Section
2 Construction and installation
2.1 Materials
2.1.1 The
selection of materials in piping systems for provision refrigeration
systems is to recognise the following details:
-
Fluids, pressures
and temperatures.
-
Location.
-
Compatibility
of materials.
-
Fluid flow rates
and static conditions.
-
Minimising corrosion
and erosion through life of system.
-
Flammability and
toxicity.
2.1.2 Pipes,
valves and fittings are in general to be made of steel, ductile cast
iron, copper, copper alloy, or other approved ductile material suitable
for the intended purpose. The use of plastics materials is also acceptable,
subject to the restrictions in Vol 2, Pt 7, Ch 1 Piping Design Requirements.
2.2 Equipment - Selection and installation
2.2.2 Valves,
flexible hose lengths, expansion pieces and pumps are to comply with
the relevant requirements of Vol 2, Pt 7, Ch 1, 12 Valves.
2.2.3 Pipes
in piping systems are to be permanent pipes made with approved pipe
connections to enable ready removal of valves, pumps, fittings and
equipment. The pipes are to be efficiently secured in position to
prevent chafing or lateral movement.
2.2.4 Suitable
means for expansion is to be made, where necessary, in each range
of pipes.
2.2.5 Suitable
protection is to be provided for all pipes and equipment situated
where they are liable to mechanical damage.
2.2.6 All
moving parts are to be provided with guards to minimise danger to
personnel.
2.2.7 Low
temperature pipes in refrigeration systems are to be provided with
suitable insulation.
2.3 Valves and relief devices
2.3.1 Valves
are to be fitted in places where they are at all times readily accessible.
2.3.2 Relief
valves are to be adjusted and bursting discs so selected that they
relieve at a pressure not greater than the design pressure of the
system. When satisfactorily adjusted, relief valves are to be protected
against tampering or interference by wire with a lead seal or similar
arrangement.
2.4 Refrigerant systems
2.4.2 The compartments containing the refrigeration plants are to be provided
with refrigerant gas detectors in accordance with Vol 2, Pt 9, Ch 11 Gas detection with an alarm.
2.4.3 The
design of refrigeration systems is to be such that it permits maintenance
and repair without unavoidable loss of refrigerant to the atmosphere.
To minimise refrigerant release to the atmosphere, refrigerant recovery
units are to be provided for evacuation of a system prior to maintenance.
2.4.4 Refrigeration
systems are to be provided with relief devices, but it is important
to avoid circumstances that would bring about an inadvertent discharge
of refrigerant to the atmosphere. The system is to be so designed
that pressure due to fire conditions will be safely relieved.
2.4.5 A pressure
relief valve and/or bursting disc is to be fitted between each positive
displacement compressor and its gas delivery stop valve, the discharge
being led to the suction side of the compressor. The flow capacity
of the valve or disc is to exceed the full load compressor capacity
on the particular refrigerant at the maximum potential suction pressure.
For these internal relief valves, servo-operated valves will be accepted.
Where the motive power for the compressor does not exceed 10 kW, the
pressure relief valve and/or bursting disc may be omitted.
2.4.6 Each
pressure vessel which may contain liquid refrigerant and which is
capable of being isolated by means of a stop or automatic control
or check valves is to be protected by two pressure relief valves or
two bursting discs, or one of each, controlled by a changeover device.
Pressure vessels that are connected by pipework without valves, so
that they cannot be isolated from each other, may be regarded as a
single pressure vessel for this purpose, provided that the interconnecting
pipework does not prevent effective venting of any pressure vessel.
2.4.7 Omission
of one of the specified relief devices and changeover device, as required
by Vol 3, Pt 1, Ch 2, 2.4 Refrigerant systems 2.4.6, will be accepted
where:
-
Vessels are of
less than 300 litres internal gross volume;
or
-
Vessels discharge
into the low pressure side by means of a relief valve.
2.4.8 Sections
of systems and components that could become full of liquid between
closed valves are to be provided with pressure relief devices relieving
to a suitable point in the refrigerant circuit.
2.4.9 Where
hermetically sealed compressor units or semi-hermetic compressors
with the electric motor cooled by the circulating refrigerant are
installed, the following arrangements are to be made:
-
Each refrigeration
system containing hermetically sealed compressor units or semi-hermetic
compressors is to be independent of other refrigeration systems.
-
All hermetic motor-compressors
are to be fitted with a thermal cut-out device that protects the motor
against overheating.
-
Each refrigerant
circuit is to be designed such that debris or contaminants from a
motor failure, typically burn out of insulation, is contained and
not distributed around the system.
