12.1.1 Cargo
pump-rooms and other enclosed spaces which contain cargo-handling
equipment and similar spaces in which work is performed on the cargo
shall be fitted with mechanical ventilation systems, capable of being
controlled from outside such spaces.
12.1.2 Provision
shall be made to ventilate such spaces prior to entering the compartment
and operating the equipment and a warning notice requiring the use
of such ventilation shall be placed outside the compartment.
12.1.3 Mechanical
ventilation inlets and outlets shall be arranged to ensure sufficient
air movement through the space to avoid the accumulation of toxic
or flammable vapours or both (taking into account their vapour densities)
and to ensure sufficient oxygen to provide a safe working environment,
but in no case shall the ventilation system have a capacity of less
than 30 changes of air per hour, based upon the total volume of the
space. For certain products, increased ventilation rates for cargo
pump-rooms are prescribed in Ch 1, 15.17 Increased ventilation requirements.
12.1.4 Ventilation
systems shall be permanent and shall normally be of the extraction
type. Extraction from above and below the floor plates shall be possible.
In rooms housing motors driving cargo pumps, the ventilation shall
be of the positive-pressure type.
12.1.5 Ventilation
exhaust ducts from spaces within the cargo area shall discharge upwards
in locations at least 10 m in the horizontal direction from ventilation
intakes and openings to accommodation, service and machinery spaces
and control stations and other spaces outside the cargo area.
12.1.6 Ventilation
intakes shall be so arranged as to minimize the possibility of recycling
hazardous vapours from any ventilation discharge opening.
12.1.7 Ventilation
ducts shall not be led through accommodation, service and machinery
spaces or other similar spaces.
12.1.8 Electric motors driving fans shall be placed outside the ventilation ducts
if the carriage of flammable products is intended. Ventilation fans and fan ducts, in
way of fans only, for hazardous locations referred to in chapter 10 shall be of non-sparking construction, defined
as:
-
impellers or housing
of non-metallic construction, due regard being paid to the elimination
of static electricity;
-
impellers and housing
of non-ferrous materials;
-
impellers and housing
of austenitic stainless steel; and
-
ferrous impellers
and housing with not less than 13 mm design tip clearance.
Any combination of an aluminium or a magnesium alloy fixed or
rotating component and a ferrous fixed or rotating component, regardless
of tip clearance, is considered a sparking hazard and shall not be
used in these places.
12.1.9 Sufficient
spare parts shall be carried for each type of fan on board required
by this chapter.
12.1.10 Protection
screens of not more than 13 mm square mesh shall be fitted in outside
openings of ventilation ducts.