2.1.2 For column-stabilised units all sea inlet and overboard discharge valves
are to be provided with remote control.
2.1.3 Where remote operation is provided by power-activated valves for sea
inlets and discharges for supply to fire pumps, power supply failure of the control
system is not to result in the closing of open valves or the opening of closed
valves.
2.1.4 Consideration will be given to accepting bilge alarms in lieu of remote
operation for surface type and self-elevating units. See also Section 10 and
Pt 6, Ch 1 Control Engineering Systems.