-
The pressure envelope
of any hermetic or semi-hermetic compressor exposed to the refrigerant
pressure is to be designed and constructed in accordance with the
requirements of Vol 2, Pt 8, Ch 2 Other Pressure Vessels and Vol 2, Pt 1, Ch 4 Requirements for Fusion Welding of Pressure Vessels and Piping as applicable. Plans are to
be submitted for consideration as required by Vol 2, Pt 8, Ch 2, 1.6 Plans.
2.4.10 Sea-water
systems for refrigeration condensers are to be capable of being supplied
from not less than two independent sources. If specified, these sources
are to be located in separate compartments and zones such that the
loss of one zone or compartment will not result in the loss of all
sea-water supply sources.
2.5 Air coolers and cooling grids
2.5.1 Refrigerated
spaces may be cooled by air coolers or cooling grids on the deckhead,
bulkheads, and sides. In order to minimise the dehydration of the
stores and the frosting of the air coolers or cooling grids, the installation
is to be designed to maintain the required temperatures as defined
in the System Design Description with a minimum of difference between
the refrigerant and space temperatures.
2.5.2 The
refrigeration capacity of the air cooler arrangement is to be such
that the provisions room temperature conditions defined in the System
Design Description can be maintained under normal operating conditions.
The capacities of the fans are also to be such that they can maintain
the required air flow rates and uniform air temperature throughout
the refrigerated spaces, when part or fully loaded with stores.
2.5.3 Air
cooler fan motors are to be suitably enclosed to withstand the effects
of moisture.
2.5.4 Means
are to be provided for effectively defrosting air coolers. Air coolers
are to be provided with trays of suitable depth arranged to collect
all condensate. The trays are to be provided with drains at their
lowest points to enable the condensate to be drained away when the
refrigerated spaces are in service. Provision is to be made for the
prevention of freezing of the condensate.
2.5.5 Air
coolers are to be located such that when the refrigerated spaces are
loaded with stores, adequate space is provided for the inspection,
servicing and renewal of controls, valves, fans and fan motors.
2.5.6 Steel
air cooler circuits and cooling grids are to be suitably protected
against external corrosion.
2.6 Refrigeration units
2.6.1 A refrigerating
unit is considered to comprise a compressor, its driving motor and
one condenser. Where a secondary refrigerant, such as brine, is employed,
the unit is also to include an evaporator (secondary refrigerant cooler)
and a secondary refrigerant pump.
2.6.2 Two
or more compressors driven by a single motor, or having only one condenser
or evaporator/secondary refrigerant cooler, are to be regarded as
one unit.
2.6.3 The
refrigerating units of a classed provision stores installation are
to be completely independent of any refrigerating machinery associated
with air conditioning plant, unless full details of any proposal have
been submitted and approved.
2.7 Design pressures
2.7.1 The
design pressure of the system will be regarded as equal to its maximum
working pressure.
2.7.2 The
maximum working pressure is the maximum permissible pressure within
the system (or part system) in operation or at rest. No relief valve
is to be set to a pressure higher than the maximum working pressure.
2.7.3 The
design pressure of the low pressure side of the system is to be the
saturated vapour pressure of the refrigerant at plus 46°C. Due
regard is to be taken of defrosting arrangements which may cause a
higher pressure to be imposed on the low pressure system.
2.7.4 The
minimum design pressure of the high pressure side of the system (P
dh), is to be 1,11 × P
b, where P
b is an allowance for the compressor high pressure
cut-out. P
b is to be at least equal to 1,11
× P
a, where P
a is
the condenser working pressure, when operating in tropical zones and
equates to the saturation pressure at 46°C.
2.7.5 Design
pressures (bar g) applicable to refrigerants are to be not less than
the values given in Table 2.2.1 Pressure limits when
condensers are sea-water cooled. The design pressure for other refrigerants
is to be agreed with LR.
Table 2.2.1 Pressure limits
Refrigerant
|
Pressure (bar g)
|
High
|
Low
|
R-22
|
20,6
|
16,7
|
R-290
|
18,1
|
14,7
|
R-600a
|
6,4
|
5,2
|
R-134a
|
13,4
|
10,9
|
R-407C
|
23,5
|
19,0
|
R-410A
|
34,5
|
28,0
|
R-507A
|
25,3
|
20,5
|
R-404A
|
24,8
|
20,1
|
Note In view of increasing world-wide restrictive legislation
and phasing out of the refrigerant R-22, it is recommended that this
refrigerant should not be used in any new installation.
|
2.8 Room insulation
2.8.1 Where
applicable, having regard to their location and environmental conditions,
insulation materials are to be:
- suitably resistant to fire;
- suitably resistant to the spreading of flame;
- adequately protected against penetration of water vapour; and
- adequately protected against mechanical damage.
2.8.3 Where
the in situ foam type of insulation is proposed, full
details of the process are to be submitted for approval.
|