Section
5 Equipment and systems – Winterisation C
5.1 General
5.1.1 All items such
as pipework, components and cables are to be located inside spaces
as far as practicable to minimise exposure to low temperatures and
icing.
5.1.2 Each item of equipment
and system on the ship is to be protected against the effects of low
temperatures and build up of ice with the selection of appropriate
protection methods. Methods for protecting the equipment and systems
include the following:
-
Heating (space and dedicated
arrangements for equipment/systems).
-
Ice removal equipment.
-
Covers.
-
Drainage.
-
Insulation.
-
Selection of materials.
-
Selection of lubricants,
oils, hydraulics and greases.
5.1.3 Where heating
arrangements are provided, they are to be fitted with the following:
-
Means for ascertaining the
temperature.
-
For systems where heating
arrangements could result in excessively high temperatures or pressures
being generated, that may cause damage, malfunction, loss of effective
lubrication or braking of equipment, arrangements are to be provide
which will cut off the heating.
-
Suitable control arrangements.
-
Indication that the system(s)
are in use or not.
-
Where failure of a heating arrangement could result in a hazardous
situation, an alarm in accordance with the alarm system required by Pt 6, Ch 1, 2 Essential features for control, alarm, monitoring and safety systems of the Rules and Regulations for the Classification of Ships, July 2022 is to
be activated to allow responsible personnel to prevent the hazardous situation
occurring.
For use of electrical heating in dangerous zones, see
Pt 6, Ch 2, 14 Electrical equipment for use in explosive gas atmospheres or in the presence of combustible dusts of the Rules and Regulations for the Classification of Ships, July 2022.
5.1.4 Where PVC covers
or other water resistant materials are used, they are to be well fitting
with suitable fixing to prevent unintended removal in severe weather.
5.2 Winterisation of machinery – General requirements
5.2.1 Main and essential auxiliary machinery and equipment installed on the open
deck is to be capable of operating satisfactorily under the conditions of the external
design air temperature, see also
Ch 1, 1.4 Definitions 1.4.2.
5.3 Winterisation of main propulsion and essential auxiliary engines
5.3.1 The arrangements
for air supply to main propulsion and essential auxiliary engines
are to ensure that the engine manufacturer's specification for minimum
air intake temperature is complied with. Such arrangements may comprise
pre-heating at the air intakes or use of heated engine room air, or
other means such as scavenge air cooler bypass or exhaust gas bypass.
The main engine lubrication oil is to be maintained at a minimum temperature
in accordance with the manufacturer’s specification.
5.3.2 Sea inlets for
the cooling water system are to be provided with arrangements to maintain
ice free cooling water arrangements as given by IMO Guidance
on Design and Construction of Sea Inlets under Slush Ice Conditions MSC/Circular.504 – Guidance on Design and Construction of Sea Inlets Under Slush Ice Conditions – (28 April 1989)
or in accordance with
the Finnish Swedish Ice Class Rules. Alternative arrangements
will be considered, such as by circulating engine cooling water via
designated tanks where heat balance calculations have demonstrated
that the engines are capable of operating at their maximum continuous
rating.
5.3.3 Electrical and
hydraulic systems for podded or azimuth propulsion systems are to
be provided with suitable provisions to prevent freezing. Heating
arrangements and/or suitable lubrication oils, hydraulic oils and
anti-freeze are also to be provided.
5.3.4 Electrical and
hydraulic systems for steering systems are to be provided with suitable
provisions to prevent freezing. Heating arrangements and/or suitable
lubrication oils, hydraulic oils and anti-freeze are also to be provided.
5.3.5 Steering gear
components are to be provided with suitable low temperature greases
and lubrication oils.
5.4 Winterisation of auxiliary machinery systems and deck working
areas
5.4.2 Systems are to
be arranged to ensure they can be drained to protect against fluids
freezing in pipes. Drainage valves are to be provided and pipework
inclined to ensure drainage of fluids is possible under all normal
angles of list and trim. As a minimum, drain valves are to be provided
at forward, aft, port and starboard locations. Additional shut off
valves are to be installed on the branch pipes (and as close to the
main line as practicable) to allow drainage and protection against
freezing in branch pipes when the main line is under pressure and
branch lines are not in use.
5.4.3 Measures for protection
against freezing of condensate in exposed steam pipework are to be
fitted with thermal insulation and/or connections for dry air to be
blown through. Steam deck machinery is to be provided with measures
for the continuous circulation of steam.
