Section
2 Scantlings of erections other than forecastles
2.1 Thickness of bulkhead and side plating
2.1.1 The
thickness, t, of plating of the fronts, sides and aft
ends of all erections, other than the sides of superstructures where
these are an extension of the side shell, is to be not less than:
t
|
= |
|
but in no case is the thickness to be less than:
-
for the lowest
tier:
t
|
= |
|
-
for the upper
tiers:
t
|
= |
but not less than 5,0 mm
|
2.2 Stiffeners and their connections
2.2.1 The
modulus of stiffeners, Z, on front, side and end bulkheads
of all erections, other than sides of superstructures, is to be not
less than:
Z
|
= |
0,0035hs
s
2
k cm3
|
2.3 Deck plating
2.3.1 The requirements of Pt 3, Ch 8, 2.3 Deck plating need not apply to effective
superstructure decks of passenger ships and ferries where direct calculations have been
carried out in accordance with the SDA procedure relevant to the ship type.
2.3.3 When
decks are fitted with approved sheathing, the thicknesses derived
from Table 8.2.2 Thickness of deck plating may be reduced
by 10 per cent for a 50 mm sheathing thickness, or 5 per cent for
25,5 mm, with intermediate values in proportion. The steel deck is
to be coated with a suitable material in order to prevent corrosive
action, and the sheathing or composition is to be effectively secured
to the deck, see also
Pt 6, Ch 4 Fire Protection, Detection and Extinction Requirements. Inside deckhouses the thickness may be reduced by a further
10 per cent.
Table 8.2.1 Stiffener end connections
Position
|
Attachment at top and
bottom
|
1.
|
Front stiffeners of
lower tiers and of upper tiers when L is 160 m or greater
|
See
Pt 3, Ch 10 Welding and Structural Details
|
2.
|
Front stiffeners of
upper tiers when L is less than 160 m
|
May be
unattached
|
3.
|
Side stiffeners of
lower tiers where two or more tiers are fitted
|
Bracketed, unless
stiffener modulus is increased by 20 per cent and ends are welded to the
deck all round
|
4.
|
Side stiffeners if
only one tier is fitted, and aft end stiffeners of after deckhouses on deck
to which D is measured
|
See
Pt 3, Ch 10 Welding and Structural Details
|
5.
|
Side stiffeners of
upper tiers when L is 160 m or greater
|
See
Pt 3, Ch 10 Welding and Structural Details
|
6.
|
Side stiffeners of
upper tiers when L is less than 160 m
|
May be
unattached
|
7.
|
Aft end stiffeners
except as covered by item 4
|
May be
unattached
|
8.
|
Exposed machinery and
pump-room casings -Front stiffeners on amidship casings and all stiffeners
on aft end casings which are situated on the deck to which D is
measured
|
Bracketed
|
9.
|
All other stiffeners
on exposed machinery and pump-room casings
|
6,5 cm2 of
weld
|
Table 8.2.2 Thickness of deck plating
|
Thickness of deck plating, in mm
|
Position
|
L ≤ 100 m
|
L > 100 m
|
Top of first tier
erection
|
|
|
|
Top of second tier
erection
|
|
|
|
Top of third tier and
above
|
|
but not
less than 5,0 mm
|
|
2.4 Deck longitudinals and beams
2.4.1 The requirements of Pt 3, Ch 8, 2.4 Deck longitudinals and beams need not apply to
effective superstructure decks of passenger ships and ferries where direct calculations
have been carried out in accordance with the SDA procedure relevant to the ship
type.
2.4.3 Transverse
deck beams in deckhouses and deck longitudinals other than as in Pt 3, Ch 8, 2.7 Erections contributing to hull strength are to have a section modulus, Z, not less than:
Z
|
= |
0,0048 h
2
s
e
2
k cm3,
but in no case less than:
|
and the value of h
2, the
load head, is to be taken as not less than:
|
on first tier decks
|
0,9 m
|
|
on second tier decks
|
0,6 m
|
|
on third tier decks and above
|
0,45 m.
|
2.5 Deck girders and transverses
2.6 Strengthening at ends and sides of erections
2.6.1 Web
frames or partial bulkheads are to be fitted within poops and bridges
that have large deckhouses or other erections above.
2.6.2 Web
frames or equivalent strengthening are also to be arranged to support
the sides and ends of large deckhouses.
2.6.3 These
web frames should be spaced about 9 m apart and are to be arranged,
where practicable, in line with watertight bulkheads below. Webs are
also to be arranged in way of large openings, boats, davits and other
points of high loading.
2.6.4 Arrangements
are to be made to minimise the effect of discontinuities in erections.
All openings cut in the sides are to be substantially framed and have
well rounded corners. Continuous coamings or girders are to be fitted
below and above doors and similar openings. House tops are to be strengthened
in way of davits. Special care is to be taken to minimise the size
and number of openings in the side bulkheads in the region of the
ends of erections within 0,5L amidships. Account is to
be taken of the high vertical shear loading which can occur in these
areas.
2.6.5 Adequate
support under the ends of erections is to be provided in the form
of webs, pillars, diaphragms or bulkheads in conjunction with reinforced
deck beams. At the corners of houses and in way of supporting structures,
attention is to be given to the connection to the deck, and inserts
or equivalent arrangements are generally to be fitted especially for
erections that are effective in resisting vertical hull girder bending
as defined in Pt 3, Ch 3, 4.2 Collision bulkhead.
2.6.6 The
side plating of bridges having a length of 0,15L or greater
is to be increased in thickness by 25 per cent at the ends of the
structure, and is to be tapered into the upper deck sheerstrake. This
plating is to be efficiently stiffened at the upper edge and supported
by web plates not more than 1,5 m from the end bulkhead. Proposals
for alternative arrangements, including the use of higher tensile
steel, will be individually considered.
2.7 Erections contributing to hull strength
2.8 Unusual designs
2.8.1 Where
superstructures or deckhouses are of unusual design, the strength
is to be not less than that required by this Chapter for a conventional
design.
|