13.6.1 The
temperature rise on the live parts of socket outlet and plugs is not
to exceed 30°C. Socket outlets and plugs are to be so constructed
that they cannot be readily short-circuited whether the plug is in
or out, and so that a pin of the plug cannot be made to earth either
pole of the socket outlet.
13.6.2 All
socket outlets of current rating in excess of 16 A are to be provided
with a switch, and be interlocked such that the plug cannot be inserted
or withdrawn when the switch is in the 'on' position.
13.6.3 Where
it is necessary to earth the non-current carrying parts of portable
or transportable equipment, an effective means of earthing is to be
provided at the socket outlet.
13.6.4 On
weather decks, galleys, laundries, machinery spaces and all wet situations
socket outlets and plugs are to be effectively shielded against rain
and spray and are to be provided with means of maintaining this quality
after removal of the plug.