5.4.4 Valves, gauges,
indicators and monitoring equipment for essential services are to
be protected from icing and provided with ice removal measures or
by covers where ice removal measures are not suitable. Exposed valves
at inaccessible locations are to be provided with covers or positioned
in heated cabinets (by means of a heated frame or internal space heating).
Gauges, indicators and monitoring equipment which are sited in exposed
locations but are unsuitable for removal of ice are to be positioned
in heated cabinets. Valve actuators, solenoids and pressure gauge
transmitters for essential services are to be provided with heating
arrangements.
5.4.5 Where no heating arrangements are provided, valves, gauges, indicators and
monitoring equipment for essential services are to be suitable for the external design
air temperature.
5.4.6 Exposed control
stand valves for hydraulic oil lines used for remote control are to
be provided with heating arrangements to protect against freezing
of the mechanism.
5.4.7 As far as practicable, hydraulic oil power packs are to be sited in heated
enclosed spaces. Where this is not practicable, the hydraulic fluid and pipework system
materials are to be suitable for operation at the external design air temperature.
5.4.8 Measures to protect
against water freezing in exposed fresh water and sea water pipes
and valves are to be fitted. Exposed sections of seawater and freshwater
lines are to be fitted with an isolating valve located inside a heated
space such that the exposed length may be drained. Alternatively,
a drain valve is to be provided at the lowest position on deck, and
an air blow connection provided at the furthest forward end to keep
the line dry after use. Alternatively, heating arrangements or continuous
circulation is to be provided.
5.4.9 Measures are to
be provided to protect against humidity freezing the supply of air
to pneumatic devices used on deck. They are to be designed for specified
dew point appropriate to the external design air temperature, or be
provided with air driers, or suitable heating arrangements. A drain
valve is to be provided at the lowest point of the line on the exposed
deck.
5.4.11 The sea inlet and overboard discharge valves are to be provided with low
pressure steam connection for clearing purposes, see
Pt 5, Ch 13 Ship Piping Systems of the Rules and Regulations for the Classification of Ships, July 2022.
Alternatively, arrangements are to be made for supplying water for machinery cooling
purposes by circulating from ballast tanks(s) or those situated in the double bottom.
Such tank(s) must be used only for storage of water ballast or fresh water.
5.4.15 To protect against
freezing, the Oil Discharge Monitoring Equipment (ODME) is to be provided
with heating arrangements on exposed supply/discharge lines and with
steam blowing on the overboard discharge.
5.5 Winterisation of anchoring/mooring equipment and deck cranes
5.5.2 Exposed control
panels are to be provided with suitable steel covers to protect against
icing.
5.5.3 Measures are to
be provided to protect against freezing of fluids, such as lubricants
and hydraulic oil. The fluids are to be suitable for low temperature
operation, and heating arrangements are to be provided where appropriate.
5.5.6 The hawse pipe
is to be sited in a heated space or provided with suitable heating
arrangements and deck steam connection valve(s) located within the
vicinity to protect against icing.
5.5.7 For hydraulically
operated equipment and systems, steam ice removal measures are to
be provided for protection against icing.
5.5.9 Means are to be provided for habitable working conditions in crane cabs,
where fitted, by providing internal space heating arrangements. Cab windows are to be
provided with heating arrangements to protect from the build up of ice, see
Ch 1, 5.8 Winterisation of spaces/compartments 5.8.3. Ice
removal measures are to be provided to protect against icing. Window wiper operating
devices are to be arranged inside the cab or to be provided with heating arrangements.
5.5.10 Suitable provisions
for cold start arrangements for exposed deck cranes are to be provided.
Suitable lubrication oils and greases, circulation facilities for
hydraulic oils and a flushing system for the hydraulic oil are to
be provided.
5.6 Winterisation of electrical installations
5.6.2 The schedule of
loads is to include operation in cold climates as a separate winterisation
condition.
5.6.3 Emergency generators are to be capable of operating at the external design
air temperature and are to be provided in a heated room and/or are to be suitable for
using fuel oil specified for low temperature conditions, and provided with protection or
heating arrangements on the air intake. Suitable antifreeze or heating arrangements are
to be used in the cooling system with a dew point appropriate to the external design air
temperature. Where an air start system is installed the air is to be dried.
