8.1.6 Any electrical equipment which has to remain operational during a Major
                                 Accident Event (e.g. rupture of a process vessel or pipe), whether or not installed
                                 in a hazardous zone or location, is to be suitable for use in an explosive gas
                                 atmosphere. Such equipment is to be of a type permitted within Zone 1 locations,
                                 unless it is demonstrated that the equipment is appropriately protected against
                                 potentially coming into contact with a flammable atmosphere by being located in an
                                 enclosed safe area with appropriate mitigating measures. Mitigation methods
                                 acceptable to LR for enclosed safe areas may include, but are not limited to:
                                 installation of suitably sealed barriers and doors, sealing to a suitable level of
                                 smoke and gas tightness; rated gas dampers; suitable gas detection located at
                                 associated air intake ducts, main access doorways, located within the enclosure;
                                 positive pressurisation. Other arrangements may also be submitted for consideration
                                 by LR. 
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.7 Flame-proof enclosures and intrinsically safe electrical apparatus, and
                                 apparatus incorporating flame-proof or intrinsically safe components or otherwise
                                 tested or certified for particular groups, with reference to the group(s) of gas(es)
                                 that may be present, is to be selected with reference to IEC/TR 60079-20:
                                    Electrical apparatus for explosive gas atmospheres – Part 20: Data for flammable
                                    gases and vapours, relating to the use of electrical apparatus. 
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.8 The electrical apparatus shall be so selected that its maximum surface
                                 temperature as indicated by its temperature class, or otherwise documented, will not
                                 reach the auto-ignition temperature of any gas or vapour, or mixture of gases or
                                 vapour, which can be present. The ambient temperature range for which the apparatus
                                 is certified is to be taken to be minus 20°C to 40°C, unless otherwise stated, and
                                 account is to be taken of this when assessing the suitability of the equipment for
                                 the auto-ignition temperature of the gases encountered.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.9 Cables are not permitted to pass through locations classified as Zone 0,
                                 and are permitted to enter such locations only where required for the operation of
                                 any electrical equipment located therein.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.10 Cables are to be either:
                                 
                                    - Mineral insulated with copper sheath; or
 
                                    - Armoured or braided, except where:
                                       
                                          - The cable is associated with an intrinsically safe
                                             circuit; or
                                          
 
                                          - The cable does not pass into or through any location
                                             classified as Zone 1, and is routed or protected so as to present
                                             only a low risk of mechanical damage; or
                                          
 
                                          - A cable of flexible construction is demanded by
                                             operational requirements, and its construction, routing and means of
                                             support are such as to present only a low risk of mechanical damage;
                                             or
                                          
 
                                          - The cable is installed within a conduit system meeting
                                             the relevant requirements of IEC60079-14.
                                          
 
                                       
                                       
                                     
                                 
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.11 Metal coverings of cables installed in hazardous zones or spaces are to
                                 be effectively earthed at both ends, at least, except where otherwise permitted by
                                 IEC 60079-14.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.12 Cables associated with intrinsically safe circuits are to be used only
                                 for such circuits. They are to be physically separated from cables associated with
                                 non-intrinsically safe circuits, e.g. neither installed in the same protective
                                 casing nor secured by the same fixing clip, except where alternative arrangements
                                 are permitted by IEC 60079-14.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.13 No more than one intrinsically safe circuit should be run in any
                                 multicore cable unless:
                                 
                                    - No circuit is required to be of category ‘ia’, and either:
                                       
                                          - The cable is run or protected so as to present little
                                             risk of its suffering mechanical damage; or
                                          
 
                                          - Each intrinsically safe circuit is contained within an
                                             earthed metallic screen; or
                                          
 
                                       
                                       
                                     
                                    - It can be shown that no combination of faults between the
                                       intrinsically safe circuits within the cable can lead to an unsafe
                                       condition.
                                    
 
                                 
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              8.1.14 Cabling, wiring, and connections within enclosures containing more than
                                 one intrinsically safe circuit, or containing both intrinsically safe and other
                                 circuits, are to be arranged in accordance with the relevant requirements of
                                 IEC60079-11 and IEC60079-14 so as to minimise the risk of inadvertent
                                 interconnections between different circuits.