Section
5 Supply and distribution
5.1 Systems of supply and distribution
5.1.1 The following
systems of generation and distribution are acceptable:
-
d.c., two-wire;
-
a.c., single-phase,
two-wire;
-
a.c., three-phase;
three-wire;
four-wire with neutral solidly earthed but without hull return.
5.1.2 System voltages for both alternating current and direct current in general
are not to exceed:
- 35000 V for power distribution;
- 15 000 V for generation and propulsion;
- 500 V for power, cooking and heating equipment permanently connected to fixed
wiring;
- 250 V for lighting, heaters in cabins and public rooms, and other
applications not mentioned above;
- Voltages exceeding these will be the subject of special consideration.
5.1.3 The arrangement
of the main system of supply is to be such that a fire or other casualty
in any space containing the main source of electrical power, associated
converting equipment, if any, the main switchboard or the main lighting
switchboard will not render inoperable any emergency service, other
than those located within the space where the fire or casualty has
occurred.
5.1.4 The main
switchboard is to be so placed relative to the main source of power
that, as far as is practicable, the integrity of the main system of
supply will be affected only by a fire or other casualty in one space.
5.1.5 The arrangement
of the emergency system of supply is to be such that a fire or other
casualty in spaces containing the emergency source of electrical power,
associated converting equipment, if any, the emergency switchboard
and the emergency lighting switchboard, will not cause loss of services
required to maintain the propulsion and safety of the craft.
5.1.6 Distribution
systems required in an emergency are to be so arranged that a fire
in any main vertical zone will not interfere with the emergency distribution
in any other such zone.
5.1.7 Feeders
from the main and the emergency sources of electrical power are to
be separated both vertically and horizontally as widely as is practicable.
5.1.8 For Passenger
(A) or Passenger (B) Craft or cargo craft of 500 tons gross tonnage
and over, and in any case where the total installed electrical power
of the main generating sets is in excess of 3 MW or is supplied at
high voltage, arrangements are to be made so that it is possible to
split the switchboard, by a multipole linked circuit-breaker, disconnector
or switch-disconnector, into at least two independent sections, each
supplied by at least one generator.
5.1.9 Where Pt 16, Ch 2, 5.1 Systems of supply and distribution 5.1.8 is applicable and the essential
services which are duplicated are supplied from a section-board, arrangements
are to be made so that it is possible to split the section-board into
at least two independent sections each supplied by an independent
section of the main switchboard either directly or through a transformer.
5.1.10 For
Passenger (B) high speed craft, each part of the main busbars with
its associated generators is to be arranged in separate compartments.
5.2 Essential services
5.2.1 Essential
services that are required to be duplicated are to be served by individual
circuits, separated in their switchboard or section board and throughout
their length as widely as is practicable without the use of common
feeders, protective devices, control circuits or controlgear assemblies,
so that any single fault will not cause the loss of both services.
5.2.2 Where Pt 16, Ch 2, 5.2 Essential services 5.2.1 is applicable the main busbars
of the switchboard, or section boards, are to be capable of being
split, by removable links or other means, into at least two independent
sections, each supplied by at least one generator, either directly
or through a converter. The essential services are to be equally
divided, as far as is practicable, between the independent sections.
5.2.3 Where Pt 16, Ch 2, 5.1 Systems of supply and distribution 5.1.8 is applicable provision is to
be made to transfer to a temporary circuit those essential services
which are not required to be, and have not been, duplicated in the
event of loss of their normal section of switchboard or section board.
5.2.4 Where
the loss of the electrical supply to a particular essential service
which is not duplicated would cause serious risk to the craft, it
is to be fed by two independent supplies complying with Pt 16, Ch 2, 5.2 Essential services 5.2.1. Such circuits are to be provided
with short circuit protection and an overload and phase-failure alarm.
Failure of either supply is not to cause risk to the craft during
switching to the alternative supply.
5.3 Isolation and switching
5.3.1 The incoming
and outgoing circuits from every switchboard or section board are
to be provided with a means of isolation and switching to permit each
circuit to be switched off:
-
on load;
-
for mechanical maintenance;
-
in an emergency
to prevent or remove danger.
Precautions are to be taken to minimise the risk of inadvertent
or accidental switching.
5.3.2 Isolation
and switching is to be by means of a circuit breaker or switch arranged
to open and close simultaneously all insulated poles. Where a switch
is used as the means of isolation and switching, it is to be capable
of:
-
switching off the
circuit on load;
-
withstanding, without
damage, the overcurrents which may arise during overloads and short
circuit.
