Section 17 Fire safety systems
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules and Regulations for the Classification of Ships, July 2022 - Part 6 Control, Electrical, Refrigeration and Fire - Chapter 2 Electrical Engineering - Section 17 Fire safety systems

Section 17 Fire safety systems

17.1 Fire detection and fire alarm systems

17.1.1 Fire detection and fire alarm systems are to comply with Chapter 9 of the Fire Safety Systems Code (FSS Code), SOLAS Chapter II-2, Part C, Regulation 7 - Detection and alarm and the requirements in this Section.

17.1.2 In passenger ships, a section of detectors and manually operated call points shall not be situated in more than one main vertical or horizontal zone, except on cabin balconies.

17.2 Automatic Sprinkler, fire detection and fire alarm systems

17.2.1 Automatic sprinkler, fire detection and fire alarm systems are to comply with Chapter 8 - Automatic Sprinkler, Fire Detection and Fire Alarm Systems of the FSS Code. See also Pt 6, Ch 2, 1.16 Operation under fire conditions.

17.3 Fixed water-based local application fire-fighting systems

17.3.1 Fixed water-based local application fire-fighting systems are to comply with SOLAS, Chapter II-2, Part C, Regulation 10 - Fire fighting, Section 5.6 and Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.2 to Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.13.

17.3.2 The fire detection, control and alarm systems are to be provided with an emergency source of electrical power required by Pt 6, Ch 2, 3.3 Emergency source of electrical power in passenger ships or Pt 6, Ch 2, 3.4 Emergency source of electrical power in cargo ships and are also to be connected to the main source of electrical power. Separate feeders, reserved solely for this purpose, with automatic changeover facilities located in, or adjacent to, the main control panel are to be provided.

17.3.3 Failure of any power supply is to operate an audible and visual alarm. See also Pt 6, Ch 2, 1.14 Alarms and Pt 6, Ch 2, 1.15 Labels, signs and notices.

17.3.4 Means to activate a system are to be located at easily accessible positions inside and outside the protected space. Arrangements inside the space are to be situated such that they will not be cut off by a fire in the protected areas and are suitable for activation in the event of escape. Where it is proposed to install local activation means outside of the protected space, details are to be submitted for consideration.

17.3.5 As far as is practicable, electrical and electronic equipment is not to be located within protected areas or adjacent areas.

17.3.6 High voltage equipment and their enclosures are not to be installed in protected areas or adjacent areas. For high voltage generators enclosures which cannot be fully located outside of adjacent areas due to close proximity, a technical justification, including proposed degree of protection ratings that are normally not to be lower that IP54, may be submitted for consideration that demonstrates the overall safety of the installation in the event of system operation.

17.3.7 In addition to the degree of protection requirements of Pt 6, Ch 2, 1.11 Location and construction 1.11.1, electrical and electronic equipment enclosures located within protected areas and within adjacent areas are to provide adequate protection in the event of system operation.

17.3.8 To demonstrate compliance with Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.7, evidence of the suitability of electrical and electronic equipment for use in protected areas and adjacent areas is to be submitted in accordance with Pt 6, Ch 2, 1.2 Documentation required for design review 1.2.13. The evidence is to demonstrate that additional precautions have been taken, where necessary, in respect of:

  1. satisfying Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.5 and Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.6;

  2. personnel protection against electric shock;

  3. cooling airflow, where necessary, for equipment required to operate during system operation; and

  4. maintenance requirements for equipment before return to operation following system activation.

Any test evidence submitted is to consider the overall installation, including equipment types, system configuration and nozzles and the potential effects of airflows in the protected space.

17.3.9 The evidence required by Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.8 is to demonstrate the safe and effective operation of the overall arrangements in the event of system operation. This evidence is to demonstrate that exposure to system spray and/or water:

  • cannot result in loss of essential services (e.g. unintended activation of automatic machinery shutdown);
  • cannot result in loss of availability of emergency services;
  • will not affect the continued safe and effective operation of electrical and electronic equipment required to operate during the required period of system operation;
  • does not present additional electrical or fire hazards; and
  • would require only identified readily replaceable components to be repaired or replaced.

The installation of electrical and electronic equipment required to provide essential or emergency services in enclosures with a degree of protection less than IP44 within areas exposed to direct spray is to be acceptable to LR, and evidence of suitability is to be submitted accordingly.

17.3.10 Fixed water-based local application fire-fighting system electrically driven pumps may be shared with:

  • equivalent automatic sprinkler systems;
  • equivalent main machinery space fire-fighting systems; or
  • local fire-fighting systems for deep-fat cooking equipment;

provided that the shared use is accepted by the National Administration as complying with applicable statutory regulations and the arrangements comply with the requirements of Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.11 to Pt 6, Ch 2, 17.3 Fixed water-based local application fire-fighting systems 17.3.13.

17.3.11 Shared electrically driven sea-water pumps are to be served by not less than two circuits reserved solely for this purpose, one fed from the main source of electrical power and one from the emergency source of electrical power. Such feeders are to be connected to an automatic changeover switch situated near the pumps and the switch is to be normally closed to the feeder from the main source of electrical power. No other switches are permitted in the feeders. The switches on the main and emergency switchboards are to be clearly labelled and normally kept closed.

17.3.12 Failure of a component in the power and control system is not to result in a reduction of the total available pump capacity below that required by any of the areas which the system is required to protect. For equivalent automatic sprinkler systems, a failure is not to prevent automatic release or reduce sprinkler pump capacity by more than 50 per cent.

