Section
9 Rotating machines
9.1 General requirements
9.1.1 In addition to the requirements of this Section, rotating machines are to comply with
the relevant requirements of the following standards, amended where necessary for
ambient temperature, see
Pt 16, Ch 2, 1.9 Ambient reference and operating conditions:
- IEC 60034 Rotating electrical machines (all parts);
and
- IEC 60092 Electrical installations in ships (all parts);
or
- an alternative International or National Standard acceptable to
LR.
9.1.2 The insulation systems of electrical rotating machines used for essential services are
to be tested following the principles detailed in IEC 60505, Evaluation and
qualification of electrical insulations systems, or an equivalent National
Standard acceptable to LR.
9.1.3 For all
the rotating machines a manufacturer's test certificate is to be provided, see also
Pt 16, Ch 2, 1.4 Surveys.
9.1.4 All machines of 100 kW and over, intended for essential services, are to be
surveyed by the Surveyor during manufacture and test, see also
Pt 16, Ch 2, 1.4 Surveys 1.4.5.
9.1.6 Where
welding is applied to shafts of machines for securing arms or spiders,
stress relieving is to be carried out after welding. The finalized
assembly is to be visually examined by the Surveyors, crack detection
carried out by an appropriate method and the finished welds found
sound and free from cracks.
9.1.7 The rotating
parts of machines are to be so balanced that when running at any speed
in the normal working range the vibration does not exceed the levels
of IEC 60034-14: Rotating electrical machines – Part 14:
Mechanical vibration of certain machines with shaft heights 56 mm
and higher – Measurement, evaluation and limits of vibration
severity.
9.1.8 The lubrication
arrangement for bearings are to be effective under all operating conditions
including the maximum craft inclinations defined by Pt 16, Ch 2, 1.10 Inclination of craft and there are to be effective
means provided to ensure that lubricant does not reach the machine
windings or other conductors and insulators.
9.1.9 Means
are to be taken to prevent the ill effects of the flow of currents
circulating between the shaft and machine bearings or bearings of
connected machinery.
9.1.10 Alternating
current machines are to be constructed such that, under any operating
conditions, they are capable of withstanding the effects of a sudden
short-circuit at their terminals without damage.
9.1.12 The entity responsible for assembling the alternating current generating set is to
install a rating plate marked with at least the following information:
- the generating set manufacturer’s name or mark;
- the set serial number;
- the set date of manufacture (month/year);
- the rated power (both in kW and kVA) with one of the power rating prefixes COP, PRP
(or, only for emergency generating sets, LTP) as defined in ISO 8528-1
Reciprocating internal combustion engine driven alternating current generating
sets;
- the rated power factor;
- the set rated frequency (Hz);
- the set rated voltage (V);
- the set rated current (A); and
- the mass (kg).
9.2 Rating
9.2.1 Generators,
including their excitation systems, and continuously rated motors
are to be suitable for continuous duty at their full rated output
at maximum cooling air or water temperature for an unlimited period,
without the limits of temperature rise in Pt 16, Ch 2, 9.3 Temperature rise being exceeded. Generators are to be capable of an overload
power of not less than 10 per cent at their rated power factor for
a period of 15 minutes without injurious heating. Other machines are
to be rated in accordance with the duty which they have to perform
and, when tested under rated load conditions, the temperature rise
is not to exceed the values in Pt 16, Ch 2, 9.3 Temperature rise.
9.2.2 When a
rotating machine is connected to a supply system with harmonic distortion
the rating of the machine is to allow for the increased heating effect
of the harmonic loading.
9.2.3 The design
and construction of smoke extraction fan motors are to be suitable
for the ambient temperature and operating time required. Type test
reports to verify the performance of the electric motor are to be
submitted for consideration.
9.3 Temperature rise
9.3.1 The limits
of temperature rise specified in Table 2.9.1 Limits of temperature rise of
machines cooled by air, are based on the cooling air temperature and cooling
water temperature given in Pt 16, Ch 2, 1.9 Ambient reference and operating conditions.
