15.2.1 At
the surveys described in Pt 1, Ch 3, 15.1 Frequency of surveys,
the boilers, superheaters, economizers and air heaters are to be examined
internally on the water-steam side and the fire side. Where considered
necessary, the pressure parts are to be tested by hydraulic pressure
and the thicknesses of plates and tubes and sizes of stays are to
be ascertained to determine a safe working pressure. The safety valves
and principal mountings on boilers, superheaters and economizers are
to be examined and opened up as necessary by the Surveyor. The adjustment
of safety valves is to be verified during each boiler internal survey.
Boiler safety valves and their relieving gear are to be examined and
tested to verify their satisfactory operation. Safety valves are to
be set under steam to a pressure not greater than the approved design
pressures of the respective parts. As a working tolerance, the setting
is acceptable, provided that the valves lift at not more than 103
per cent of the approved design pressure. However, for exhaust gas
heated economizers, if steam cannot be raised in port, the safety
valves may be set by the Chief Engineer at sea, and the results recorded
in the log book and reviewed by the attending Surveyor. The following
records since the previous Boiler Survey are to be reviewed as part
of the survey:
- Operation
- Maintenance
- Repair history
- Feedwater chemistry.
The remaining mountings are to be examined externally and, if
considered necessary by the Surveyor, are to be opened up for internal
examination. Collision chocks, rolling stays and boiler stools are
to be examined and maintained in an efficient condition.
15.2.2 In
addition to the foregoing, in exhaust gas heated economizers of the
shell type, all accessible welded joints are to be subjected to a
visual examination in order to identify any evidence of cracking.
Non-destructive testing may be required for this purpose and may be
requested by the Surveyor.
15.2.3 In
fired boilers employing forced circulation, the pumps used for this
service are to be opened and examined at each Boiler Survey.
15.2.4 The
fuel oil burning system is to be examined under working conditions
and a General Examination made of fuel tank valves, pipes, deck controlgear
and oil discharge pipes between pumps and burners.
15.2.5 At
each survey of a cylindrical boiler which is fitted with smoke tube
superheaters, the saturated steam pipes are to be examined as detailed
in Section 16.