17.3.13 Where fire-fighting systems share fire-fighting pumps, failure of one system is not to prevent activation of the pumps by any other system.

17.4 Fire pumps

17.4.1 When the emergency fire pump is electrically driven, the power is to be supplied by a source other than that supplying the main fire pumps. This source is to be located outside the machinery spaces containing the main fire pumps and their source of power and drive units.

17.4.2 The cables to the emergency fire pump are not to pass through the machinery spaces containing the main fire pumps and their source of power and drive units. The cables are to be of a fire-resistant type where they pass through other high fire risk areas.

17.5 Fixed gas fire-extinguishing systems

17.5.1 Where there are electrically operated fixed gas fire-extinguishing systems, they are to comply with Chapter 5 - Fixed Gas Fire-Extinguishing Systems of the FSS Code.

17.5.2 Where there are electrically driven refrigeration units for carbon dioxide fire-extinguishing systems, one unit is to be supplied by the main source of electrical power and the other unit from the emergency source of electrical power.

17.5.3 Each electrically driven carbon dioxide refrigerating unit is to be arranged for automatic operation in the event of loss of the alternative unit.

17.5.4 Where it is required that alarms be provided to warn of the release of a fire-extinguishing medium, and these are electrically operated;

17.5.5 The opening of the fire-extinguishing media control cabinet door, or panel, for any purpose other than for the release of the fire-extinguishing media, is not to cause the loss of any essential services, see Pt 6, Ch 2, 1.6 Definitions 1.6.1.

17.6 Fire safety stops

17.6.1 In order to limit the fire growth potential in every space of the ship, means for controlling the air supply to the spaces and flammable liquids within the spaces are to comply with SOLAS Chapter II-2, Part B, Regulation 5 - Fire growth potential.

17.6.2 In passenger ships, the control and indication arrangements at the central control station are to comply with SOLAS Chapter II-2, Part A, Regulation 3 - Definitions.

17.6.3 In passenger ships and cargo ships, to which SOLAS 1974 as amended applies, exhaust ducts from main laundries, drying rooms and galley ranges are to be fitted with additional remote-control arrangements as required by SOLAS, Chapter II-2, Part C, Regulation 9 - Containment of fire, Section 7.

17.6.4 To control flammable liquids, a means of stopping all fuel oil, lubricating oil, hydraulic oil, cargo oil and thermal oil pumps, oil purifiers from outside the spaces being served is to be provided. The position is not to be cut off in the event of a fire.

17.6.5 Means of cutting off all electrical power to the galley except lighting circuits, in the event of a fire, is to be provided outside the galley exits, at positions which will not readily be rendered inaccessible by such a fire. Consideration may be given to relaxing this requirement for supplies to equipment not used for heating or cooking (e.g. alarm and clock systems) that do not present an electrical shock risk to fire-fighting personnel.

17.6.6 Following activation of any fire safety stops, a manual reset is to be provided in order to restart the associated equipment.

17.6.7 Fire safety stop systems are to be designed on the fail safe principle or alternatively the power supplies to, and the circuits of, the fire safety stop systems are to be continuously monitored and an alarm initiated in the event of a fault. Cables are to be of a fire-resistant type, see Pt 6, Ch 2, 11.5 Construction 11.5.3. See also Pt 6, Ch 2, 5.2 Essential services 5.2.1.

17.7 Fire doors

17.7.1 The electrical power required for the control, indication and alarm circuits of fire doors is to be provided by an emergency source of electrical power as required by Pt 6, Ch 2, 3.3 Emergency source of electrical power in passenger ships. In passenger ships carrying more than 36 passengers an alternative supply fed from the main source of electrical power, with automatic change over facilities, is to be provided at the central control station. Failure of any power supply is to operate an audible and visual alarm, see also Pt 6, Ch 2, 1.14 Alarms and Pt 6, Ch 2, 1.16 Operation under fire conditions.

17.7.2 The control and indication systems for the fire doors are to be designed on the fail-safe principle with the release system having a manual reset.

17.8 Fire dampers

17.8.1 The electrical power required for the control and indication circuits of fire dampers is to be supplied from the emergency source of electrical power, see also Pt 6, Ch 2, 1.16 Operation under fire conditions.

17.8.2 The control and indication systems for the fire dampers are to be designed on the fail-safe principle with the release system having a manual reset.

17.8.3 In passenger ships and cargo ships, to which SOLAS 1974 as amended applies, where electrically operated fire dampers are fitted in main laundries, drying rooms and galley ranges, they are to be as required by SOLAS, Ch II-2, Part C, Regulation 9 - Containment of fire, Section 7.

17.9 Safety centre on passenger ships

17.9.1 Safety centres on passenger ships are to comply with SOLAS Chapter II-2, Part G, Regulation 23 - Safety centre on passenger ships.

17.9.2 Operation, control and/or monitoring facilities provided at the safety centre are additional to any dedicated facilities required at other locations by the Rules or the National Administration.

17.9.3 Where arrangements are operated, controlled and/or monitored from the safety centre in accordance with Pt 6, Ch 2, 17.9 Safety centre on passenger ships 17.9.2, they are to comply with the relevant requirements of Pt 6, Ch 1, 2 Essential features for control, alarm, monitoring and safety systems in respect of control, alarm and programmable electronic systems.

17.10 Electrically powered air compressors for breathing air cylinders

17.10.1 In passenger ships carrying more than 36 passengers where electrically powered air compressors are installed they are to be in accordance with SOLAS, Chapter II-2, Part C, Regulation 10 - Fire fighting, Section 10.2.6.1.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.