Section
11 System arrangement requirements
11.1 General requirements
11.1.1 The BWTS arrangement is to satisfy the requirements of this Section as
applicable. The applicability of the requirements for each BWTS technology is to be in
accordance with Table 25.11.1 Applicability of the
requirements for each BWTS technology.
Table 25.11.1 Applicability of the
requirements for each BWTS technology
BWTS
category
|
1
|
2
|
3a
|
3b
|
3c
|
4
|
5
|
6
|
7a
|
7b
|
8
|
Pt 5, Ch 25, 11.1 General requirements 11.1.1 to Pt 5, Ch 25, 11.1 General requirements 11.1.7
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.1 General requirements 11.1.8 to Pt 5, Ch 25, 11.1 General requirements 11.1.11
|
|
|
x
|
x
|
x
|
|
|
|
|
|
x
|
Pt 5, Ch 25, 11.1 General requirements 11.1.12
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.1 General requirements 11.1.13
|
|
|
x
|
x
|
x
|
|
|
|
|
|
x
|
Pt 5, Ch 25, 11.1 General requirements 11.1.14
|
|
|
|
x
|
|
|
|
|
|
x
|
|
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.2
|
|
|
|
x
|
x
|
|
|
|
x
|
x
|
|
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.3
|
|
|
|
|
|
x
|
x
|
x
|
|
|
|
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.4 and Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.5
|
x
|
x
|
x
|
x
|
|
x
|
x
|
x
|
x
|
x
|
|
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.6
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.7
|
x
|
x
|
x
|
x
|
|
x
|
x
|
x
|
x
|
x
|
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(a)
|
|
x
|
x
|
|
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(b)
|
|
|
x
|
x
|
x
|
|
|
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(c)
|
|
|
|
|
|
|
|
|
x
|
x
|
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(d)
|
|
|
|
|
|
x
|
x
|
x
|
x
|
x
|
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(e)
|
|
|
|
|
|
x
|
x
|
x
|
|
|
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(f)
|
|
|
x
|
x
|
x
|
|
|
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(a) to Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(d)
|
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(e)
|
|
|
x
|
|
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(f)
|
|
|
x
|
|
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(g)
|
|
|
x
|
|
|
|
|
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(h)
|
|
|
x
|
|
|
x
|
x
|
x
|
x
|
x
|
x
|
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.3
|
|
x
|
|
|
|
x
|
x
|
x
|
x
|
x
|
|
|
BWTS
category
|
BWTS
Technologies
|
|
|
1
|
In-line UV or UV + Advanced Oxidation Technology (AOT) or UV + TiO2 or
UV + Plasma
|
|
|
2
|
In-line flocculation
|
|
|
3a
|
In-line membrane separation and de-oxygenation (injection of
N2 from a N2 generator)
|
|
|
3b
|
In-line de-oxygenation (injection of inert gas from inert gas generator)
|
|
|
3c
|
In-tank de-oxygenation with inert gas generator
|
|
|
4
|
In-line full flow electrolysis
|
|
|
5
|
In-line side stream electrolysis
|
|
|
6
|
In-line (stored) chemical injection
|
|
|
7a
|
In-line side-stream ozone injection without gas/liquid separation tank
and without discharge treatment tank
|
|
|
7b
|
In-line side-stream ozone injection with gas/liquid separation tank and
discharge water treatment tank
|
|
|
8
|
In-tank pasteurisation and de-oxygenation with N2 generator
|
|
|
|
|
|
|
11.1.2 The BWTS is to be provided with a by-pass and isolation or override
arrangement to effectively isolate it from the ship’s ballast system and any essential
ship system to which it is connected. The arrangement of the by-passes or overrides of
the BWTS is to be consistent with the Operation Maintenance and Safety Manual approved
by the Flag Administration during Type Approval.
11.1.3 The by-pass and isolation arrangements are to meet the electrotechnical
requirements of Pt 5, Ch 25, 9.1 General as applicable.