5.6.4 The emergency
generator room air intakes are to be provided with protection from
icing by ice removal measures or heating arrangements. In addition,
the air intake is to be provided with an automatic louvre which closes
whilst the generator is inactive (to reduce heat loss), and open when
starting.
5.6.5 Exposed electric
motors installed on equipment are to be provided with covers or ice
removal measures to aid the removal of ice. Measures are to be provided
to protect against humidity and condensation freezing in the motor
and to achieve this they are to be provided with suitable heating
arrangements.
5.6.6 Exposed components of electrical cabling are to be suitable for operation at
the external design air temperature.
5.6.7 Measures to protect
exposed cables from manual ice removal methods are to be provided.
Penetrations in exposed decks for electrical cables are to be enclosed
in protective steel covers extending 0,5 m from the penetration or
to the item if this is closer.
5.6.8 Switch boxes and control panels in unheated areas are to be fitted with
heating arrangements or be sealed units suitable for operation at the external design
air temperature, to prevent condensation freezing.
5.6.9 For navigation aids and equipment, the temperature for use as stated by the
manufacturer is to be suitable for the external design air temperature.
5.6.10 Protection measures
are to be fitted for the continuous operation of the radar motors
against the humidity and icing freezing the motor. Radar motors are
to be provided with heating arrangements and with the provision for
suitable use of low temperature grease.
5.6.11 Measures for
continuous operation of the navigation air horn, where fitted, are
to be provided to protect against humidity freezing in components
and icing. Dry air is to be used and suitable heating arrangements
are to be provided. Air pipe lines for the navigation air horn are
to be arranged in heated compartments as far as practicable, see
also
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.9.
5.6.12 Remotely controlled
and focused search lights are to be provided at the bow and the bridge
wings to combat reduced daylight hours and aid navigation in ice infested
waters. The search lights are to be fitted with trace heating on the
lens or provided with a cover, and with heating arrangements for the
directional motor.
5.6.13 Exposed magnetic
compasses, where fitted, are to be protected by covers from icing.
5.6.14 Where closed
circuit television systems are fitted in exposed locations, these
are to be provided with heating arrangements or covers, and ice removal
measures to protect against icing and freezing of the motors, wipers
and screen.
5.6.15 Satellite/GPS
motors are to be provided with suitable low temperature grease. Antenna
systems are to be protected from icing.
5.6.16 Lighting arrangements in working areas on the deck, and in particular the
forecastle, are to be located at accessible positions to facilitate ice removal. Exposed
lights are to be suitable for the external design air temperature and with due regard
being given to changes in illumination values.
5.6.17 Navigation lights are to be of a type tested with the intended light source
to demonstrate that they are suitable for the external design air temperature, such that
illumination will not be reduced or obscured.
5.7 Winterisation of emergency appliances
5.7.1 Fire pumps and
the emergency fire pump are to be located in heated spaces to protect
against freezing components and fluids.
5.7.2 The fire main
in exposed positions (including the main deck line and accommodation)
is to be protected against freezing in the line and hydrants. Isolating
valves are to be located in a heated space and arranged such that
the exposed part may be drained. Alternatively, means are to be provided
to ensure the isolating valve is dry before closing, continuously
circulated and with thermal insulation or provided with heating arrangements. See
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.8 for similar arrangements.
5.7.3 The exposed fire
main is to be routed through internal heated spaces as far as practicable
considering particular ship arrangements.
5.7.4 Sea water suctions
for fire pumps are to be provided with heating arrangements for ice
clearing. Steam blowing is to be provided or means of using the engine
room sea chest.
5.7.5 Water spray lines,
where fitted, are to be designed to protect against the lines freezing
and the nozzles clogging with ice. They are to be located inside and
have external nozzles of a design to minimise freezing, or provided
with drainage facilities and arranged to be blown through with dry
air, or provided with heating arrangements.
5.7.7 For fire-extinguishing media, such as foam systems, the temperature for use
as stated by the manufacturer is to be suitable for the external air temperature.
Extinguishers are to be suitable for low temperature use or located in heated
spaces.
5.7.8 Arrangements are
to be provided such that after use, the fire hoses can be drained
and dried to protect from freezing. Stowage arrangements are to be
provided with heating arrangements or at least two additional hoses
provided to enable wet hoses to be replaced whilst drying.
5.7.9 As far as practicable,
lifeboats and liferafts are to be located in protected locations (recesses
or garages) to provide protection from icing.
