Section
8 Hydraulic tests on pipes and fittings
8.1 Hydraulic tests before installation on board
8.1.1 All Class I and II pipes and their associated fittings are to be tested by
hydraulic pressure to the Surveyor’s satisfaction. Further, all steam, feed, compressed
air and fuel oil pipes, together with their fittings, are to be similarly tested where
the design pressure is greater than 0,7 MPa. The test is to be carried out after
completion of manufacture and before installation on board and, where applicable, before
insulating and coating. An exception is made for carbon steel steam heating coils for
cargo and slop tanks that are subjected to hot dip coating using zinc or aluminum which
may be subjected to hydraulic testing after the application of the coatings.
8.1.2 Where
the design temperature does not exceed 300°C, the test pressure
is to be 1,5 times the design pressure, as defined in Pt 5, Ch 12, 1.4 Design pressure.
8.1.4 For
steel pipes and integral fittings for use in systems where the design
temperature exceeds 300°C, the test pressure is to be as follows:
-
For carbon and
carbon-manganese steel pipes, the test pressure is to be twice the
design pressure, as defined in Pt 5, Ch 12, 1.4 Design pressure.
-
For alloy steel
pipes, the test pressure is to be determined by the following formula,
but need not exceed 2p:
8.1.6 Consideration
will be given to the reduction of the test pressure to not less than
1,5p, where it is necessary to avoid excessive stress
in way of bends, branches, etc.
8.1.7 Valves
and fittings non-integral with the piping system, intended for Classes
I and II, are to be tested in accordance with recognised standards,
but to not less than 1,5 times the design pressure. Where design features
are such that modifications to the test requirements are necessary,
alternative proposals for hydraulic tests are to be submitted for
special consideration.
8.1.9 In
no case is the membrane stress to exceed 90 per cent of the yield
stress at the testing temperature.
8.2 Testing after assembly on board
8.2.1 Heating coils in tanks, gas fuel and fuel oil piping are to be tested by
hydraulic pressure, after installation on board, to 1,5 times the design pressure but in
no case to less than 0,4 MPa.
8.2.3 The
hydraulic test required by Pt 5, Ch 12, 8.2 Testing after assembly on board 8.2.2 may
be omitted provided non-destructive tests by ultrasonic or radiographic
methods are carried out on the entire circumference of all butt welds
with satisfactory results. Where ultrasonic tests have been carried
out, the manufacturer is to provide the Surveyor with a signed statement
confirming that ultrasonic examination has been carried out by an
approved operator and that there were no indications of defects which
could be expected to have a prejudicial effect on the service performance
of the piping.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
![](LR-FooterLogo.png) |
|