Section
4 Electrical system
4.1 Electrical Load Transfer
4.1.1 ‘Dead
transfer’ arrangements are to be provided that permit transfer
between operation using ship sources of electrical power and an external
electrical power supply by disconnecting one from the ship distribution
system and then connecting the other to the dead system.
4.1.3 Means
to automatically synchronise a ship source of electrical power with
an external electrical power supply and connect them in parallel for
load transfer when requested by operating staff are to be provided.
4.1.4 Means
to automatically transfer load between a ship source of electrical
power and an external electrical power supply following their connection
in parallel, are to be provided. The load transfer is to be completed
in as short a time as practicable without causing machinery or equipment
failure or operation of protective devices and this time is to be
used as the basis for defining the Transfer Time Limit required by Pt 7, Ch 13, 4.1 Electrical Load Transfer 4.1.5.
4.1.5 When
transferring of load between ship sources of electrical power and
an external electrical power supply exceeds a defined Transfer Time
Limit then, arrangements are to be such that:
- the transfer is aborted;
- load is removed from the ship sources of electrical power or external
electrical power supply that was intended to take the load; and then
- the Connection Circuit-Breaker is opened.
An alarm is to be provided at a machinery control station that
is attended when connected to an external electrical power supply
when the Transfer Time Limit is exceeded and is to indicate the return
to previous operating conditions.
4.1.7 An
external power supply may only be connected in parallel with a single
ship source of electrical power. Arrangements are to be provided to
ensure that this requirement is satisfied before and during parallel
connection. Details of alternative proposals may be submitted for
consideration.
4.1.8 Arrangements
provided to adjust ship sources of electrical power to allow connection
in parallel and transfer of load are not to cause machinery or equipment
failure, operation of protective devices or damage under normal conditions
or in the event of a failure.
4.1.9 Where
load reductions are required to transfer load they are not to result
in loss of essential services or the loss of availability of emergency
services. Means are to be provided to readily make necessary load
reductions and re-instate supplies following transfer.
4.2 Capacity
4.2.1 Arrangements
for operating from external supplies are to be sufficiently rated
to supply the following:
- essential services normally required in port;
- emergency services;
- services required to ensure ready availability of non-operating
main and auxiliary machinery;
- services required to prevent damage to cargo or stores; and
- the services required for the Defined Operations.
The schedule of loads required by Pt 6, Ch 2, 1.3 Documentation required for supporting evidence 1.3.3 is to incorporate operation when connected
to an external electrical power supply.
4.2.3 Consideration
is to be given to providing means to inhibit automatically the connection
of large motors, or the connection of other large loads, that the
arrangements are not rated to supply when connected to an external
electrical power supply having the defined minimum apparent power
or current capacity, see
Pt 7, Ch 13, 3.1 General 3.1.10 and Pt 6, Ch 2, 6.9 Load management 6.9.4.
4.3 Protection
4.3.1 Where an external electrical power supply is not arranged to operate in
parallel with ship sources of electrical power, the connection to the external
electrical power supply is to be provided with a Connection Circuit-Breaker arranged to
open simultaneously, in the event of short-circuit, overload or undervoltage, all
insulated poles.
4.3.2 Where an external electrical power supply is arranged to operate in parallel
with ship sources of electrical power during load transfer, the connection to the
external electrical power supply is to be provided with a Connection Circuit-Breaker
arranged to open simultaneously, in the event of a short-circuit, an overload or an
undervoltage, all insulated poles. This circuit-breaker is to be provided with reverse
power protection with time delay, selected or set within the limits of 2 per cent to 15
per cent of full load to a value fixed in accordance with the rating defined in the
Design Statement; a fall of 50 per cent in the applied voltage is not to render the
reverse power mechanism inoperative, although it may alter the amount of reverse power
required to open the circuit breaker.
4.3.3 The electrical system, including short-circuit protective device rating, is
to be suitable for the highest prospective fault level at the point of installation. The
short-circuit current calculations required by Pt 6, Ch 2, 1.2 Documentation required for design review 1.2.6 are to identify the system state that
would result in the highest prospective fault level. The highest prospective fault level
may occur during parallel connection with an external power supply and the resulting
combination of:
-
ship sources of electrical power, taking into account Pt 7, Ch 13, 4.1 Electrical Load Transfer 4.1.7; and
-
an external electrical power supply having the defined maximum
permitted prospective fault level, see
Pt 7, Ch 13, 4.1 Electrical Load Transfer 4.1.7.
Details of alternative proposals may be submitted for consideration.
4.3.4 The connection circuit is to be arranged such that contamination due to the
products of arcing as a result of a fault in the Connection Circuit-Breaker enclosure on
the external power supply side will not result in essential or emergency services not
being available when supplied by ship sources of electrical power.
4.3.5 Initial connection of an external electrical power supply to the ship
switchboards or converter equipment to connect to ship loads is to be arranged to be
made by closing of the Connection Circuit-Breaker only.