11.1.5 Under normal operating conditions of ballasting and de-ballasting given in the Ballast
Water Management Plan (BWMP), the adequacy of the generating plant capacity installed on
the vessel is to be demonstrated by an electrical load analysis. For retrofit
installation on existing ships, a revised electrical load analysis with preferential
trips of non-essential services can be accepted.
11.1.6 The BWTS is to be operated in accordance with the requirements specified in the Type
Approval Certificate (TAC) issued by the Flag Administration.
11.1.7 The BWTS is to be operated within its Treatment Rated Capacity (TRC) as specified in the
TAC. This may require limiting of the ship’s ballast pump(s) flow rate. In case the
maximum capacity of the ballast pump(s) exceeds the maximum TRC of the BWTS specified in
the TAC issued by the Flag Administration, there is to be a limitation in the BWMP
giving a maximum allowable flow rate for operating the ballast pump(s) that shall not
exceed the maximum TRC of the BWTS.
11.1.8 The BWTS’s components including pressure vessels, piping Class I or II, filters and
switchboards, section boards and distribution boards are required to be designed,
constructed and tested and certified as per relevant requirements of LR Rules.
11.1.9 Where a vacuum or overpressure may occur in the ballast piping or in the
ballast tanks due to the height difference or injection of inert gas or nitrogen
(N2), a suitable protection device is to be provided (i.e. P/V valves, P/V
breakers, P/V breather valves, pressure safety relief valves or high/low pressure
alarms).
The pressure and vacuum settings of the protection device are not to exceed
the design pressure of the ballast piping (BWTS categories 3a and 3b) or ballast tank
(BWTS categories 3a, 3b and 3c), as applicable.
For BWTS categories 3a, 3b and 3c, the inert gas or nitrogen product
enriched air from the inert gas system and from the protection devices installed on the
ballast tanks (i.e. P/V valves, P/V breakers or P/V breather valves) is to be discharged
to a safe location*(1) and (2) (see
Pt 5, Ch 25, 1.2 Definitions) on the open deck.
11.1.10 When the ballast tanks are considered hazardous areas, the hazardous area
is to include the outlet of the protection devices: with reference to Pt 6, Ch 2, 14.2 Hazardous areas 14.2.5 the
areas on the open deck, or semi-enclosed spaces on the open deck, within 1,5 m of their
outlets are to be categorised hazardous Zone 1 and with reference to Pt 6, Ch 2, 14.2 Hazardous areas 14.2.6, an
additional 1,5 m surrounding the 1,5 m hazardous Zone 1 is to be categorised hazardous
Zone 2. Any source of ignition such as anchor windlass or opening into chain locker is
to be located outside the hazardous areas. Further requirements of Pt 6, Ch 2, 14.2 Hazardous areas 14.2.5 are to be
complied with as applicable.
11.1.11 Where products covered by IEC 60092-502 are stored on board or generated during
operation of the BWTS, the requirements of this standard are to be followed in order
to
- Define hazardous areas and acceptable electrical equipment; and
- Design ventilation systems.
11.1.13 Inert gas systems installed for de-oxygenation BWTS (categories 3a, 3b, 3c and 8) are to
be designed in accordance with the following requirements:
- International Code for Fire Safety Systems
(FSS Code), Ch 15 Inert Gas Systems requirements
- Inert gas system and Gas-safe space are defined in
2.1.2, 2.1.3;
- for all inert gas systems, the general requirements of sections
2.2.1.3, 2.2.1.4, 2.2.2.1, the safety measures as per 2.2.2.2, 2.2.2.3,
2.2.2.6, indicators and alarms as per 2.2.4.1 to 2.2.4.5 with the exception of
clauses 2.2.4.5.1.3 and 2.2.4.5.3;
- for flue gas and inert gas generator systems, the system
requirements of sections 2.3.1.1.2, 2.3.1.2, 2.3.1.4.2, 2.3.1.5, 2.3.1.6 with
the exception of clause 2.3.2.2.1;
- for nitrogen generator systems, the system requirements 2.4.1.3,
2.4.1.4 and 2.4.2.
- For inert gas systems installed for in-tank de-oxygenation BWTS
(category 8): the requirements of 2.2.3.1, 2.2.3.2 except 2.2.3.2.6, 2.2.3.2.7
and 2.2.3.2.10.