5.7.10 Lifeboats are
to be of totally enclosed type and provided with internal space heaters
to maintain a habitable temperature. Adjacent receptacles for electrical
heating arrangements are to be supplied from the emergency switchboard.
5.7.11 The lifeboat
coxswain’s control panel is to be provided with heating arrangements.
Ice removal measures to remove icing from windows are to be provided.
5.7.12 Lifeboat engines
are to be provided with suitable low temperature grades of fuel oil
and lubrication oil to protect against the effects of freezing. The
cooling system for the engines is to be provided with suitable anti-freeze.
5.7.13 Lifeboat engine
batteries are to be suitable for low temperature conditions, or a
flexible lead for battery charging and a means of safe heating is
to be provided.
5.7.14 Lifeboat winches,
where fitted, are to be provided with suitable covers or ice removal
measures. The operating devices (brake(s)) are to be protected from
icing by ice removal measures, suitable grease and lubricants with
covers or heating arrangements. Hydraulic systems, including tanks,
pipes and mechanisms, are to be provided with suitable steam ice-removal
measures, suitable grease and lubricants or heating arrangements.
5.7.15 Lifeboat davits/sheaves/release
hooks are to have provision for the use of suitable low temperature
grease, covers and heating arrangements, to protect the mechanisms
from icing.
5.7.16 To protect from
icing, the embarkation (lifeboat rope) ladders are to be provided
with covers in the stowed position.
5.7.17 Lifeboat water
spray lines, where fitted, are to be located inside and have external
nozzles of a design to minimise freezing or to have drainage facilities
and arranged to be blown through with dry air, see
Ch 1, 5.7 Winterisation of emergency appliances 5.7.5. In addition, the water intake is to
be protected from ice build up.
5.7.18 Liferafts are to be suitable for the external design air temperature. A
steam connection for ice removal measures is to be provided for protection against icing
of the liferaft. Davit-launched liferafts are to comply with Ch 1, 5.7 Winterisation of emergency appliances 5.7.14.
5.7.19 For life saving equipment, the temperature for use as stated by the
manufacturer is to be suitable for the external design air temperature. Measures are to
be provided for lifeboat contents (including flares and torch batteries) for low
temperature operation. Ice removal measures are to be provided for the EPIRB/SART.
5.7.20 Rescue boats
are to be provided with systems which are similar to those for lifeboats.
5.7.21 Means are to
be provided to protect fluids within exposed pipes for decontamination
showers and eyewash systems from freezing, where fitted. Heating arrangements
are to be provided in the water tank and exposed sections of piping
are to be provided with insulation or trace heating arrangements.
Alternatively, these are to be sited in a heated room/compartment.
Additional eyewash fluids are to be stored in an alternative heated
space.
5.7.23 Immersion suits
are to be suitable for low temperature operation and stored in heated
spaces or containers in locations with suitable ice removal measures.
5.8 Winterisation of spaces/compartments
5.8.1 Accommodation heating/air conditioning systems are to be capable of
maintaining internal design air temperature in all spaces normally occupied when the
ship is at sea, based on the external design air temperature, see
Ch 1, 1.3 Information required 1.3.4 and Ch 1, 1.4 Definitions 1.4.4. This may be achieved by controlling the number of
air changes providing acceptable levels of fresh air required for personnel efficiency,
combustion or other oxidation processes.
5.8.2 The requirements
in Ch 1, 5.8 Winterisation of spaces/compartments 5.8.1 are intended to mitigate risks
associated with the failure to maintain suitable (and agreed, see
Ch 1, 1.3 Information required 1.3.4 and Ch 1, 1.4 Definitions 1.4.4)
temperatures associated with the defined spaces, and do not cover
air-conditioning arrangements, air distribution ductwork, heating
systems, chilled water systems or the calculation and verification
of air flow rates and cooling/heating loads within the air-conditioned
spaces. The method used to calculate the capacity of the air conditioning,
refrigeration and heating equipment is the responsibility of the Shipbuilder
and Owner and should be in accordance with a recognised code or standard
such as ISO 7547:2002 Ships and marine technology – Air
conditioning and ventilation of accommodation spaces – Design
conditions and basis of calculations, or ASHRAE 26- 1996(RA2006) Mechanical refrigeration and air-conditioning installations aboard
ship.
