Section 
                     3 Emergency source of electrical power
                  
                  
                  
                  
                  
                  
                  
                     
                        
                         
                        3.1 General
                        
                        
                        
                        
                           
                           
                              
                              
                              3.1.1 The requirements of this Section apply to units to be classed for
                                 unrestricted service. They do not apply to units of less than 500 tons gross
                                 tonnage. Alternative arrangements in accordance with the requirements of the
                                 National Administration may also be acceptable.
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              3.1.3 The emergency source of power for units of less than 500 tons gross
                                 tonnage will be the subject of special consideration.
                               
                              
                              
                            
                           
                           
                           
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.2 Emergency source of electrical
                           power
                        
                        
                        
                        
                           
                           
                           
                           
                           
                              
                              
                              3.2.2 The emergency source of electrical power, associated transforming
                                 equipment, if any, transitional source of emergency power, emergency switchboard and
                                 emergency lighting switchboard are to be located in a non-hazardous space above the
                                 uppermost continuous deck and above the worst damage waterline, inboard of the
                                 damage zones, see Pt  4, Ch  7,  2 Definitions and Pt  4, Ch  7,  3 Installation layout and stability. They are not to be located forward of the
                                 collision bulkhead, if any. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              3.2.3 The space containing:
                                  
                                    - the emergency source of electrical power, associated
                                       transforming equipment, if any;
                                    
 
                                    - the transitional source of emergency electrical power; and
 
                                    - the emergency switchboard;
 
                                  
                                 
                               
                              
                              
                              
                              is not to be contiguous to the boundaries of hazardous areas or
                                 machinery spaces of Category A or those spaces containing: 
                                  
                                    - the main source of electrical power, associated transforming
                                       equipment, if any; or
                                    
 
                                    - the main switchboard.
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              3.2.4 The electrical power available is to be sufficient to supply all those
                                 services that are essential for safety in an emergency, due regard being paid to
                                 such services as may have to be operated simultaneously. 
                               
                              
                              
                              
                              Where emergency sources of electrical power such as Uninterruptible Power
                                 Systems (UPS) systems are required to support sequential depressurisation systems,
                                 the location and integrity of the systems are to meet the requirements of Pt  3, Ch  8,  3.7 Depressurising system 3.7.8. The
                                 performance of the sequential depressurisation system shall not be impacted due to
                                 the location of UPS or routing of cables in the event of a fire or explosion in the
                                 room.
                               
                              
                              
                              
                              The emergency source of electrical power is to be capable, having regard to starting
                                 currents and the transitory nature of certain loads, of supplying simultaneously at
                                 least the following services for the periods specified hereinafter, if they depend
                                 upon an electrical source of power for their operation:
                               
                              
                              
                              
                              
                                 
                                 
                                    - For a period of 18 hours, emergency
                                       lighting:
                                       
                                          - in alleyways, stairways and exits, giving access to the
                                             muster and embarkation stations:
                                          
 
                                          - in all service and accommodation alleyways, stairways
                                             and exits, personnel lift cars and personnel lift;
                                          
 
                                          - in the machinery spaces and main generating stations
                                             including their control positions;
                                          
 
                                          - in all control stations, machinery control rooms, and
                                             at each main and emergency switchboard;
                                          
 
                                          - at all stowage positions for fireman’s outfits;
 
                                          - at the steering gear;
 
                                          - at the emergency fire pump, at the sprinkler pump, if
                                             any, and at the emergency bilge pump, if any, and at the starting
                                             positions of their motors;
                                          
 
                                          - in any stored oil pump-room;
 
                                          - at every survival craft preparation station, muster and
                                             embarkation station and over the sides;
                                          
 
                                          - on helicopter decks, to include deck perimeter lights
                                             and helideck status lights, wind direction indicator illumination,
                                             and related obstruction lights, if any;
                                          
 
                                          - in all spaces from which control of the drilling
                                             process or pipe-laying operations (as defined in Pt  3, Ch  17,  1.1 Application 1.1.1) is performed
                                             and where controls of machinery essential for the performance of
                                             this process, or devices for emergency switching off of the power
                                             plant are located; and
                                          
 
                                          - at ESD manual activation points.
 
