Section
2 Ventilators
2.1 General
2.1.2 Special
care is to be taken in the design and positioning of ventilator openings
and coamings, particularly in the region of the forward end of superstructures
and other points of high stress. The deck plating in way of the coamings
is to be efficiently stiffened.
2.1.3 Ventilators
from deep tanks and tunnels passing through 'tween decks are to have
scantlings suitable for withstanding the pressures to which they may
be subjected, and are to be made watertight.
2.2 Coamings
2.2.1 The scantlings and height of ventilator coamings exposed to the weather are
to be not less than required by Table 12.2.1 Ventilator coaming
requirements but the thickness need not exceed that of the
adjacent deck or bulkhead plating. In particularly exposed positions, the height of
coamings and scantlings may be required to be increased.
Table 12.2.1 Ventilator coaming
requirements
Feature
|
Requirements
|
Height (measured above sheathing if
fitted)
|
(1)
|
zc = 900 mm at
Position 1 (see
Pt 3, Ch 1, 6.6 Position 1 and Position 2)
|
|
|
z
c = 760 mm at Position 2 (see
Pt 3, Ch 1, 6.6 Position 1 and Position 2)
|
Thickness
|
(2)
|
t
c = 5,5 + 0,01 δv mm
where 7,5 mm ≤ t
c ≤ 10,0 mm
|
Support
|
(3)
|
If z
c
> 900 mm the coaming is to be specially supported
|
Symbols
|
t
c = thickness of coaming, in mm
|
z
c = height of coaming, in mm
|
δv = internal diameter of coaming, in mm
|
NOTE Where the height of the ventilator exceeds that given
in Item (1), the thickness given by (2) may be generally reduced, above that
height, to a minimum of 6,5 mm. The ventilator is to be adequately
stayed.
|
2.2.2 Where ventilators in locations above Position 2 are included in the consideration of
intact and damage stability or are in critical locations above Position 2, then the
height of ventilator coamings is to be specially considered.
2.2.4 For gooseneck ventilators, the coaming height is to be measured to the
underside of the bend, this being the lowest point through which water on deck could
pass freely to spaces below.
2.2.5 Where wall vents are fitted with an internal baffle which rises above the
lower edge of the exterior opening, the coaming height is measured to the top of the
baffle.
2.2.6 Where permitted by the National Authority, ventilator coaming heights may be
reduced on ships engaged on protected or extended protected water service. Coaming
heights are to be as high as practicable, with a minimum height of 450 mm in Position 1
and 300 mm in Position 2.
2.3 Closing appliances
2.3.2 In
ships where the load line length, L
L (see
Pt 3, Ch 1, 6.1 Principal particulars), is not more than 100 m,
the closing appliances are to be permanently attached to the ventilator
coaming. Where not so provided in other ships, they are to be conveniently
stowed near the ventilator to which they are to be fitted.
2.3.3 Where,
in ferries, ventilators are proposed to be led overboard in an enclosed
'tween deck, the closing arrangements are to be submitted for approval.
If such ventilators are led overboard more than 4,5 m above the main
vehicle deck, closing appliances may be omitted, provided that satisfactory
baffles and drainage arrangements are provided, as in the case of
air intakes or exhaust openings for machinery spaces, which may be
arranged in the sides of the ship.
2.3.4 On
offshore supply ships, to ensure satisfactory operation in all weather
conditions, machinery space ventilation inlets and outlets are to
be located in such positions that closing appliances will not be necessary.
2.3.5 Mushroom
ventilators closed by a head revolving on a centre spindle (screw
down head) are acceptable in Position 2, and also in sheltered positions
in Position 1, excluding those described in Pt 3, Ch 12, 2.1 General 2.1.1, but the diameter is not
to exceed 300 mm if situated within the forward 0,25L
L.
2.3.6 Mushroom ventilators with a fixed head and closed by a screw down plate
(screw down cover) may be accepted in exposed positions within the forward 0,25L
L, excluding those described in Pt 3, Ch 12, 2.1 General 2.1.1, up to a diameter of 750 mm.
2.3.7 Wall
ventilators (jalousies) may be accepted provided they are capable
of being closed weathertight by hinged steel gasketed covers secured
by bolts or toggles.
2.3.8 A ventilator
head not forming part of the closing arrangements is to be not less
than 6,5 mm thick.
2.3.9 In order to limit the fire growth potential in every space of the ship, the
main inlets and outlets of all ventilation systems shall be capable of being closed from
outside the spaces being ventilated. The means of closing shall be easily accessible as
well as prominently and permanently marked and shall indicate whether the inlet or
outlet is open or closed. Unless required by SOLAS, Chapter II-2, Part C, Regulation 9 - Containment of fire, emergency generator room
ventilators need to be fitted with such means of closing, only when the emergency
generator room is fitted with a fixed gas fire-fighting system. Battery room ventilators
are only to be fitted with a means of closing, whenever:
-
the battery room
does not open directly on to an exposed deck; or
-
the ventilation
opening for the battery room is required to be fitted with a closing
device according to the Load Line Convention; or
-
the battery room is fitted with a fixed gas fire-extinguishing
system.
Where a battery room ventilator is fitted with a closing device see
Pt 6, Ch 2, 12.5 Thermal management and ventilation 12.5.2. The means of closing mentioned in this
paragraph refers to closing appliances of ventilation inlets and outlets for minimising
the potential fire growth. The requirements specified are distinct from those for
weathertight closing appliances.
2.4 Machinery spaces
2.4.1 In general, ventilators necessary to continuously supply the machinery
space are to have coamings of sufficient height to comply with Pt 3, Ch 12, 2.3 Closing appliances 2.3.1 without having to fit weathertight closing
appliances. Ventilators to emergency generator rooms are to be so positioned that
weathertight closing appliances are not required.
2.4.2 Where due to ship size and arrangement this is not practicable, lesser
heights for machinery space ventilator coamings fitted with weathertight closing
appliances may be permitted by the Administration in combination with other suitable
arrangements to ensure uninterrupted, adequate supply of ventilation to these
spaces.
2.4.3 Where closing appliances are fitted as per Pt 3, Ch 12, 2.3 Closing appliances 2.3.9 or Pt 3, Ch 12, 2.4 Machinery spaces 2.4.2, to
ventilators serving emergency generator rooms or closable ventilation louvres are used
for emergency generator rooms, the following requirements are to be applied in addition
to the requirements of Pt 3, Ch 12, 2.4 Machinery spaces 2.4.2:
- Ventilation louvres and closing appliances may either be
hand-operated or power-operated (hydraulic/pneumatic/electric) and are to be
operable under a fire condition. Closing appliances, which automatically close in
response to exposure to fire products, are not to be fitted on ventilators located
at outside boundaries and serving emergency generator rooms.
- Hand-operated ventilation louvres and closing appliances are to be
kept open during the normal operation of the vessel. Corresponding instruction
notices are to be provided at the location where hand operation is provided.
- Power-operated ventilation louvres and closing appliances are to open
automatically whenever the emergency generator is starting/in operation. Closed
ventilation louvres and closing appliances are acceptable during normal operation
of the vessel. In the event of power failure, the default position of the
ventilation louvres or closing appliances is to be the open position.
- Ventilation openings are to be capable of being operated manually
from a clearly marked safe position outside the space where the closing operation
can be easily confirmed. The louvre status (open/closed) is to be indicated at
this position. Such closing is not to be possible from any other remote
position.
|