5.8.3 Heating arrangements (in addition to, and not necessarily serviced by, the
air-conditioning system as specified in Ch 1, 5.8 Winterisation of spaces/compartments 5.8.1) are to be provided for spaces containing machinery
and equipment for essential or emergency services and for spaces accessed during ship
operation in order that equipment may be maintained. Heating arrangements are to be
included in, but not limited to, the spaces as given in Table 1.5.1 Space heating arrangements for
Winterisation C(t) (where fitted): The heating of each space is
to be capable of maintaining its internal design air temperature based on the external
design air temperature, insulation and the volume of air in each space. The internal
temperature, and lowest limit for alarms, for each space is to be provided (and agreed
with the Owner and Shipbuilder), but is to be a minimum of zero degrees Celsius at the
external design air temperature.
Table 1.5.1 Space heating arrangements for
Winterisation C(t)
Space
|
Heating
arrangements
|
Alarm, see Note
1
|
Navigation bridge
|
Fixed
|
X
|
Radio room (where fitted)
|
Fixed
|
X
|
Hospital room/sick bay
|
Fixed
|
X
|
Battery room, see Note 2
|
Fixed
|
|
Mooring rope stores (including the
bosun's store)
|
Multiple fixed
|
|
Observation/security cabins (where
fitted)
|
Portable
|
|
Enclosed forecastle/sheltered deck
(where fitted)
|
Portable
|
|
Under-deck passageways (where fitted,
to allow alternative access to bow spaces and which are adjacent to exposed
external boundaries)
|
Multiple fixed
|
X
|
Main engine and auxiliary machinery
space(s)
|
Multiple fixed
|
X
|
Podded propulsion or azimuth thruster
space(s)
|
Portable
|
|
Boiler room
|
Portable
|
|
Generator room(s)
|
Multiple fixed
|
X
|
Workshop room and store(s)
|
Portable
|
|
Engine control room
|
Portable
|
|
Switchboard room
|
Fixed electrical type
|
|
Steering gear room
|
Multiple fixed
|
X
|
Bow thruster(s) room (when an
integral part of dynamic positioning or for essential manoeuvring),
see Note 3
|
Fixed
|
|
Oil Discharge Monitoring Equipment
(ODME) room
|
Multiple fixed
|
X
|
Emergency generator room, see
Note 4
|
Fixed
|
X
|
Fire-fighting control room(s) and
inert gas cylinder and foam system equipment rooms where fitted
|
Fixed
|
X
|
Fire-fighting equipment store room
(including location of fireman’s outfit)
|
Multiple fixed
|
X
|
Emergency fire
pump-room, see Note 5
|
Multiple fixed
|
X
|
Note
2. In addition, a portable heater is to
be provided. Alternatively, an additional battery or increased heating
capacity may be provided.
Note
3. Alternatively, the bow thruster is to
be suitable for operation at the design external air temperature.
Note
5. A single heater may be provided when
located below the waterline and adjacent to a heated space.
|
5.8.4 Means of regulating
the engine room temperature are to be provided. Where machinery space
funnel louvres are fitted, these are to be capable of being adjusted
to different open positions. The means of regulating temperature is
not to prevent air supply or exhaust to machinery or machinery spaces
required for operation.
5.8.5 Pipework and electrical components in and passing through spaces and tanks,
without space heating and which are exposed to low temperatures, such as void spaces and
underdeck passageways, are to be suitable for the external design air temperature or
have suitable heating arrangements to protect against the low temperatures, see
also
Ch 1, 3.4 Plating 3.4.3.
5.8.6 The air intakes
and exhaust louvres for accommodation and machinery spaces are to
be provided with protection from icing by ice removal measures and
heating arrangements.
5.8.7 All cargo control
room windows are to be fitted with heating arrangements to provide
protection against the formation of ice obscuring visibility during
discharging/loading operations. Ice removal measures are to be provided. See also
Ch 1, 5.8 Winterisation of spaces/compartments 5.8.8 for other suitable
arrangements.
5.8.8 All bridge windows
(excluding door windows) are to be fitted with heating arrangements
to provide protection against the build up of ice obscuring visibility.
The use of hot air blowers on the inside is to be provided for all
windows. Consideration is to be given to fitting double glazed windows
in order to provide protection against cold water cracking glass which
is exposed to warm internal conditions.
5.8.9 The system for
window cleaning is to be protected against freezing in the lines and
clogging of the nozzles with frequent operation. Cold fresh water
systems with heated spray nozzles or hot water systems designed to
be drained and dry air blown through after use are to be provided.
