3.2.1 An
alarm system is to be provided to indicate faults in essential machinery
and control systems in accordance with this Chapter.
3.2.2 Machinery
faults are to be indicated at the control stations on the bridge and
in the machinery space.
3.2.3 In
the event of a machinery fault occurring, the alarm system is to be
such that the watchkeeping officer on the bridge is made aware of
the following.
-
A machinery fault
has occurred.
-
The machinery
fault is being attended to, and
-
The machinery
fault has been rectified. (Alternative means of communication between
the bridge control station and the machinery control station may be
used for this function.)
3.2.4 The
alarm system should be designed with self-monitoring properties. As
far as practicable, any fault in the alarm system should cause it
to fail to the alarm condition.
3.2.5 The
alarm system should be capable of being tested during normal machinery
operation.
3.2.6 Failure
of the power supply to the alarm system is to be indicated as a separate
fault alarm.
3.2.7 Alarm
indication is to be both audible and visual. If arrangements are made
to silence audible alarms they are not to extinguish visual alarms.
3.2.8 The
acceptance of an alarm on the bridge is not to silence the audible
alarm in the machinery space.
3.2.9 Machinery
alarms should be distinguishable from other audible alarms, e.g. fire,
carbon dioxide.
3.2.10 Acknowledgement
of visual alarms is to be clearly shown.
3.2.11 If
the audible alarm has been silenced and a second fault occurs before
the first has been rectified, the audible alarm is again to operate.
To assist in the detection of transient faults which are subsequently
self-correcting, fleeting alarms should lock-in until accepted.