In addition, these requirements do not preclude the provision
of single pole control switches in final sub-circuits, for example
light switches. For circuit-breakers, see
Pt 16, Ch 2, 6.5 Circuit-breakers and Pt 16, Ch 2, 7.3 Circuit-breakers.
5.3.3 Provision
is to be made, in accordance with one of the following, to prevent
any circuit being inadvertently energised:
-
the circuit breaker
or switch can be withdrawn, or locked in the open position;
-
the operating handle
of the circuit breaker or switch can be removed;
-
the circuit fuses,
where fitted, can be readily removed and retained by authorised personnel.
5.3.4 All lighting
and power circuits installed in unattended spaces are to be controlled
by multipole linked switches situated outside such spaces. Provision
is to be made for the complete isolation of these circuits and locking
the means of control in the off position.
5.3.5 Where
arrangements are in place for automatic changeover between two or
more supplies of electrical power in the event of failure of one supply,
the arrangements are to be such that a fault in one feeder does not
result in the loss of all supplies to the automatic changeover switch.
5.3.6 Where
a section board, distribution board or item of equipment can be supplied
by more than one circuit, a switching device is to be provided to
permit each incoming circuit to be isolated and the supply transferred
to the alternative circuit.
5.3.7 The switching
device required by Pt 16, Ch 2, 5.3 Isolation and switching 5.3.6 is
to be situated within or adjacent to the section board, distribution
board or item of equipment. Where necessary, interlocking arrangements
are to be provided to prevent circuits being inadvertently energised.
5.3.8 A notice is to be
fixed to any section board, distribution board or item of equipment
to which Pt 16, Ch 2, 5.3 Isolation and switching 5.3.4 applies warning
personnel before gaining access to live parts of the need to open
the appropriate circuit breakers or switches, unless an interlocking
arrangement is provided so that all circuits concerned are isolated
before access is gained.
5.3.9 High voltage switchgear and controlgear assemblies that use liquids or gasses other than
ambient air as an insulating medium are to be installed in spaces that are adequately
protected according to the following requirements:
- The space is to be provided with ventilation to ensure that gasses cannot accumulate
unnoticed.
- Leakages of liquid are to be properly collected and contained.
- An alarm is to be initiated at a manned control station to indicate when the
insulating medium has reduced to an abnormally low level. Interlocks are to be
provided to ensure that the switchgear or controlgear cannot be closed when this
alarm is active. The interlocks are to ensure that services essential for the
propulsion and safety of the ship are not disconnected in the event of this alarm
being activated.
5.4 Insulated distribution systems
5.4.1 A device(s)
is to be installed for every insulated distribution system, whether
primary or secondary, for power, heating and lighting circuits, to
continuously monitor the insulation level to earth and to operate
an alarm in the engine control room, or equivalent attended position,
in the event of an abnormally low level of insulation resistance.
5.4.2 Where
any insulated lower voltage system is supplied through transformers
from a high voltage system, adequate precautions are to be taken to
prevent the low voltage system being charged by capacitive leakage
from the high voltage system.
5.4.3 Where
filters are fitted, for example to reduce EMC susceptibility, these
are not to cause distribution systems to be unintentionally connected
to earth.
5.5 Earthed distribution systems
5.5.1 No fuse,
non-linked switch or non-linked circuit-breaker is to be inserted
in an earthed conductor. Any switch or circuit-breaker fitted is to
operate simultaneously in the earthed conductor and the insulated
conductors. These requirements do not preclude the provision (for
test purposes) of an isolating link to be used only when the other
conductors are isolated.
5.5.2 For high
speed craft, earthed electrical distribution systems are not to be
used, with the exception of earthed intrinsically safe circuits, in
areas where an explosive gas atmosphere may arise from the presence
of fuel with a flash point below 43ºC, see
Pt 15, Ch 3, 3.1 Flash point.
5.5.3 For high
voltage systems, where the earthed neutral system of generation and
primary distribution is used, earthing is to be through an impedance
in order to limit the total earth fault current to a magnitude which
does not exceed that of the three phase short circuit current for
which the generators are designed.
5.5.4 Generator
neutrals may be connected in common, provided that the third harmonic
content of the voltage waveform of each generator does not exceed
five per cent.
5.5.5 Where
a switchboard is split into sections operated independently or where
there are separate switchboards, neutral earthing is to be provided
for each section or for each switchboard. Means are to be provided
to ensure that the earth connection is not removed when generators
are isolated.
5.5.6 A means
of isolation is to be fitted in the earthing connection of each generator
so that generators can be completely isolated for maintenance.
