Section
1 Testing and trials
1.1 Testing
1.1.1 Tests
in accordance with Vol 2, Pt 9, Ch 12, 1.1 Testing 1.1.2 are
to be satisfactorily carried out on all electrical equipment, complete
or in sections, at the manufacturer’s premises and a test report
issued by the manufacturer.
1.1.2 A high
voltage at any frequency between 25 and 100 Hz is to be applied between:
-
all current carrying
parts connected together and earth;
-
all current carrying
parts of opposite polarity or phase.
For rotating machines the value of test voltage is to be 1000
V plus 2 x rated voltage with a minimum of 2000 V, and for other electrical
equipment, it is to be in accordance with Table 12.1.1 Test voltage. Items of equipment
included in the assembly for which a test voltage lower than the above
is specified may be disconnected during the test and tested separately
at the appropriate lower test voltage. The test is to be commenced
at a voltage of about one-third the test voltage and is to be increased
to full value as rapidly as is consistent with its value being indicated
by the measuring instrument. The full test voltage is then to be maintained
for 1 minute, and then reduced to one-third full value before switching
off. The assembly is considered to have passed the test if no disruptive
discharge occurs.
Table 12.1.1 Test voltage
Rated voltage,
Un
Un V
|
Test voltage a.c.
(r.m.s.), V
|
Un ≤ 60
|
500
|
60
< Un ≤ 1000
|
2Un + 1000
|
1000
< Un ≤ 2500
|
6500
|
2500
< Un ≤ 3500
|
10000
|
3500
< Un ≤ 7200
|
20000
|
7200
< Un ≤ 12000
|
28000
|
12000
< Un ≤ 15000
|
38000
|
15000
< Un ≤ 22000
|
50000
|
22000
< Un ≤ 33000
|
70000
|
33000
< Un ≤ 35000
|
80000
|
1.1.3 When
it is desired to make additional high voltage tests on equipment which
has already passed its tests, the voltage of such additional tests
is to be 80 per cent of the test voltage the equipment has already
passed.
1.1.4 Immediately
after the high voltage test, the insulation resistance is to be measured
using a direct current insulation tester, between:
-
all current carrying
parts connected together and earth;
-
all current carrying
parts of different polarity or phase.
The minimum values of test voltage and insulation resistance
are given in Table 12.1.2 Test voltage and minimum
insulation.
Table 12.1.2 Test voltage and minimum
insulation
Rated
voltage Un V
|
Minimum voltage of
the tests, V
|
Minimum insulation
resistance, MΩ
|
Un ≤ 250
|
2Un
|
1
|
250
< Un ≤ 1000
|
500
|
1
|
1000
< Un ≤ 7200
|
1000
|
|
7200 <
Un ≤ 15000
|
5000
|
|
Un > 15000
|
5000
|
|
1.1.5 Tests
in accordance with the standard with which the equipment complies
may be accepted as an alternative to the above.
1.1.6 Tests at the manufacturers’ works and trials after installation on board
are to include such tests necessary to demonstrate, to the Surveyor’s satisfaction, the
suitability and safety of the lithium battery system for its intended duty and location.
As a minimum, the tests listed in Table 12.1.3 Test/Trials requirements on lithium battery systems are required.
Table 12.1.3 Test/Trials requirements on lithium battery systems
Item
|
Tests
|
Trials
|
Performance test
|
X
|
X
|
Sensor failures
test
|
X
|
|
State of
Charge (SOC) indication test
|
X
|
X
|
State of
Health (SOH) indication test
|
X
|
X
|
High voltage
test
|
X
|
|
Insulation resistance
test
|
X
|
|
Alarms
and safeguards required by Table 2.7.1 Lithium battery system: alarms and safeguards
|
X
|
X
|
Communication failure between Battery Management System (BMS) and external
charge control system test
|
X
|
X
|
Verification of thermal management at maximum achievable load under service
conditions during trials
|
|
X
|
Tests of the safety
functions in the battery compartment, i.e. fire detection and extinguishing,
gas detection, off-gas exhaust/extraction, ventilation, etc., as applicable
to the installation
|
|
X
|
1.2 Trials
1.2.1 Before
a new installation, or any alteration or addition to an existing installation,
is put into service the applicable trials in Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.2 are to be carried
out. These trials are in addition to any acceptance tests which may
have been carried out at the manufacturer’s works and are to
be to the Surveyor’s satisfaction. A report having the results
of measurements taken during the trials is to be submitted for record
purposes.
1.2.2 Means
are to be provided to facilitate testing during normal machinery operation,
e.g. by the provision of three-way test valves or equivalent.