                                        
                                       
                                     
                                    - For a period of 18 hours:
                                       
                                          - the navigation lights and other
                                             lights and sound signals required by the International
                                                Regulations for the Prevention of Collisions at Sea in
                                             force; 
                                          
 
                                          - the radio communications as required
                                             by Amendments to Chapter IV - Radiocommunications; 
                                          
 
                                          - permanently installed diving equipment necessary for
                                             the safe conduct of diving operations, if dependent upon the unit’s
                                             electrical power;
                                          
 
                                          - the emergency fire pump if dependent upon the emergency
                                             generator for its source of power;
                                          
 
                                          - one of the refrigerated liquid carbon dioxide units
                                             intended for fire protection, where both are electrically
                                             driven;
                                          
 
                                          - on column-stabilised units: ballast pump control
                                             system, ballast pump status-indicating system, ballast valve control
                                             system, ballast valve position indicating system, draft level
                                             indicating system, tank level indicating system, heel and trim
                                             indicators, power availability indicating system (main and
                                             emergency), ballast system hydraulic/pneumatic pressure-indicating
                                             system and the largest capacity ballast pump required by Pt  5, Ch  13,  11 Ballast system of the Rules and Regulations for the Classification of Ships, July 2022; and 
                                          
 
                                          - abandonment systems dependent on electric power.
 
                                        
                                       
                                     
                                    - For a period of 18 hours:
                                       
                                          - the navigational aids as required by
                                             Amendments to Regulation 19–1 - Long-range identification and tracking of ships1 as
                                             applicable; 
                                          
 
                                          - general alarm and communication
                                             systems required in an emergency;
                                          
 
                                          - intermittent operation of the
                                             daylight signalling lamp and the unit’s whistle, the manually
                                             operated call points and all internal signals that are required in
                                             an emergency;
                                          
 
                                          - the fire and gas detection systems
                                             and their alarms; and
                                          
 
                                          - the capability of closing the blow
                                             out preventer and of disconnecting the unit from the wellhead
                                             arrangement, if electrically controlled, unless such services have
                                             an independent supply from an accumulator battery suitably located
                                             for use in an emergency and sufficient for the period of 18
                                             hours.
                                          
 
                                        
                                       
                                     
                                    - The steering gear for the period of time
                                       required by Pt  5, Ch  19,  6 Emergency power of theRules and Regulations for the Classification of Ships, July 2022. 
                                    
 
                                    - For a period of four days, any signalling
                                       lights or sound signals which may be required for marking offshore
                                       structures, unless such services have an independent supply from an
                                       accumulator battery suitably located for use in an emergency and sufficient
                                       for the period of four days.
                                    
 
                                    - For a period of half an hour:
                                       
                                          - power to operate any watertight doors but not
                                             necessarily all of them simultaneously, unless an independent
                                             temporary source of stored energy is provided; and
                                          
 
                                          - power to operate the controls and indicators
                                             provided.
                                          
 
                                        
                                       
                                     
                                    - Where applicable, the services required by
                                       Pt  6, Ch  2,  2.3 Starting arrangements 2.3.2. 
                                    