In general, when applying FSS Code Ch 15
requirements to inert-gas based BWTS, the following modifications are
to be considered:
- The terms ‘cargo tank’ and ‘cargo piping’ are to be
replaced by ‘ballast water tank’ or ‘ballast water piping’ as
relevant;
- The term ‘cargo control room’ is to be replaced by ‘BWTS
control station’ as relevant;
- Requirements for slop tanks on combination carriers are
to be disregarded;
- When applying FSS Code 15.2.2.4.5.1.1, the acceptable
oxygen content is to be specified by the manufacturer. 5 per cent
oxygen content need not necessarily be applied.
- Pt 5, Ch 15, 7 Inert gas systems on Tankers of 8,000 tonnes DWT and above as applicable. The terms ‘cargo tanks’ and
‘cargo piping’ are to be understood as ‘ballast tanks’ and ‘ballast piping’
respectively. For de-oxygenation BWTS (categories 3a, 3b, 3c and 8), the requirements
in Pt 5, Ch 25, 11.1 General requirements 11.1.13.(a) prevail.
11.1.14 When cavitation is the BWTS treatment process or part of the BWTS treatment process, the
design and the wall thickness or grade of materials or inside coating or surface
treatment of the part of the piping where the cavitation is taking place is to be
specifically considered.
11.2 Additional requirements for tankers
11.2.2 BWTS using ozone generators (categories 7a and 7b) and de-oxygenation BWTS
using inert gas generator with treated flue gas from main or auxiliary boilers or gas
from an oil or gas-fired gas generator (categories 3b and 3c) are to be located outside
the cargo area in accordance with Section 2.3.1.1.2 of FSS Code Ch 15. This requirement
does not apply to inert gas generators for which FSS Code Ch 15/2.4.1 and Pt 5, Ch 15, 7 Inert gas systems on Tankers of 8,000 tonnes DWT and above.
11.2.3 In-line full flow electrolysis BWTS (category 4), in-line side-stream
electrolysis BWTS (category 5) and in-line injection BWTS using a chemical which is
stored on board (category 6) can be located inside the hazardous areas with due
consideration of the requirement of Pt 5, Ch 25, 9.1 General 9.1.10, but are not be located
inside the cargo pump-room unless it is demonstrated by the BWTS manufacturer that the
additional hazards that could be expected from dangerous liquids and dangerous gases
stored or evolved from the BWTS:
- do not lead to an upgrade of the hazardous area
categorisation of the cargo pump-room;
- are not reactive with the cargo vapours expected
to be present in the cargo pump-room;
- are not reactive with the fire-extinguishing
medium provided inside the cargo pump-room;
- are not impacting the performance of the
existing fire-fighting systems provided inside the cargo pump-room;
- are not introducing additional hazards inside the
cargo pump-room, such as toxicity hazards that would not have been prior addressed
by suitable counter measures.
11.2.4 In case two independent BWTS systems are not fitted, one for ballast tanks
located within the cargo area and the other one for ballast tanks located outside thw
cargo area, non-hazardous areas are not to be rendered hazardous by the use of the BWTS
or its connections with the ballast system. Specific arrangements where only one single
in-line BWTS (categories 1, 2, 3a, 3b, 4, 5, 6, 7a and 7b) could be accepted are given
in Section 13.
11.2.6 Isolation between the ballast piping serving the ballast tanks inside the cargo area and
that serving the ballast tanks outside the cargo area is to be in accordance with the
following requirements:
- Interconnection between the ballast piping serving
the ballast tanks located within the cargo area and the ballast piping serving the
ballast tanks located outside the cargo area may be accepted if an appropriate
isolation arrangement is provided.