Window wiper operating devices are to be arranged inside the bridge
or to be provided with heating arrangements. Safe access is to be
provided externally for ice removal.
5.8.10 Measures to
protect personnel operating on the bridge from cold temperatures are
to be provided. Where ships have exposed bridge wings, the wing controls/equipment
are to be provided with heating arrangements and covers.
5.9 Winterisation of accommodation and escape routes
5.9.1 Measures are to
be provided to assist in the opening of doors when covered in ice
and to protect seals against freezing. External doors are to be positioned
in protected locations or recessed as far as practicable to provide
protection from icing. The enclosed space adjacent to external doors
on escape routes is to be fitted with heating arrangements.
5.9.2 Suitable changing
rooms are to be arranged to provide adequate space for changing into
and out of cold weather working clothing adjacent to the entrance
door. A heated space is to be provided for drying and storing cold
weather working clothing.
5.9.3 Measures are to
be provided to reduce the likelihood of damage to insulation fitted
to exposed external boundaries caused by humidity freezing within
it. In particular the accommodation bulkhead/deckhead insulation is
to be fitted with a protective vapour barrier such as aluminium foil
or equivalent means.
5.9.4 To protect against
fluids freezing, cabin bathrooms are not to be located adjacent to
exposed external boundaries, as far as practicable.
5.9.5 Insulation and
heating arrangements are to be provided for all exposed external boundaries
in bathrooms and washrooms to prevent freezing of water in these spaces.
5.9.6 Means such as
a gutter and drainage on the deck below to collect condensed water
are to be provided adjacent to external boundaries.
5.10 Winterisation of tanks
5.10.1 Fresh water
and sea-water ballast tanks, the tops of which are situated above
the design ballast waterline and adjacent to the shell, which are
intended to be used in ice and cold navigating conditions, are to
be provided with means to prevent freezing. Measures are to be provided
to demonstrate that they protect against the following:
-
hull structural damage
from pumping water creating a vacuum beneath a layer of ice across
the top of the water in the tank;
-
hull structural damage
from ice expansion;
-
engineering systems damage
from ice expansion or ice blockage; and
-
engineering systems damage
from ice pieces melting or dislodging from upper sections of the tank.
Heating coils are considered an effective means for tanks entirely
above the waterline. Heating coils or other effective means such as
continuous circulation, air bubbling and/or tank pressure/engineering
systems alarms are considered effective for tanks partially below
the waterline. Alternatively, demonstration that the above hazards
have been mitigated is to be submitted through theoretical calculations,
service experience, experimental tests, or a combination thereof.
5.10.3 Tank systems and components for monitoring and alarms (1st and 2nd stage
high level alarm systems, gas detection system, etc.), are to be suitable for the
design external air temperature.
5.10.4 The sewage tanks
and associated pipe systems, where located adjacent to external ship
boundaries, are to be located in heated compartments or provided with
heating arrangements.
5.10.5 Measures to
provide protection from icing and blockage by ice formation resulting
from humidity in tanks are to be fitted. Exposed air vent pipe heads
of tanks are to be readily accessible, positioned in protected locations
as far as practicable and fitted with covers to limit build up of
ice. The covers are not to interfere with the free flow of air through
the vent openings.
5.10.6 Where ballast
tank heating coils are provided as given in Ch 1, 5.10 Winterisation of tanks 5.10.1, a section of the heating coil is to be positioned below the
air pipe vent, as far as practicable, to provide protection against
freezing of the pipe and vent.
5.10.7 The overboard
ballast discharge line located above the waterline is to be provided
with suitable heating arrangements.
5.11 Ice removal and prevention measures
5.11.1 The following
areas of exposed decks are to be provided with:
-
heated decks;
-
gratings;
-
checkered plate:
-
welded studs; or
-
non-slip decking with coarse
sand embedded into the paint.
In addition ice removal measures are to be installed, of either
steam or hot water types, with a fixed pipe line on the deck with
connection valves for hoses in the following areas:
-
Gangways and stairways
for safe access to bow, lifeboats, rescue boats and pilot boarding
locations, see also
Ch 1, 6.7 Winterisation of accommodation and escape routes 6.7.2.
-
Areas adjacent to escape
exits.
-
Areas in way of lifeboats/rescue
boats, davits, and liferafts including launching areas.
-
Adjacent to storage facilities
for fire fighting equipment.