1.2.3 Acceptance
tests and trials for Programmable Electronic Systems are to include
verification of software lifecycle activities appropriate to the stage
in the system's lifecycle at the time of system examination. The documentation
required by Vol 2, Pt 9, Ch 1, 1.4 Documentation required for design review 1.4.8 is
to be in accordance with the current configuration and the testing
and trials are to address software modifications to the Surveyor’s
satisfaction.
1.2.4 Wireless
data communication links are to be operational and tested during trials.
Tests are to demonstrate that radio-frequency transmission does not
interfere with the operation of equipment required by this Chapter
or other Sections of the Rules and does not itself malfunction as
a result of electromagnetic interference during expected operating
conditions. Reversionary modes are to be activated to demonstrate
continued safe and effective operation in the event of fault conditions.
1.2.5 The insulation resistance is to be measured of all electrical power circuits
and electrical equipment, using a direct current insulation tester, between:
-
all current carrying
parts connected together and earth and, so far as is reasonably practicable;
-
all current carrying
parts of different polarity or phase.
The minimum values of test voltage and insulation resistance
are given in Table 12.1.2 Test voltage and minimum
insulation The
installation may be subdivided and appliances may be disconnected
if initial tests produce results less than these figures.
1.2.6 Tests
are to be made to verify the effectiveness of:
-
earth continuity
conductor;
-
the earthing
of non-current carrying exposed metal parts of electrical equipment
and cables not exempted by Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.2;
-
bonding for the
control of static electricity.
1.2.7 It
is to be demonstrated that the Rules have been complied with in respect
of:
-
satisfactory performance of each power source supporting Mobility or
Ship type systems, including its auxiliary services, throughout a run at full
rated load;
-
temperature of
joint, connections, circuit-breakers and fuses;
-
the operation
of engine governors, synchronising devices, overspeed trips, reverse-current,
reverse-power and over-current trips and other safety devices;
-
voltage regulation
of every generator when full rated load is suddenly thrown off and
when starting the largest motor connected to the system;
-
voltage drop
at the worst case condition;
-
harmonic distortion of the voltage waveform. Where harmonic filters
are installed, the calculation results provided by the system integrator are to be
verified by the Surveyor. Simulations in trials of harmonic filter failure that
would result in THD levels calculated to be higher than the acceptable limit are
to be avoided. See
Vol 2, Pt 9, Ch 3, 4.11 Harmonic filtering;
-
satisfactory
parallel operation, and kW and KVA load sharing of all generators
capable of being operated in parallel at all loads up to normal working
load;
-
all Mobility systems, Ship Type systems, and other important equipment
are to be operated under service conditions, though not necessarily at full load
or simultaneously, for a sufficient length of time to demonstrate that they are
satisfactory;
-
propulsion equipment
is to be tested under working conditions and operated in the presence
of the Surveyors and to their satisfaction. The equipment is to have
sufficient power for going astern to secure proper control of the
ship in all normal circumstances. The ability of the machinery to
reverse the direction of thrust of the propeller in sufficient time,
under normal manoeuvring conditions, and so bring the ship to rest
from maximum ahead service speed, is to be demonstrated at the sea
trial, see also
Vol 2, Pt 1, Ch 3, 17.3 Performance testing requirements for naval vessels 17.3.9;
- the operation of the propulsion system with the harmonic filter removed
from circuit is to be verified in accordance with the design intent, see
Vol 2, Pt 4, Ch 5, 4.5 Harmonic filtering for propulsion 4.5.2; any
operational and functional limitations are to be documented and details retained on
board;
-
operation of power management for electric propulsion; and
-
satisfactory performance of each Mobility or Ship Type system energy storage
arrangement, including its auxiliary services, throughout a run at full-rated
charging capacity.
1.2.8 Measurements
are to be taken as part of the trials specified in Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.7.(c), Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.7.(d), Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.7.(e) and Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.7.(c) to verify that the installation
will provide a quality of power supply in accordance with the values
listed in Vol 2, Pt 9, Ch 1, 2.1 Quality of power supplies (QPS).
1.2.9 In
addition to Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.5, unless
it has been satisfactorily shown by the design verification and validation
process required by Vol 2, Pt 9, Ch 1, 3.2 General requirements 3.2.4,
that the power supply quality complies with the requirements of the
specified standard, then compliance is to be demonstrated by measurements
taken at representative ship operating loads, as defined by the Naval
Administration, see
Vol 2, Pt 9, Ch 1, 3.1 General 3.1.1.
1.2.10 It
is to be demonstrated by practical tests that the Rules have been
complied with in respect of fire, crew emergency and ship safety systems.
1.2.11 On
completion of the general emergency alarm system and the crew and
embarked personnel address system tests, the Surveyor is to be provided
with two copies of the test schedule, detailing the measured sound
pressure levels. Such schedules are to be signed by the Surveyor and
the Builder.