- The means of appropriate isolation described in
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.6.(c) is necessary for the interconnection in the case of active
substance piping such as N2 gas piping, inert gas piping, neutraliser
piping, fresh water piping for filter cleaning, compressed air piping for remaining
water purge and sea water piping for adjusting the salinity, etc. regardless of the
diameter of the piping. For active substance piping and neutraliser piping (both up
to DN50) only, alternative isolation arrangements, preferably on the open deck,
offering equivalent safety and gas tightness may be considered for penetration of the
bulkhead separating the non-hazardous machinery space from a hazardous area (such as
the cargo pump-room) at as high an elevation in the machinery space as possible,
preferably just below the main deck. The arrangements are to provide suitable
protection measures in addressing the pollution hazards and safety concerns due to
the potential migration of hydrocarbons or flammable or toxic liquids or vapours from
the hazardous areas.
The means of appropriate isolation described in
Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.6.(c) need not be applied to the sampling lines described in Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.7.
- The means of appropriate isolation is to be one of
the following:
- Two non-return valves with positive means of closing in series
with a spool piece (also mentioned ‘means of dis-connection’ in Annex I); or
![](GUID-52451F65-89C3-43F3-BB88-7BDC72B1609D-low.png)
Note As an alternative to
positive means of closure, an additional valve having such means of
closure may be provided between the non-return valve and the spool
piece.
- Two non-return valves with positive means of closing in series
with a liquid seal at least 1,5 m in depth; or
![](GUID-85B7DBF6-D2D8-48B0-995E-D45AFAF04952-low.png)
Note As an alternative to
positive means of closure, an additional valve having such means of
closure may be provided between the non-return valve and the liquid seal.
Note 2. For ships operating
in cold weather conditions, freeze protection should be provided in the
water seal. A portable heating system can be accepted for this purpose.
- Automatic double block and bleed valves and a non-return valve
with positive means of closing.
![](GUID-9E33BCDC-8C90-48F2-9C33-C2D803AB97A4-low.png)
Note . As an alternative to
positive means of closure, an additional valve having such means of
closure may be provided after the non-return valve.
- The above-mentioned means of appropriate isolation
in Pt 5, Ch 25, 11.2 Additional requirements for tankers 11.2.6.(c) is to be provided on the open deck in the cargo area.
11.2.7 Sampling lines which are connected to the ballast water piping system serving the tanks
in the cargo area and provided for the purpose of the following:
- any BWTS: ballast water sampling required by the G2 Guideline of the BWM
Convention (2004); or
- BWTS categories 4, 5, 6, 7a and 7b: total residual oxidant (TRO)
analysis in closed loop system;
are not to be led into a non-hazardous enclosed space outside the cargo area. However,
the sampling lines may lead into a non-hazardous enclosed space outside the cargo area
provided the following requirements are fulfilled:
- The sampling facility (for BWTS
monitoring/control) is to be located within a gastight enclosure (hereinafter
referred to as a ‘cabinet’), and the following (i) through (iv) are to be complied
with.
- In the cabinet, a stop valve is to be
installed on each sampling line.
- Gas detection equipment is to be installed
in the cabinet and the valves specified in (i) above are to be automatically
closed upon activation of the gas detection equipment.
- Audible and visual alarm signals are to be
activated both locally and at the BWTS control station when the
concentration of explosive gases reaches a pre-set value, which is not to be
higher than 30 per cent of the lower flammable limit (LFL). Upon activation
of the alarm, all electrical power to the cabinet is to be automatically
disconnected. When the electrical equipment is of a certified safety type,
the automatic disconnection of power the supply is not required.
- The cabinet is to be vented to a safe
location (see
Pt 5, Ch 25, 1.2 Definitions)
in a non-hazardous area on the open deck and the vent is to be fitted with a
flame arrester.
- The standard internal diameter of sampling pipes
is to be the minimum necessary in order to achieve the functional requirements of
the sampling system.
- The cabinet is to be installed as close as
possible to the bulkhead facing the cargo area, and the sampling lines located
outside the cargo area are to be routed on their shortest paths.
- Stop valves are to be located in the
non-hazardous enclosed space outside the cargo area, on both the suction and
return lines close to the penetrations through the bulkhead facing the cargo area.
A warning plate stating ‘Keep valve closed when not performing measurements’ is to
be posted near the valves. Furthermore, in order to prevent backflow, a water seal
or equivalent arrangement is to be installed on the hazardous area side of the
return pipe.
