6.1.1 Where provision is made for heating of the collected oil, the requirements of Pt 7, Ch 5, 6 Fire protection and extinction are applicable for assignment of the
notation Oil Recovery (F.P. >60°C). Where there is no provision for heating the
collected oil, the requirements of Pt 7, Ch 5, 6 Fire protection and extinction are not applicable for assignment of
the notation Oil Recovery (F.P. >60°C) in this case the structural fire
protection is to be installed as required by the applicable rules for a cargo ship.
6.1.2 Exterior
boundaries of superstructures and deckhouses enclosing accommodation
and service spaces, including any overhanging decks which support
such accommodation and service spaces, are to be insulated to `A-60'
standard for all parts which face deck areas where there are arrangements
for collection, handling and transfer of recovered oil and for a distance
3 m aft or forward thereof.
6.1.3 Windows
and side scuttles in the exterior boundaries, referred to in Pt 7, Ch 5, 6.1 Structural fire protection 6.1.2, are to be provided with permanently
installed inside covers of steel. Aluminium alloy components are not
to be used in the construction of the windows and side scuttles.
6.1.4 As an
alternative to compliance with Pt 7, Ch 5, 6.1 Structural fire protection 6.1.2 and Pt 7, Ch 5, 6.1 Structural fire protection 6.1.3, a fixed water spraying system
may be accepted. The system is to be capable of delivering water at
a rate of 10 litres/m2/min. on all boundaries, windows
and side scuttles, that would otherwise be required to comply with Pt 7, Ch 5, 6.1 Structural fire protection 6.1.2 and Pt 7, Ch 5, 6.1 Structural fire protection 6.1.3.