4.1 For systems of type B (see table 3-1) an efficient fire detection
and fire confirmation system covering all parts of the ro-ro or special
category spaces should be provided.
4.2 The fire detection system should consist of
flame detectors and smoke detectors of approved types. The flame detectors
should be installed under fixed continuous decks according to the
limitation and application defined by the maker and the approval certificate.
The smoke detector arrangement shall comply with the International
Code for Fire Safety Systems (FSS Code). Smoke
detectors with a spacing not exceeding 11 m should be installed under
hoistable ramps.
4.3 A colour TV monitoring system should cover
all parts of the ro-ro or special category spaces. Cameras need not
be installed below hoistable decks if the camera arrangement can identify
smoke (confirm fire) based on positions under a fixed continuous deck.
4.4 The relevant section of the deluge system
should be automatically released when two detectors covering this
area activate. Systems being released when only one detector activates
may also be accepted. The automatic release should not prevent manual
operation (both opening and closing) of the section valves. The automatic
release may be disconnected during on- and off-loading operations,
provided that this function is automatically re-connected after a
pre-set time being appropriate for the operations in questions.
4.5 All release controls for the deluge system,
monitor(s) for the CCTV system and the control panel (or an indication
panel) for the fire detection system should be available and grouped
together in a continuously manned control station.