2.1.2 Coal
is to be stored in not less than two bunkers. Vessels on restricted
routes having a voyage time less than the capacity of the daily service
hoppers, or where the boiler has the alternative means of firing,
or where alternative means of propulsion are fitted, may be provided
with only one bunker.
2.1.3 The
clearance spaces between the boilers, other heated surfaces and the
coal bunkers are to be adequate for the free circulation of air necessary
to avoid transmission of heat to the coal.
2.1.4 A daily
service storage hopper is to be provided for each coal-fired boiler.
2.1.5 Coal
bunkers and daily service storage hoppers are to be designed to avoid
dead spots and areas where coal can accumulate and impede the normal
flow or can provide the conditions to promote spontaneous combustion.
2.1.6 Bunker
and daily service storage hopper outlet gravity-fed discharges are
to be provided with shut-off devices. Stopping the transfer device
will be acceptable in lieu where a bunker delivers to transfer arrangements
and stopping the transfer device effectively prevents flow from the
bunker, see
Pt 7, Ch 7, 2.2 Coal handling 2.2.4.
2.1.7 Shut-off
devices on the coal bunker and daily service storage hopper outlets
are to be capable of being operated locally and also from an accessible
position outside the compartment in which they are situated.
2.1.8 The
arrangements for loading coal into bunkers or during transfer into
daily service storage hoppers should, in general, avoid the tendency
of the coal to segregate. For this purpose multiple loading points
should be used if necessary.