- A stop valve is to be installed on the cargo
area for each sampling line (i.e. both the suction line and the return line).
- The samples which are extracted from the ballast
water piping system serving the tanks within the cargo area are not to be
discharged to a tank located outside the cargo area and are not to discharge to a
piping line supplying the spaces located outside the cargo area.
- Pipes are to be manufactured from steel or
equivalent and be protected against mechanical damage.
- The ballast water sampling/analysis unit is to
meet electrotechnical requirements of Pt 5, Ch 25, 9.1 General as
applicable.
Figure 25.11.1 Ballast water sampling/analysis
11.3 Special requirements for BWTS generating
dangerous gas or dealing with dangerous liquids (categories 2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and
8)
11.3.1 Where the operating principle of the BWTS involves the generation of a dangerous gas,
the following requirements are to be satisfied:
- Gas detection in spaces: Gas detection
equipment is to be fitted in the spaces where dangerous gas could be present, and an
audible and visual alarm is to be activated both locally and at the BWTS control
station in the event of leakage.
The gas detectors are to be located as
close as possible to the BWTS components where the dangerous gas may
accumulate.
For flammable gases and explosive atmosphere
including but not limited to hydrogen, the construction, testing and performance
of the gas detection devices is to be in accordance with IEC 60079-29-1, IEC
60079-29-2, IEC 60079-29-3 and/or IEC 60079-29-4, as applicable.
Where other hazards are considered, such as toxicity, asphyxiation, corrosive and
reactivity hazards, a recognised standard acceptable to LR is to be selected with
due consideration of the specific gases to be detected and due consideration of
the performance of the detection device with regards to the specific atmosphere
where it is used.
- Oxygen sensors: In spaces where inert gas
generator systems are fitted (BWTS categories 3b and 3c) or nitrogen generators are
fitted (BWTS categories 3a and 8), at least two oxygen sensors are to be positioned
at appropriate locations (as required by paragraph 2.2.4.5.4 of Chapter 15 of the FSS
Code as amended by IMO resolutions up to MSC.410(97)) to trigger an alarm when the
oxygen level falls below 19 per cent. The alarms are to be both audible and visual
and are to be activated inside the space, at the entry into the space and inside the
BWTS control station.
For BWTS categories 7a and 7b, at least two
oxygen sensors are to be positioned at appropriate locations in the following
spaces. Spaces where ozone generators are fitted; spaces where ozone destructors
are fitted; or spaces where ozone piping is routed to trigger an alarm when the
oxygen level rises above 23 per cent. The alarms are to be both audible and visual
and are to be activated inside the space, at the entry into the space, and inside
the BWTS control station.
Automatic shutdown of the BWTS is to
be arranged when the oxygen level rises above 25 per cent. Audible and visual
alarms independent from those specified in the preceding paragraph are to be
activated prior to this shutdown.
- Ozone sensors: For BWTS categories 7a and
7b, at least one ozone sensor is to be provided in the vicinity of the discharge
outlet to the open deck from the ozone destructors addressed in Pt 5, Ch 25, 1.2 Definitions 1.2.5 to trigger an alarm
when the ozone concentration level rises above 0,1 ppm. The alarm is to be both
audible and visual and is to be activated in the BWTS control room. In addition, at
least two ozone sensors are to be positioned at appropriate locations in the
following spaces: spaces where ozone generators are fitted; spaces where ozone
destructors are fitted; or spaces where ozone piping is routed.
These
sensors are to trigger an alarm when the ozone concentration level rises above 0,1
ppm. The alarms are to be both audible and visual and shall be activated at the
following locations: inside the space; at the entry into the space; and inside the
BWTS control room.
Automatic shutdown of the BWTS is to be
arranged when the ozone concentration measured from any one or both of the two
sensors inside the space rises above 0,2 ppm.
