9.3.1 Cooling water piping that is welded in situ is to be hydraulically
strength tested at 1,5 times the design pressure, but in no case less than 0,35 MPa.
9.3.2 A distribution
test is to be carried out to ensure that even fresh water distribution
to each container as well as sufficient flow is achieved. As the fresh
water system may be somewhat complicated, this test should be carried
out with care, using all possible combinations of fresh water pumps
installed.
9.3.3 If
required, the distribution test can be carried out without containers,
utilising flexible hoses for connecting the water supply and return
pipes together. The return valves should be partly closed or flexible
pipe may be crimped to represent the condenser pressure drop. Water
flow meters are to be installed at the highest and the lowest container
levels to verify equal water flow.
9.3.4 The
capacity of each pump should be measured by a flow meter with an accuracy
of ±3 per cent. Alternatively, this capacity could be obtained
from the manufacturer's curves if the static pressure difference across
a pump under test conditions is measured.
9.3.5 Sea-water
pumps and heat exchangers are normally subjected to a functional test
only.