 
                                    - For a minimum of 30 minutes, the ESD system
                                       with its indication circuits as required by Pt  7, Ch  1,  7.1 General 7.1.10
                                       
                                    
 
                                  
                                 
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              3.2.5 The emergency source of electrical power may be either a generator or an
                                 accumulator battery, which is to comply with the following:
                                  
                                    - Where the emergency source of electrical
                                       power is a generator it is to be:
                                       
                                          - driven by a suitable prime mover with an independent
                                             supply of fuel, having a flashpoint (closed-cup test) of not less
                                             than 43°C;
                                          
 
                                          - started automatically upon failure of the main source
                                             of electrical power supply unless a transitional source of emergency
                                             electrical power in accordance with Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.6 is provided; where the
                                             emergency generator is automatically started, it is to be
                                             automatically connected to the emergency switchboard; those services
                                             referred to in Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.6 are to be connected
                                             automatically to the emergency generator; and
                                          
 
                                          - provided with a transitional source of emergency
                                             electrical power as specified in Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.6 unless an emergency generator
                                             is provided capable both of supplying the services mentioned in that
                                             paragraph and of being automatically started and supplying the
                                             required load as quickly as is safe and practicable subject to a
                                             maximum of 45 seconds.
                                          
 
                                        
                                       
                                     
                                    - Where the emergency source of electrical power is an accumulator
                                       battery it is to be capable of:
                                       
                                          - carrying the emergency electrical load without
                                             recharging while maintaining the voltage of the battery throughout
                                             the discharge period within 12 per cent above or below its nominal
                                             voltage;
                                          
 
                                          - automatically connecting to the emergency switchboard
                                             in the event of failure of the main source of electrical power;
                                             and
                                          
 
                                          - immediately supplying at least those services specified
                                             in Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.6.
                                          
 
                                        
                                       
                                     
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              3.2.6 The transitional source of emergency electrical power where required by
                                  Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.5 is to consist of an accumulator battery
                                 suitably located for use in an emergency which is to operate without recharging
                                 while maintaining the voltage of the battery throughout the discharge period within
                                 12 per cent above or below its nominal voltage and be of sufficient capacity and be
                                 so arranged as to supply automatically in the event of failure of either the main or
                                 the emergency source of electrical power for half an hour at least the following
                                 services if they depend upon an electrical source for their operation:
                                  
                                    - the lighting required by Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(a) and Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(c). For this transitional phase, the
                                       required emergency electric lighting, in respect of the machinery space and
                                       accommodation and service spaces may be provided by permanently fixed,
                                       individual, automatically charged, relay operated accumulator lamps,
                                       and
                                    
 
                                    - all services required by Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(c).(ii), Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(c).(iii), Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(c).(iv) and Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(c).(v) and Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4.(h) unless such services have
                                       an independent supply for the period specified from an accumulator battery
                                       suitably located for use in an emergency.
                                    
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.3 Starting arrangements
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.4 Prime mover governor
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.5 Radio installation
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.6 Accommodation units
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        3.7 Alternative sources of emergency
                           electrical power
                        
                        
                        
                        
                           
                           
                              
                              
                              3.7.1 Where it is proposed that a dedicated emergency source of electrical
                                 power and its associated transitional source of power will not be provided, the
                                 installation is to meet the requirements of this sub-Section.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              3.7.2 The main sources of electrical power are to be:
                                  
                                    - separated and located in two or more compartments that are not
                                       contiguous with each other;
                                    
 
                                    - self-contained and arranged to be independent such that each
                                       system can operate without recourse to the other main source(s) including
                                       power distribution and any associated converting equipment and control
                                       systems;
                                    
 
                                    - arranged such that a fire or casualty in any one of the
                                       compartments will not affect the electrical power distribution from the
                                       other(s), or to the services required by Pt  6, Ch  2,  3.2 Emergency source of electrical power 3.2.4; 
                                    
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                              
                              
                              3.7.8 Where these Rules specify that a service is required to be connected to
                                 both the main and emergency source of electrical power or is to be connected to the
                                 emergency switchboard, these services are to be served by at least two individual
                                 circuits from the separated main sources of electrical power with arrangements to
                                 transfer between the two sources. The supplies are to be separated in their
                                 switchboard and throughout their length as widely as is practicable without the use
                                 of common feeders, protective devices, control circuits or control gear assemblies,
                                 so that any single electrical fault will not cause the loss of both supplies.
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                           
                           
                         
                        
                        
                      
                     
                   
                
             |