13.1 Goal
The goal of this chapter is to provide for the ventilation required for safe
operation of gas-fuelled machinery and equipment.
13.2 Functional requirements
This chapter is related to functional requirements in 3.2.2, 3.2.5, 3.2.8, 3.2.10,
3.2.12 to 3.2.14 and 3.2.17.
13.3 Regulations – General
13.3.1 Any ducting used for the ventilation of hazardous spaces shall be separate
from that used for the ventilation of non-hazardous spaces. The ventilation shall
function at all temperatures and environmental conditions the ship will be operating
in.
13.3.2 Electric motors for ventilation fans shall not be located in ventilation ducts
for hazardous spaces unless the motors are certified for the same hazard zone as the
space served.
13.3.3 Design of ventilation fans serving spaces containing gas sources shall fulfil
the following:
-
.1 Ventilation fans shall not produce a source of vapour ignition in either
the ventilated space or the ventilation system associated with the space.
Ventilation fans and fan ducts, in way of fans only, shall be of
non-sparking construction defined as:
-
.1 impellers or housings of non-metallic material, due regard being
paid to the elimination of static electricity;
-
.2 impellers and housings of non-ferrous metals;
-
.3 impellers and housings of austenitic stainless steel;
-
.4 impellers of aluminium alloys or magnesium alloys and a ferrous
(including austenitic stainless steel) housing on which a ring of
suitable thickness of non-ferrous materials is fitted in way of the
impeller, due regard being paid to static electricity and corrosion
between ring and housing; or
-
.5 any combination of ferrous (including austenitic stainless steel)
impellers and housings with not less than 13 mm tip design
clearance.
-
.2 In no case shall the radial air gap between the impeller and the casing be
less than 0.1 of the diameter of the impeller shaft in way of the bearing
but not less than 2 mm. The gap need not be more than 13 mm.
-
.3 Any combination of an aluminium or magnesium alloy fixed or rotating
component and a ferrous fixed or rotating component, regardless of tip
clearance, is considered a sparking hazard and shall not be used in these
places.
13.3.4 Ventilation systems required to avoid any gas accumulation shall consist of
independent fans, each of sufficient capacity, unless otherwise specified in this
Code.
13.3.5 Air inlets for hazardous enclosed spaces shall be taken from areas that, in
the absence of the considered inlet, would be non-hazardous. Air inlets for
non-hazardous enclosed spaces shall be taken from non-hazardous areas at least 1.5 m
away from the boundaries of any hazardous area. Where the inlet duct passes through
a more hazardous space, the duct shall be gas-tight and have over-pressure relative
to this space.
13.3.6 Air outlets from non-hazardous spaces shall be located outside hazardous
areas.
13.3.7 Air outlets from hazardous enclosed spaces shall be located in an open area
that, in the absence of the considered outlet, would be of the same or lesser hazard
than the ventilated space.
13.3.8 The required capacity of the ventilation plant is normally based on the total
volume of the room. An increase in required ventilation capacity may be necessary
for rooms having a complicated form.
13.3.9 Non-hazardous spaces with entry openings to a hazardous area shall be arranged
with an airlock and be maintained at overpressure relative to the external hazardous
area. The overpressure ventilation shall be arranged according to the following:
-
.1 During initial start-up or after loss of overpressure ventilation, before
energizing any electrical installations not certified safe for the space in
the absence of pressurization, it shall be required to:
-
.2 Operation of the overpressure ventilation shall be monitored and in the
event of failure of the overpressure ventilation:
-
.1 an audible and visual alarm shall be given at a manned location;
and
-
.2 if overpressure cannot be immediately restored, automatic or
programmed, disconnection of electrical installations according to a
recognized standardfootnote shall be required.
13.3.10 Non-hazardous spaces with entry openings to a hazardous enclosed space shall
be arranged with an airlock and the hazardous space shall be maintained at
underpressure relative to the non-hazardous space. Operation of the extraction
ventilation in the hazardous space shall be monitored and in the event of failure of
the extraction ventilation:
-
.1 an audible and visual alarm shall be given at a manned location; and
-
.2 if underpressure cannot be immediately restored, automatic or programmed,
disconnection of electrical installations according to a recognized standard
in the non-hazardous space shall be required.
LR 13.3-01 All spaces that are adjacent to more hazardous spaces
or areas, are to be maintained at a pressure 25 Pa (0,25 mbar) or more above the
pressure of the more hazardous space or area.