- Gas detection in double walled pipes or pipe
ducts: Inside double walled spaces or pipe ducts required by Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(a).(i),
sensors are to be provided for the detection of hydrogen leakages (BWTS categories 4,
5 and 6 when relevant) or oxygen leakages (BWTS categories 7a and 7b) or ozone
leakages (BWTS categories 7a and 7b). The sensors are to activate an alarm at the
high concentration level settings and automatic shutdown of the BWTS at the high-high
concentration level settings described in Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(a) to Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(c).
Note As an
alternative to the sensor for the gas detection, monitored under-pressurisation
inside the double walled spaces or pipe ducts may be provided with an alarm and
automatic shutdown of the BWTS in case of loss of the under-pressurisation. This
may be achieved by monitoring the pressure inside the double walled spaces or pipe
ducts.
- Hydrogen: For in-line full flow electrolysis
BWTS (category 4), in-line side-stream electrolysis BWTS (category 5) and in-line
injection BWTS using a chemical which is stored on board (category 6): the hydrogen
de-gas arrangement (when provided) is to be provided with redundant ventilation fans
and redundant monitoring of the ventilation system.
In addition, the
ventilation fan is to be certified explosion proof and have a spark arrestor to
prevent ignition sources entering the ventilation system where hydrogen may be
present in explosive concentrations.
Audible and visual alarms
and automatic shutdown of the BWTS are to be arranged for respectively high and
high-high levels of hydrogen concentration. The open end of the hydrogen
by-product enriched gas relieving device is to be led to a safe location*(3)
(see
Pt 5, Ch 25, 1.2 Definitions) on the open
deck.
- Vents: The open ends of the inert gas or
nitrogen gas enriched air (BWTS categories 3a, 3b, 3c and 8) or oxygen-enriched air
vent pipes (BWTS categories 3a, 7a, 7b and 8) are to be led to a safe location*(1)
and (2) (see
Pt 5, Ch 25, 1.2 Definitions) on the open deck.
11.3.2 Where the piping is conveying active substances, by-products or
neutralisers that contain dangerous gas or dangerous liquids as defined respectively in
Pt 5, Ch 25, 1.2 Definitions, the following requirements
are to be satisfied:
Note This
requirement is applicable to the injection lines conveying the dangerous gas or
dangerous liquids but not applicable to the ballast waterlines where the dangerous
gas or dangerous liquids are diluted.
- The piping is to be of either Class I without
special safeguard or Class II with special safeguard as listed below, irrespective
of design pressure and temperatures (see
Pt 5, Ch 12, 1.6 Classes of piping systems and components). The selected materials, the testing of the material,
the welding, the non-destructive tests of the welding, the type of connections,
the hydrostatic tests and the pressure tests after assembly on board are to be as
required in Pt 5, Ch 12 Piping Design Requirements. Mechanical joints, where allowed, are to be
selected in accordance with Table 12.2.9 Application of mechanical joints
depending on class of piping.
- For piping Class II with special
safeguards conveying a dangerous gas such as hydrogen (H2),
oxygen (O2) or ozone (O3), the special safeguards are
to be either double walled pipes or pipe ducts.
- For piping Class II with special
safeguards conveying dangerous liquids, other special safeguards could be
considered such as shielding, screening, etc.
- Plastic pipes may be accepted after due
assessment of the dangerous gas or dangerous liquids conveyed inside. When
plastic pipes are accepted, the requirements of Pt 5, Ch 12 Piping Design Requirements apply.
- The length of pipe and the number of connections
are to be minimised.
- Inside double walled space or pipe ducts
required by Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(a).(i) is
to be equipped with mechanical exhaust ventilation leading to a safe location*(3)
and (4) (see
Pt 5, Ch 25, 1.2 Definitions) on the
open deck.
- The routing of the piping system is to be kept
away from any sources of heating or ignition and any other sources that could
react hazardously with the dangerous gas or liquid conveyed inside. The pipes are
to be suitably supported and protected from mechanical damage.
- Pipes carrying acids are to be arranged so as to
avoid any projection onto crew in case of a leakage.
- Hydrogen (H2) by-product enriched air
vent pipes (BWTS categories 4, 5 and 6) or oxygen (O2) enriched air
vent pipes (BWTS categories 3a, 7a, 7b and 8) or ozone (O3) piping
(BWTS categories 7a and 7b) are not to be routed through accommodation spaces,
services spaces and control stations.