5.5.7 All earthing
impedances are to be connected to a common earth connection/bar. The
connections to the common earth connection/bar are to be so arranged
that any circulating currents in the earth connections do not interfere
with radio, radar, communication and control equipment circuits.
5.6 Diversity factor
5.6.1 Circuits
supplying two or more final sub-circuits are to be rated in accordance
with the total connected load subject, where justified, to the application
of a diversity factor. Where spare ways are provided on a section
or distribution board, an allowance for future increase of load is
to be added to the total connection load before application of any
diversity factor.
5.6.2 A diversity
factor may be applied to the calculation for size of cable and rating
of switchgear and fusegear, taking into account the duty cycle of
the connected loads and the frequency and duration of any motor starting
loads.
5.6.3 For winches
and crane motors the diversity factor is to be calculated and submitted
when required.
5.7 Lighting circuits
5.7.1 Lighting
circuits are to be supplied by final sub-circuits separate from those
for heating and power. This does not preclude the supply from a lighting
circuit supplying a single fixed appliance, such as a cabin fan, a
dry shaver, a wardrobe or anti-condensation heater, taking a maximum
current of 2 A. (This does not apply to cabin and wardrobe heaters).
5.7.2 Lighting
for machinery spaces, control stations, normal working spaces, large
galleys, corridors, stairways leading to boat decks and in public
rooms is to be supplied from at least two final sub-circuits in such
a way that failure of any one of the circuits does not leave the space
in darkness. One of these circuits may be the emergency circuit, provided
it is normally energised.
5.7.3 Lighting
for enclosed hazardous spaces is to be supplied from at least two
final sub-circuits to permit light from one circuit to be retained
while maintenance is carried out on the other.
5.8 Motor circuits
5.9 Motor control
5.9.1 Every
electric motor is to be provided with efficient means for starting
and stopping so placed as to be easily operated by the person controlling
the motor. Every motor above 0,5 kW is to be provided with control
apparatus as given in Pt 16, Ch 2, 5.9 Motor control 5.9.2.
5.9.2 Means
to prevent undesired restarting after a stoppage due to low volts
or complete loss of volts are to be provided. This does not apply
to motors where a dangerous condition might result from the failure
to restart automatically, e.g. steering gear motor.
5.9.3 Means
for automatic disconnection of the supply in the event of excess current
due to mechanical overloading of the motor are to be provided, see
also
Pt 16, Ch 2, 6.9 Load management.
5.9.4 Motor
controlgear is to be suitable for the starting current and for the
full load rated current of the motor.
5.10 Harmonic distortion measurement
5.10.1 The requirements of Pt 16, Ch 2, 5.10 Harmonic distortion measurement apply to
electrical distribution systems that include harmonic filters. This requirement
applies both to high voltage and low voltage busbars. See also Pt 16, Ch 2, 6.13
Harmonic filters. Harmonic filters associated with frequency drives for
individual applications (i.e. pump motors) are excluded from the following
requirements.
5.10.2 Means are to be provided to continuously monitor the levels of harmonic distortion
experienced on the main busbars and to operate an alarm in the engine control room,
or equivalent attended position, in the event that the harmonic distortion exceeds
the acceptable limits, see also Pt 6, Ch 1, 4.2 Alarm system for
machinery.
5.10.3 Where the engine room is provided with automation systems to continuously monitor the
levels of harmonic distortion experienced on the main busbars, this reading is to be
logged electronically; otherwise it is to be measured annually and after any
modification to the craft electrical distribution system or associated consumers and
recorded in the engine log book for future inspection by the Surveyor.
5.11 Harmonic filtering
5.11.1 The requirements in this Section apply to systems provided with harmonic
filters. They apply in particular to, but are not limited to, electrical propulsion
systems and are in addition to the requirements for harmonic filters in Pt 16, Ch 2, 6.13 Harmonic filters.
5.11.3 The service life of the harmonic filter is to be declared, and details are to be
included in the harmonic calculation report.
5.11.4 The temperature rating of the harmonic filter is to allow for the increased heating
effect of the harmonic distortion.
5.11.6 The modes of operation of the electrical distribution system for which harmonic
distortion levels at the main switchboard busbars are maintained within the
acceptable limits during normal operation are to be defined by the system
integrator.
5.11.7 Harmonic distortion calculations are to include levels of harmonic
distortion expected in normal operation and in the event of a failure of a harmonic
filter or the failure of any combination of harmonic filters. See also
Pt 16, Ch 2, 21.2 Trials.
|