LR 13.3-02 In general, ventilators necessary to continuously
supply the machinery space are to have coamings of sufficient height as described in
Pt 3, Ch 12,2.4.1 of the Rules for Ships.
13.4 Regulations for tank connection space
13.4.1 The tank connection space shall be provided with an effective mechanical
forced ventilation system of extraction type. A ventilation capacity of at least 30
air changes per hour shall be provided. The rate of air changes may be reduced if
other adequate means of explosion protection are installed. The equivalence of
alternative installations shall be demonstrated by a risk assessment.
13.4.2 Approved automatic fail-safe fire dampers shall be fitted in the ventilation
trunk for the tank connection space.
LR 13.4-01 It is to be confirmed if ‘fail-safe’ is ‘fail-close’
or ‘fail-open’ and agreed with LR.
LR 13.4-02 In lieu of an automatic fail–safe fire damper, other
arrangements providing an equivalent level of safety will be considered subject to
agreement by the National Administration.
13.5 Regulations for machinery
spaces
13.5.1 The ventilation system for machinery spaces containing gas-fuelled
consumers shall be independent of all other ventilation systems.
LR 13.5-01 Spaces enclosed within the boundaries of machinery
spaces (such as purifier rooms, engine-room workshops and stores) are considered an
integral part of machinery spaces containing gas-fuelled consumers and, therefore,
their ventilation system does not need to be independent of the ventilation system
serving the machinery spaces.
13.5.2 ESD protected machinery spaces shall have ventilation with a
capacity of at least 30 air changes per hour. The ventilation system shall ensure a
good air circulation in all spaces, and in particular ensure that any formation of
gas pockets in the room are detected. As an alternative, arrangements whereby under
normal operation the machinery spaces are ventilated with at least 15 air changes an
hour is acceptable provided that, if gas is detected in the machinery space, the
number of air changes will automatically be increased to 30 an hour.
13.5.3 For ESD protected machinery spaces the ventilation arrangements
shall provide sufficient redundancy to ensure a high level of ventilation
availability as defined in a standard acceptable to the Organization.footnote
13.5.4 The number and power of the ventilation fans for ESD protected
engine-rooms and for double pipe ventilation systems for gas safe engine-rooms shall
be such that the capacity is not reduced by more than 50% of the total ventilation
capacity if a fan with a separate circuit from the main switchboard or emergency
switchboard or a group of fans with common circuit from the main switchboard or
emergency switchboard, is inoperable.
13.6 Regulations for fuel preparation room
13.6.1 Fuel preparation rooms, shall be fitted with effective mechanical ventilation
system of the underpressure type, providing a ventilation capacity of at least 30
air changes per hour.
13.6.2 The number and power of the ventilation fans shall be such that the capacity
is not reduced by more than 50%, if a fan with a separate circuit from the main
switchboard or emergency switchboard or a group of fans with common circuit from the
main switchboard or emergency switchboard, is inoperable.
13.6.3 Ventilation systems for fuel preparation rooms, shall be in operation when
pumps or compressors are working.
13.7 Regulations for bunkering station
Bunkering stations that are not located on open deck shall be suitably ventilated to
ensure that any vapour being released during bunkering operations will be removed
outside. If the natural ventilation is not sufficient, mechanical ventilation shall
be provided in accordance with the risk assessment required by 8.3.1.1.
13.8 Regulations for ducts and
double pipes
13.8.1 Ducts and double pipes containing fuel piping shall be fitted with
effective mechanical ventilation system of the extraction type, providing a
ventilation capacity of at least 30 air changes per hour. This is not applicable to
double pipes in the engine-room if fulfilling 9.6.1.1.
13.8.2 The ventilation system for double piping and for gas valve unit
spaces in gas safe engine-rooms shall be independent of all other ventilation
systems.
LR 13.8-01 The ventilation system for double piping and gas valve
unit spaces in gas safe engine-rooms may extend outside of the gas safe
engine-rooms.
13.8.3 The ventilation inlet for the double wall piping or duct shall
always be located in a non-hazardous area away from ignition sources. The inlet
opening shall be fitted with a suitable wire mesh guard and protected from ingress
of water.
LR 13.8-02 The ventilation inlet referred to in 13.8.3 shall
always be located in open air.
13.8.4 The capacity of the ventilation for a pipe duct or double wall
piping may be below 30 air changes per hour if a flow velocity of minimum 3 m/s is
ensured. The flow velocity shall be calculated for the duct with fuel pipes and
other components installed.