- Oxygen (O2) enriched air vent pipes
(BWTS categories 3a, 7a, 7b and 8) are not to be routed through hazardous areas
unless they are arranged inside double walled pipes or pipe ducts required by
Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.2.(a).(i) and provided with suitable gas detection as described in Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(d) and mechanical exhaust ventilation as described in Pt 5, Ch 25, 11.3 Special requirements for BWTS generating dangerous gas or dealing with dangerous liquids (categories
2, 3a, 3b, 3c, 4, 5, 6, 7a, 7b and 8) 11.3.1.(c).
- The routing of hydrogen (H2)
by-product enriched air vent pipes (BWTS categories 4, 5 and 6) or oxygen
(O2) enriched air vent pipes (BWTS categories 3a, 7a, 7b and 8) is
to be as short and as straight as possible. When required, horizontal portions are
to be arranged with a minimum slope in accordance with the manufacturer’s
recommendation.
11.3.3 For BWTS using chemical substances or dangerous gases which are stored on board for
either:
- storage or preparation of the active substances (BWTS categories 2 and
6);
- storage or preparation of the neutralisers (BWTS categories 4, 5, 6, 7a
and 7b); or
- recycling the wastes produced by the BWTS (BWTS category 2);
handling procedures are to be in accordance with the Material Safety
Data Sheet and BWM.2/Circ.20 Guidance to ensure safe handling and storage of
chemicals and preparations used to treat ballast water and the development of
safety procedures for risks to the ship and crew resulting from the treatment
process, and the following measures are to be taken as appropriate:
- The materials or inside coating used for
the chemical storage tanks, piping and fittings are to be resistant to such
chemical substances.
- Chemical substances (even if they are not
defined as dangerous according to Pt 5, Ch 25, 1.2 Definitions)
and gas storage tanks are to be designed, constructed, tested, inspected,
certified and maintained in accordance with:
- for independent tanks permanently fixed on board
containing dangerous liquids (e.g. sulphuric acid,
H2SO4) or dangerous gas (e.g. oxygen,
O2) the LR Rules for pressure vessels of Class I or II
as applicable, see
Pt 5, Ch 11 Other Pressure Vessels;
- for independent tanks permanently fixed on board not
containing dangerous liquids (e.g. sodium sulphite, sodium biosulphite
or sodium thiosulfphate neutralisers) and not containing dangerous gas
(e.g. nitrogen, N2): the Classification Rules or other
industry standard recognised by the Classification Society;
- for portable tanks: the IMDG Code or other industry
standard recognised by the Classification Society;
- Atmospheric storage tanks will be considered for
non-hazardous and non-toxic chemicals not requiring inert gas
blanketing and with negligible vapour pressure.
- When the chemical substances are stored
inside integral tanks, the ship's shell plating is not to form any boundary
of the tank.
- Dangerous liquids and dangerous gas
storage tank air pipes are to be led to a safe location*(1) and (2)
(see
Pt 5, Ch 25, 1.2 Definitions) on
the open deck.
- An operations manual containing chemical
injection procedures, alarm systems, measures in case of emergency, etc. is
to be provided and kept on board.
- Dangerous liquid storage tanks and their
associated components, such as pumps and filters, are to be provided with
spill trays or a secondary containment system of sufficient volume to
contain potential leakages from tank openings, gauge glasses, pumps, filters
and piping fittings.
Further to the safety and/or pollution assessment of the concerned chemical
substances, consideration is to be provided for segregation of the drains from such
spill trays (or secondary containment system) or piping systems from the engine room
bilge system or from the cargo pump-room bilge system, as applicable. When necessary,
arrangement is to be provided within the spill trays (or within the secondary
containment system) for the detection of dangerous liquid or dangerous gas as defined
respectively in Pt 5, Ch 25, 1.2 Definitions.
Note The IMO reports issued during the
basic and final approval procedures of the BWTS that make use of active substances (G9
Guideline) and/or the Marine Safety Data Sheet (MSDS) could be used for this
assessment.
|