-
Areas in way of anchoring
and mooring operations (including windlass, chain and hawse pipe).
-
Areas for open navigation
and lookout.
-
Helicopter deck areas,
where fitted.
-
Working areas on
the open deck (including ice removal measures for hatch covers, containers
and grain loading covers).
5.11.2 To aid the removal
of ice and protect against the ingress of water into components that
may subsequently freeze and result in damage, mechanical and electrical
equipment and control panels that may be exposed to icing are to be
provided with suitable covers, as far as practicable, and unless other
arrangements are specified in these Rules.
5.11.3 A minimum of
the following manual tools for removing ice are to be provided, provided,
with at least one set of tools at each storage location. Storage locations
should be as given in Ch 1, 5.11 Ice removal and prevention measures 5.11.4. A set
of tools is to comprise at least the following:
-
3 shovels,
-
3 hammers or mallets,
-
3 scrapers.
Storage facilities for the manual tools are to be provided and
sited in protected areas, as far as practicable, to provide access
and protection from icing behind bulwarks and accommodation walls.
5.11.4 Containers for
the storage of de-icing compounds are to be provided at the following
locations as a minimum:
-
Bow area
-
Close to midships (with
port and starboard access, and close to the boarding area)
-
Stern area (close to the
life saving launching areas)
Containers are to be sited in protected areas, as far as practicable,
to provide access and protection from icing behind bulwarks and accommodation
walls.
5.12 Bow loading systems
5.12.1 In general,
bow loading systems are to comply with Table 1.5.2 Bow loading systems - System with
valve coupling connection overboard or Table 1.5.3 Bow loading systems - System with
valve coupling connection inboard . Alternative
arrangements and components are to be suitably reviewed and assessed
by LR in conjunction with the appropriate requirements in the Winterisation
Rules, taking into account the intended operational and environmental
conditions.
Table 1.5.2 Bow loading systems - System with
valve coupling connection overboard
Component
|
Applicable winterisation requirement
|
See also Rule reference
|
Horizontal slipway from bow to the
coupling valves
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Coupling valve attached to fixed
piping
|
A
|
Materials are to be suitable for
operation at the external design air piping temperature or components are
to be provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
‘A’ frame lifting device
|
|
Material grades are to be in
accordance with LR’s Code for Lifting Appliances in a Marine
Environment and suitable for operation at the external design air
temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.11
|
Inboard ball valve
|
A
|
Materials are to be suitable for
operation at the external design air temperature or components are to be
provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
Bow loading housing, where
fitted
|
|
All items such as pipework, components
and cables are to be located inside spaces as far as practicable to minimise
exposure to low temperature and icing
|
Ch 1, 5.1 General 5.1.2
|
Bow door, where housing fitted
|
|
Materials grades to be taken as for
hatch covers
|
Table 1.2.5 Material classes and
grades
|
Remote control post (RCPH/E)
|
|
Exposed control panels are to be
fitted in heated steel covers to protect against icing and components
freezing
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.2
|
Guide rollers for hose handling
wire
|
|
Material grades are to be suitable
for operation at the external design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Ball valve cabinet (emergency
shut-down)
|
|
Exposed control panels are to be
fitted in heated steel covers to protect against icing and components
freezing
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.2
|
Hydraulic power packs
|
|
Hydraulic oil power packs are to be
sited in heated enclosed spaces Where this is not
practicable, the hydraulic fluid and pipework system materials are to be
suitable for operation at the design external air temperature
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.7
|
Electro Hydraulic main pump
|
|
Exposed electric motors installed on
equipment are to be provided with covers or ice removal measures. Measures
are to be provided to protect against the humidity and condensation freezing
in the motor, and are to be provided with suitable heating
arrangements
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.5
|
Hydraulic oil tank
|
|
Heating is to be provided under the
bottom of the hydraulic oil tank
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.7
|
|
A
|
Materials are to be suitable for
operation at the external design air temperature or components are to be
provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
Auxiliary and starter cabinet
|
|
Where located in unheated areas, are
to be fitted with heating arrangements to prevent condensation
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.8
|
Electric equipment cabinet
|
|
Where located in unheated areas, are
to be fitted with heating arrangements to prevent condensation
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.8
|
Table 1.5.3 Bow loading systems - System with
valve coupling connection inboard
Component
|
Applicable winterisation requirement
|
See also Rule reference
|
‘Moment free’ bow loading coupler with
a ship valve
|
A
|
Materials are to be
suitable for operation at the external design air temperature or components
