Section
10 Container ships fitted with refrigerating plant to supply cooled
air to insulated containers in holds
10.1 General
10.1.2 The
classed refrigerating installation is to include the refrigerating
machinery, air coolers, supply and return air ducting, and the flexible
couplings between containers and the duct system. Where the arrangements
are such that cell air conditioning is essential to the carriage of
the containers, the air conditioning equipment and (if fitted) the
insulation of the hold, deckheads, sides and tank tops are to be included
in the classification.
10.2 Additional information and plans
10.2.1 In
addition to those requirements detailed in Pt 6, Ch 3, 1 General requirements which are also applicable to refrigerated container ships,
the following information is to be submitted before the work commences:
- Details of air coolers.
- Details of the design of ducting proposed, including joints, connections,
insulation, vapour sealing and linings.
- Details of cell air conditioning arrangements and components.
- Details of couplings between ducting and containers, including
operating arrangements.
10.3 Air coolers
10.3.1 Air
ducts supplying more than ten standard 20 ft containers or five standard
40 ft containers are to have a single air cooler with multiple circuits
or two independent coolers. The individual circuits or coolers are
to be provided with stop valves so that each circuit or cooler may
be readily isolated.
10.3.2 The
refrigeration capacity of the air cooler arrangement is to be such
that the temperature conditions can be maintained with any one circuit
or independent cooler out of action.
10.3.3 For
air ducts supplying ten standard 20 ft containers or five standard
40 ft containers or less, a single cooler with one circuit will be
acceptable.
10.4 Air duct systems
10.4.1 The
air ducts, together with all branches and couplings, supplying refrigerated
air to insulated containers in holds, are to be made airtight. For
design purposes, however, an air leakage rate of 0,5 per cent of total
volume flow at the design pressure for each duct is to be taken.
10.4.2 Where
air ducting is insulated on the internal surfaces, provision is to
be made to prevent retention of odour which may taint subsequent cargo.
10.4.3 Couplings
are to be of a type that has been approved by LR. Prototypes are to
be tested under all operating conditions, witnessed by the Surveyors,
to demonstrate that they extend, retract and separate satisfactorily
from a `container end wall' at the minimum temperature condition.
When operated by means of air pressure they are to be supplied with
air sufficiently dry to avoid ice formation. The air supply lines
are to be strength pressure tested to 1,5 × design pressure.
10.5 Duct air leakage and distribution tests
10.5.1 Air
leakage tests on at least 10 per cent of ducting, selected at random,
are to be carried out to the satisfaction of the Surveyors before
the insulation is applied. The Surveyors may require further testing
to demonstrate airtightness of ducting. The air leakage from each
duct will depend on several factors and, while complete airtightness
should be the objective, the air leakage rate for design purposes
is not to exceed 0,5 per cent of total volume flow at the design pressure
of 250 Pa.
10.5.2 In
the case of prefabricated ducts, the prototype is to be subjected
to air distribution, heat leakage and air leakage tests. Each production
duct is to be tested for air leakage and is not to exceed the prototype
test results by more than five per cent. Additionally, one duct in
50 or part thereof is to be tested for heat leakage and the results
are not to exceed the prototype test results by more than 10 per cent.
10.5.4 On
application from the Owner, the air leakage tests on air ducts installed
aboard the ship, as detailed in Pt 6, Ch 3, 10.5 Duct air leakage and distribution tests 10.5.1, may be omitted provided that:
- the installation is designed with at least 20 per cent surplus
refrigerating capacity, or
- assignment of a temperature notation for the installation be deferred
until verified by a thermal balance test to the Surveyor's satisfaction.
10.5.5 All
ducts are to be tested for air distribution to the containers, at
the manufacturer's works, by measuring the flow of air from the supply
couplings while the fan is operated at full speed against the designed
pressure. The air flow at each coupling is to meet the specified figure
within ±5 per cent.
10.5.6 Systems
comprising rigid prefabricated ducts complete with coolers and fans
are to be tested for air distribution at the place of manufacture.
The remaining tests are to be carried out aboard the ship.
10.6 Cell air-conditioning arrangements
10.6.1 The
cell air-conditioning equipment and ducting, and/or insulation of
the holds, deckheads, sides and tank tops, is to be such as to maintain
a uniform temperature throughout the cell and to ensure the ship's
steelwork is maintained above the minimum temperature acceptable for
the steel grade, see also
Pt 3, Ch 2, 2.2 Refrigerated spaces.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
![](LR-FooterLogo.png) |
|