Section 5 Machinery operated from a centralised control station – CCS notation
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules and Regulations for the Classification of Naval Ships, January 2023 - Volume 2 Machinery and Engineering Systems - Part 9 Electrotechnical Systems - Chapter 1 General Requirements for the Design and Construction of Electrotechnical Systems - Section 5 Machinery operated from a centralised control station – CCS notation

Section 5 Machinery operated from a centralised control station – CCS notation

5.1 General requirements

5.1.1 Where it is proposed to install control, alarm and safety systems to the equipment listed in Vol 2, Pt 9, Ch 1, 4.1 General 4.1.1 the applicable features contained in Vol 2, Pt 9, Ch 7, 4 Essential features for control, alarm and safety systems and Vol 2, Pt 9, Ch 8, 4 General requirements and Vol 2, Pt 9, Ch 8, 5 Programmable electronic systems (PES) are to be incorporated in the system design.

5.1.2 The arrangements are to be such that corrective actions can be taken at the control station in the event of machinery faults, e.g. stopping of machinery, starting of standby machinery, adjustment of operating parameters, etc. These actions may be effected by either remote manual or automatic control.

5.1.3 The controls, alarms and safeguards required by the appropriate Chapters and by Vol 2, Pt 9, Ch 1, 4.7 Bilge level detection together with a fire detection system satisfying the requirements of Vol 2, Pt 9, Ch 9, 4.1 General are to be provided.

5.1.4 Additional requirements for controls, alarms and safeguards are given in Vol 2, Pt 9, Ch 1, 5.2 Centralised control station for machinery.

5.2 Centralised control station for machinery

5.2.1 A centralised control station is to be provided at some suitable location, which satisfies the requirements of Vol 2, Pt 9, Ch 1, 5.2 Centralised control station for machinery 5.2.2 to Vol 2, Pt 9, Ch 1, 5.2 Centralised control station for machinery 5.2.7 and the ergonomics requirements of Vol 2, Pt 10 Human Factors

5.2.2 A system of alarm displays and controls is to be provided which readily ensures identification of faults in the machinery and satisfactory supervision of related equipment. The alarm and control systems are to satisfy the requirements of Vol 2, Pt 9, Ch 7, 4.3 Alarm systems, general requirements and Vol 2, Pt 9, Ch 7, 4.5 Control systems, general requirements, as applicable.

5.2.3 Indication of all essential parameters necessary for the safe and effective operation of the machinery is to be provided, e.g. temperatures, pressures, tank levels, speeds, powers, etc.

5.2.4 Indication of the operational status of running and standby machinery is to be provided.

5.2.5 At the centralised control station, means of communication with the bridge area, the accommodation for engineering personnel and, if necessary, the machinery space are to be provided.

5.2.6 In addition to the communication required by Vol 2, Pt 9, Ch 1, 5.2 Centralised control station for machinery 5.2.5, a second means of communication is to be provided between the bridge and the centralised control station. One of these means is to be independent of the main electrical power supply.

5.2.7 Arrangements are to be provided in the centralised control station so that the normal supply of electrical power may be restored in the event of failure.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.