Table 2.9.1 Limits of temperature rise of
machines cooled by air
Limits of temperature rise of machines cooled by air, °C
|
Part of machine
|
Method of
temperature measurement
|
Insulation class
|
A
|
E
|
B
|
F
|
H
|
1.
|
(a) a.c. windings of machines having output of 5000 kVa or
more
|
ETD
|
55
|
-
|
75
|
95
|
115
|
R
|
50
|
-
|
70
|
90
|
110
|
|
(b) a.c. windings of machines having output of less than 5000
kVa
|
ETD
|
55
|
-
|
80
|
100
|
115
|
R
|
50
|
65
|
70
|
95
|
110
|
2.
|
Windings of armatures having
commutators
|
R
|
50
|
65
|
70
|
95
|
115
|
|
|
T
|
40
|
55
|
60
|
75
|
95
|
3.
|
Field windings of a.c.
and d.c. machines having d.c. excitation other than those in item 4
|
R
|
50
|
65
|
70
|
95
|
115
|
|
T
|
40
|
55
|
60
|
75
|
95
|
4.
|
(a) Field windings of synchronous machines with cylindrical
rotors having d.c. excitation
|
R
|
-
|
-
|
80
|
100
|
125
|
|
(b) Stationery field windings of d.c. machines having more
than one layer
|
R
|
50
|
65
|
70
|
95
|
115
|
T
|
40
|
55
|
60
|
75
|
95
|
|
(c) Low resistance field windings of a.c. and d.c. machine
and compensating windings of d.c. machines having more than one layer
|
R, T
|
50
|
65
|
70
|
90
|
115
|
|
(d) Single-layer windings of a.c. and d.c. machines with
exposed bare or varnished metal surfaces and single-layer compensating
windings of d.c. machines
|
R, T
|
55
|
70
|
80
|
100
|
125
|
5.
|
Permanently short-circuited insulated
windings
|
T
|
50
|
65
|
70
|
90
|
115
|
6.
|
Permanently short-circuited
uninsulated windings
|
T
|
The temperature rise of these parts shall in no case reach such a
value that these is a risk to any insulation or other materials on adjacent
parts or to the item itself
|
7.
|
Magnetic cores and other parts not in
contact with windings
|
T
|
8.
|
Magnetic cores and other parts in
contact with windings
|
T
|
50
|
65
|
70
|
90
|
110
|
9.
|
Commutators and slip-rings open and
enclosed
|
T
|
50
|
60
|
70
|
80
|
90
|
Note
1. Where water cooled heat exchangers are
used in the machine cooling circuit the temperature rises are to be
measured with respect to the temperature of the cooling water at the
inlet to the heat exchanger and the temperature rises given in Table
2.8.1 shall be increased by 10oC provided the inlet water
temperature does not exceed the values given in Pt 16, Ch 2, 1.9 Ambient reference and operating conditions.
Note
2. T = thermometer method
R = resistance method
ETD = embedded temperature detector
Note
3. Temperature rise measurements are to
use the resistance method whenever practicable.
Note
4. The ETD method may only be used when
the ETDs are located between coil sides in the slot.
|
9.4 Generator control
9.4.1 Each alternating
current generator, unless of the self-regulating type, is to be provided
with automatic means of voltage regulation; voltage build-up is not
to require an external source of power. Provision is to be made to
safeguard the distribution system should there be a failure of the
voltage regulating system resulting in a high voltage.
9.4.2 The voltage
regulation of any alternating current generator with its regulating
equipment is to be such that at all loads, from zero to full load
at rated power factor, the rated voltage is maintained within ±2,5
per cent under steady conditions. There is to be provision at the
voltage regulator to adjust the generator no load voltage.
9.4.3 Generators,
and their excitation systems, when operating at rated speed and voltage
on no-load are to be capable of absorbing the suddenly switched, balanced,
current demand of the largest motor or load at a power factor not
greater than 0,4 with a transient voltage dip which does not exceed
15 per cent of rated voltage. The voltage is to recover to rated voltage
within a time not exceeding 1,5 seconds.
