7.19 Disconnectors and switch-disconnectors7.19.1 The requirements for testing are given in Pt 6, Ch 2, 7.19 Disconnectors and switch-disconnectors of the Rules for Ships, which are to be complied with where applicable. Additions or amendments to these requirements are given in the following paragraph(s) of this sub-Section. 7.19.2 Disconnectors, switch-disconnectors and their components are to comply
with one of the following standards, amended where necessary for ambient temperature
and other environmental conditions:
|
||
|
||
|