4.3.6 Converter equipment used to connect an external electrical power supply to
the ship electrical system is to ensure that a supply that would result in damage is not
applied to the connected ship electrical systems in the event of a failure.
4.3.7 The voltage and time delay settings of the Connection Circuit-Breaker
undervoltage release mechanism( s) are to be selected to ensure that the discriminative
action required by Pt 6, Ch 2, 6.1 General 6.1.1 is maintained.
4.3.8 Means are to be provided to prevent closure of the Connection
Circuit-Breaker when a connected external electrical power supply has a different phase
rotation or has a voltage or frequency that does not match the ship electrical system
rating within the tolerances defined by Pt 6, Ch 2, 1.8 Quality of power supplies 1.8.2 or Pt 6, Ch 2, 1.8 Quality of power supplies 1.8.5. Signals are to be provided, where necessary, to
allow comparison with ship electrical system characteristics.
4.3.9 For high voltage connections means are to be provided to ensure the circuit breaker
cannot be closed when any of the following conditions exist:
- one of the earthing switches is closed (shore-side/ship-side);
- the safety circuit is not established;
- emergency-stop facilities are activated;
- ship or shore control, alarm or safety system self-monitoring diagnostics detect an
error that would affect safe connection;
- the data-communication link between shore and ship is not operational, where
applicable;
- the permission from the ship is not activated;
- the HV supply is not present;
- equipotential bonding is not established (via equipotential bond monitoring devices
where utilised, or via manual override);
- the cabinet door is in the open position; or
- cable plugs both shore and ship are not fully inserted into the socket.
4.3.10 Means are to be provided to ensure that the disconnector cannot be closed, or the
circuit breaker cannot be racked into service position when any of the following
conditions exist:
- one of the earthing switches is closed (shore-side/ship-side);
- the safety circuit is not established;
- the communication link between shore and ship is not operational, where
applicable; or
- equipotential bonding is not established (via equipotential bond monitoring
devices where utilised, or via manual override).
4.4 Interlocking and synchronising arrangements
4.4.1 External
electrical power supply connections are to be provided with instruments
and devices on board equivalent to those required for alternating
current generators by Pt 6, Ch 2, 7.11 Instruments for alternating current generators 7.11.1 where synchronising is not provided, or by Pt 6, Ch 2, 7.11 Instruments for alternating current generators 7.11.2 to Pt 6, Ch 2, 7.11 Instruments for alternating current generators 7.11.3 where synchronising for
load transfer is provided. See also
Pt 6, Ch 2, 7.11 Instruments for alternating current generators and Pt 6, Ch 2, 7.12 Instrument scales.
4.4.2 Means
are to be provided to ensure that a source of electrical power or
electrical power supply can only be connected to other live parts
when synchronised. See also
Pt 7, Ch 13, 4.1 Electrical Load Transfer 4.1.2 for temporary parallel connection
for load transfer.
4.4.3 The
arrangements are to prevent Connection Equipment power conductors
being made live by connecting to the ship electrical system.
4.4.4 The
simultaneous connection of a ship source of electrical power and external
electrical power supply to the same dead part of the electrical system
is to be prevented.
4.4.5 For
high-voltage connections, suitable means are to be provided to earth
the connection power circuit so that it is discharged and so maintained
that it is safe to touch.
4.4.6 Means
provided to connect a connection power circuit to earth are to be
arranged such that the circuit may only be earthed when it is isolated.
4.5 Ship power restoration
4.5.1 When
the ship main source of electrical power is shutdown and failure of
the connected external electrical power supply occurs, the Connection
Circuit-Breaker is to be arranged to automatically open followed by:
-
connection of
the emergency source of electrical power to emergency services in
accordance with Pt 6, Ch 2, 3.3 Emergency source of electrical power in passenger ships 3.3.1 or Pt 6, Ch 2, 3.4 Emergency source of electrical power in cargo ships 3.4.1 as applicable;
and
-
automatic connection
of the transitional source of electrical power to emergency services
in accordance with Pt 6, Ch 2, 3.3 Emergency source of electrical power in passenger ships 3.3.1 or Pt 6, Ch 2, 3.4 Emergency source of electrical power in cargo ships 3.4.1 as applicable;
and
-
automatic starting
and connecting to the main switchboard of the main source of electrical
power and automatic sequential restarting of essential services, in
as short a time as is practicable. See also
Pt 7, Ch 13, 2.1 General requirements 2.1.3 and Pt 6, Ch 2, 2.2 Number and rating of generators and converting equipment 2.2.3.
Failures include loss of power, disconnection, phase failure
and quality of supply outside the tolerances given in Pt 6, Ch 2, 1.8 Quality of power supplies 1.8.2 or Pt 6, Ch 2, 1.8 Quality of power supplies 1.8.5.
4.5.2 An
alarm is to be provided at a machinery control station that is attended
when connected to an external electrical power supply to indicate
activation of the automatic power supply failure response required
by Pt 7, Ch 13, 4.5 Ship power restoration 4.5.1. The alarm is to
indicate the failure that caused the activation.
|