6.2.1 Where
machinery is fitted with automatic or remote controls so that under
normal operating conditions it does not require any manual intervention
by the operators, it is to be provided with the alarms and safety
arrangements required by Pt 5, Ch 5, 6.2 Unattended machinery,
as appropriate. Alternative arrangements which provide equivalent
safeguards will be considered.
6.2.2 Where
machinery specified in this Section is required to be provided with
a standby pump, the standby pump is to start automatically if the
discharge pressure from the working pumps falls below a predetermined
value.
6.2.3 Where
a first stage alarm together with a second stage alarm and automatic
shutdown of machinery are required in the relevant Tables of this
Section, the sensors and circuits utilised for the second stage alarm
and automatic shutdown are to be independent of those required for
the first stage alarm.
6.2.4 Alarms
and safeguards are indicated in Table 5.6.1 Main and auxiliary gear units:
Alarms and safeguards.
Table 5.6.1 Main and auxiliary gear units:
Alarms and safeguards
Item
|
Alarm
|
Note
|
Lubricating oil sump level
|
Low
|
—
|
Lubricating oil inlet pressure
*
|
1st stage low
|
Slow-down
|
Lubricating oil inlet pressure
*
|
2nd stage low
|
Automatic shutdown
|
Lubricating oil inlet temperature
*
|
High
|
—
|
Thrust bearing temperature *
|
High
|
Slow-down
|
Note For transmitted powers of 1500 kW or less, only the items
marked * are required.
|