1.3 High voltage cables
1.3.1 Before
a new high voltage cable installation, or an addition to an existing
installation, is put into service, a voltage withstand test is to
be satisfactorily carried out on each completed cable and its accessories.
The test is to be carried out after the insulation resistance test
required by Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.2 and may
use either an a.c. voltage at power frequency or a d.c. voltage.
1.3.2 When
an a.c. voltage withstand test is carried out, the voltage is to be
not less than the normal operating voltage of the cable and it is
to be maintained for a minimum of 24 hours.
1.3.3 When
a d.c. voltage withstand test is carried out, the voltage is to be
not less than:
-
1,6 (2,5U
o + 2 kV) for cables of rated voltages (U
o)
up to and including 3,6 kV; or
-
4,2U
o for higher rated voltages where U
o is
the rated power frequency voltage between conductor and earth or metallic
screen, for which the cable is designed. The test voltage is to be
maintained for a minimum of 15 minutes. After completion of the test
the conductors are to be connected to earth for a sufficient period
in order to remove any trapped electric charge. An insulation resistance
test in accordance with Vol 2, Pt 9, Ch 12, 1.2 Trials 1.2.2 is
then to be repeated.
1.4 On-line partial discharge testing of high
voltage rotating machines for ship type and mobility systems
1.4.1 Where on-line partial discharge monitoring equipment is installed for the monitoring
of high voltage rotating machines used to provide ship type and mobility systems,
the method used is to be appropriate for the design and application of the rotating
machine, and conducted and recorded in accordance with:
- PD IEC/TS 60034-27-2:2012, Rotating electrical machines Part 27-2: On-line
partial discharge measurements on the stator winding insulation of rotating
electrical machines;
- DD IEC/TS 61934:2011, Electrical insulating materials and systems –
Electrical measurement of partial discharges (PD) under short rise time and
repetitive voltage impulses; or
- an alternative International or National Standard acceptable to LR.
1.4.2 The partial discharge measurement method used is to be acceptable to the rotating
machine manufacturer. Particular attention is to be given to ensuring that:
- the test voltage and frequency (i.e. a.c., or ultra-low frequency and voltage
level), and method selected are to be compatible with the insulation systems;
and
- the tests do not over stress or cause accelerated ageing of the insulation
system.
1.5 Optical Fibre Communications Systems
1.5.1 The attenuation loss of single mode optical fibre is to be tested prior
to installation in accordance with IEC 61280: Fibre-optic communication subsystem
test procedures Part 4-2: Installed cable plant – Single-mode attenuation and
optical return loss measurement. The test is to be recorded in accordance
with the standard. The documentation is to be retained on board and made available
to the Surveyor on request. Acceptance of alternative standards will be subject to
consideration by LR.
1.5.2 The attenuation loss of multimode optical fibre is to be tested prior to
installation in accordance with IEC 61280: Fibre optic communication subsystem
test procedures – Part 4-1: Installed cable plant – Multimode attenuation
measurement. The test is to be recorded in accordance with the standard. The
documentation is to be retained on board and made available to the Surveyor on
request. Acceptance of alternative standards will be subject to consideration by LR.
1.6 Hazardous areas
1.6.1 All
electric equipment located in hazardous areas is to be examined to
ensure that it is of a type permitted by the Rules, has been installed
in compliance with its certification, and that the integrity of the
protection concept has not been impaired.
1.6.2 Alarms
and interlocks associated with pressurised equipment and the ventilation
of spaces located in hazardous areas are to be tested for correct
operation.
1.7 Unattended machinery space operation - UMS notation
1.7.1 In addition to the tests required by Vol 2, Pt 9, Ch 7 Control, Alerts and Safety Systems, the suitability of the installation for operation in the
unattended mode is to be demonstrated during sea trials over a four to six hour period
observing the following:
-
Occurring alarms
and the frequency of operation both during steady steaming and under
manoeuvring conditions using bridge control.
-
Any intervention
by personnel in the operation of the machinery.
-
Stable operation in, and transition between, power plant configuration modes which
are not considered as manual operations (see
Vol 2, Pt 9, Ch 1, 1.4 Documentation required for design review). The demonstration time of each operating mode for the
electrical power system is to be sufficient to demonstrate that the transitions
can be performed with an unattended engine room, and a stable running condition
achieved.
1.8 Operation from a centralised control station - CCS notation
1.9 Integrated platform management system failure
1.9.1 Where
mobility type ship systems are operated through an Integrated Platform
Management System (IPMS), a failure in the IPMS is not to render the
ship’s system inoperable. Reversionary modes of operation are
to be provided to ensure safe and graceful degradation under these
conditions. The Systems Design Description shall define the acceptable
levels of degraded performance.
1.10 Record of trials
|