9.4.4 The transient
voltage rise at the terminals of a generator is not to exceed 20 per
cent of rated voltage when rated kVA at a power factor not greater
than 0,8 is thrown off.
9.4.5 Generators
and their voltage regulation systems are to be capable of maintaining,
without damage, under steady state short circuit conditions a current
of at least three times the full load rated current for a duration
of at least two seconds or where precise data is available for the
duration of any time delay which may be provided by a tripping device
for discrimination purposes.
9.4.6 Generators
required to run in parallel are to be stable from no load (kW) up
to the total combined full load (kW) of the group, and load sharing
is to be such that the load on any generator does not normally differ
from its proportionate share of the total load by more than 15 per
cent of the rated output (kW) of the largest machine or 25 per cent
of the rated output (kW) of the individual machine, whichever is less.
9.4.7 When generators
are operated in parallel, the kVA loads of the individual generating
sets are not to differ from the proportionate share of the total kVA
load by more than 5 per cent of the rated kVA output of the largest
machines.
9.5 Overloads
9.5.1 Machines are to withstand on test, without injury, the following occasional
overloads.
-
Generators. An excess current of 50 per cent for 30 seconds after attaining
the temperature rise corresponding to rated current, the terminal voltage being
maintained as near the rated value as possible. The forgoing does not apply to the
overload torque capacity of the prime mover.
-
Motors.
At rated speed or, in the case of a range of speeds, at the highest
and lowest speeds, under gradual increase of torque, the appropriate
excess torque given below. Synchronous motors and synchronous induction
motors are required to withstand the excess torque without falling
out of synchronism and without adjustment of the excitation circuit
preset at the value corresponding to rated load:
d.c. motors
|
50 per cent for 15
seconds;
|
polyphase a.c. synchronous
motors
|
50 per cent for 15
seconds;
|
polyphase a.c. synchronous
induction motors
|
35 per cent for 15
seconds;
|
polyphase a.c. induction
motors
|
60 per cent for 15
seconds.
|
9.6 Machine enclosure
9.6.1 Where
water cooled heat exchangers are used in the machine cooling circuit
there is to be provision for the detection of water leakage and the
system is to be arranged so as to prevent the entry of water into
the machine.
9.6.2 An alarm
is to be provided to indicate high cooling water temperature.
9.7 Direct current machines
9.7.1 The final
running position of brushgear is to be clearly and permanently marked.
9.7.2 Direct
current machines are to work with fixed brush setting from no load
to the momentary overload specified without injurious sparking.
9.8 Survey and testing
9.8.1 On machines
for essential services tests are to be carried out and a certificate
furnished by the manufacturer. The tests are to include temperature
rise, momentary overload, high voltage, and commutation. The insulation
resistance and the temperature at which it was measured are to be
recorded.
9.8.2 In the
case of duplicate machines, type tests of temperature rise, excess
current and torque and commutation taken on a machine identical in
rating and in all other essential details may be accepted in conjunction
with abbreviated tests on each machine. Type tests for propulsion
machines will be specially considered. For the abbreviated tests,
each machine is to be run and is to be found electrically and mechanically
sound and is to have a high voltage test and insulation resistance
recorded.
9.8.3 A high
voltage test, in accordance with Pt 16, Ch 2, 21 Testing and trials, is to be applied to new machines, preferably at the conclusion
of the temperature rise test. Where both ends of each phase are brought
out to accessible separate terminals each phase is to be tested separately.
9.8.4 An impulse
test is to be carried out on the coils of high voltage machines in
accordance with IEC 60034-15: Rotating electrical machines –
Part 15: Impulse voltage withstand levels of form-wound stator coils
for rotating a.c. machines, in order to demonstrate a satisfactory
withstand level of the inter-turn insulation to voltage surges. The
test is to be carried out on all coils after they have been inserted
in the slots and after wedging and bracing. Each coil shall be subjected
to at least five impulses of injected voltage, the peak value of the
injected voltage being given by the formula:
where
V
|
= |
rated
line voltage r.m.s. |
Alternative proposals to demonstrate the withstand level of
inter-turn insulation will be considered.
|