are to be provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
Adjustable roller fairlead for chafe
chain
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Mooring
chain stopper
|
Material grades are to be suitable for operation at
the external design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Horizontal guide roller for mooring
hawser messenger
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Guide roller with load cell for
mooring hawser messenger
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Chain for emergency towing
system
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Guide rollers for hose handling
wire
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Mooring hawser messenger traction
winch
|
Winches are to be protected from icing by means of suitable
covers, alternatively a sheltered deck area is to be provided
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.1
|
Drum winch for hose wire winch (this
may be common with hydraulic power pack for the above)
|
Winches are to be protected from icing by means of suitable
covers, alternatively a sheltered deck area is to be provided
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.1
|
Guide roller for mooring hawser
messenger rope storage unit
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Mooring hawser messenger rope storage
unit
|
Winches are to be protected from icing by means of suitable
covers, alternatively a sheltered deck area is to be provided
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.1
|
Mooring hawser messenger
guide roller
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Bow door
|
Materials grades to be taken as for hatch covers
|
Table 1.2.5 Material classes and
grades
|
Inboard cargo
lines
|
Arrangements are to be provided to protect against cargo fluids
within exposed pipes from freezing. The exposed deck cargo and stripping
lines are to be fitted with thermal insulation and suitable trace heating
arrangements
|
Ch 1, 8.2 Winterisation of oil and/or chemical tankers 8.2.1
|
Drain line
|
Systems are to be arranged to ensure that they can be drained to
protect against fluids freezing in pipes. Drainage valves are to be provided
and pipework inclined to ensure that drainage of fluids is possible under
all normal angles of list and trim. As a minimum, drain valves are to be
provided at forward, aft, port and starboard locations. Additional shut-off
valves are to be installed on the branch pipes (and as close to the main
line as practicable) to allow drainage and protection against freezing in
branch pipes when the main line is under pressure and branch lines are not
in use
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.2
|
Inboard ball
valve
|
A
|
Materials are to be
suitable for operation at the external design air temperature or components
are to be provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
Inboard pressure transmitter
|
Exposed lines are to be provided with heating arrangements
|
Ch 1, 8.2 Winterisation of oil and/or chemical tankers 8.2.2
|
Remote control post
(RCPH/E)
|
Exposed control panels are to be fitted in heated steel covers to
protect against icing and components freezing
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.2
|
Ball valve cabinet (emergency
shut-down)
|
Exposed control panels are to be fitted in heated steel covers to
protect against icing and components freezing
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.2
|
Hose handling bow
roller
|
Material grades are to be suitable for operation at the external
design air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.12
|
Hydraulic pipes with
accessories
|
Hydraulic oil power packs are to be sited in heated enclosed
spaces. Where this is not practicable, the hydraulic fluid and pipework
system materials are to be suitable for operation at the lowest design
external air temperature
|
Ch 1, 5.5 Winterisation of anchoring/mooring equipment and deck cranes 5.5.8
|
Hydraulic valves
|
A
|
Materials are to be suitable for
operation at the external design air temperature or components are to be
provided with suitable heating arrangements
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.1
|
|
B
|
Valves are to be provided with ice
removal measures or by covers where ice removal measures are not suitable.
Exposed valves at inaccessible locations are to be provided with covers or
positioned in heated cabinets (by means of a heated frame or internal space
heating)
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.4
|
Control device for load
cells, storage inside
|
Exposed components of electric cabling are to be suitable for
operation at the lowest design external air temperature
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.6
|
Watchkeeper
shelter
|
Where observation cabins are fitted, suitable heating
arrangements are to be provided for the internal space and windows
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.13
|
Electric motors for
pumps
|
Exposed electric motors installed on equipment are to be provided
with covers or ice removal measures. Measures are to be provided to protect
against the humidity freezing in the motor, and are to be provided with
suitable heating arrangements
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.5
|
Hydraulic oil tank
|
Heating is to be provided under the bottom of the hydraulic oil
tank
|
Ch 1, 5.4 Winterisation of auxiliary machinery systems and deck working areas 5.4.7
|
Starter cabinets
|
Where located in unheated areas are to be fitted with heating
arrangements to prevent condensation
|
Ch 1, 5.6 Winterisation of electrical installations 5.6.8
|
|