Section
3 Fire safety measures for yachts 500 gt or more
3.1 General
3.1.1
Table 3.3.1 General fire protection, detection
and extinction requirements is a guide to the major
requirements of this Section. The Table is intended as a quick reference
to the requirements and is not to be used in isolation when designing
the fire safety arrangements.
Table 3.3.1 General fire protection, detection
and extinction requirements
Form of construction, see
Pt 17, Ch 3, 3.2 Forms of construction Structure
|
Steel or equivalent, or alternative
forms of construction may be accepted subject to extensive insulation
requirements
|
Passive fire protection, see
Pt 17, Ch 3, 3.3 Forms of construction Fire divisions
|
See
Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces
|
Means of escape, see
Pt 17, Ch 3, 3.15 Structural fire protection Means of escape:
|
|
- Category A machinery spaces
|
2
|
|
2
|
Fixed fire detection
system, see
Pt 17, Ch 3, 3.24 Fixed fire detection and fire-alarm systems
|
- Fitted in machinery spaces
- Fitted in service spaces, control stations and
accommodation spaces
|
Fire pumps, see
Pt 17, Ch 3, 3.25 Fire pumps and fire main system
|
- In general, 2 independent power pumps
- For yachts of ≥ 4000 gross tons: 3 independent power
pumps
- A fire in any one compartment is not to put all the fire
pumps out of action
|
International shore
connection, see
Pt 17, Ch 3, 3.25 Fire pumps and fire main system 3.25.11
|
At least 1
|
Fire extinguishing arrangements in
Category A machinery spaces, see
Pt 17, Ch 3, 3.26 Fire-extinguishing arrangements in spaces containing internal combustion machinery. See also
Pt 17, Ch 3, 3.27 Fire-extinguishing arrangements in spaces containing fuel oil units for fuel oil units
|
- A fixed fire extinguishing system
- Portable air-foam equipment
- 45 litre foam extinguisher
- Portable foam extinguishers within 10 m walking
distance
|
Portable fire-extinguishers in
accommodation, see
Pt 17, Ch 3, 3.32 Portable fire-extinguishers
|
Sufficient to ensure that at least
one will be readily available in every compartment, but a minimum of
five
|
Automatic sprinkler system or
equivalent, see
Pt 17, Ch 3, 3.29 Automatic sprinkler, fire detection and fire-alarm system
|
Fitted in all yachts
|
Firemans
outfits, see
Pt 17, Ch 3, 3.38 Fireman's outfit
|
At least 2
|
3.2 Forms of construction Structure
3.2.1 The hull,
superstructure, structural bulkheads, decks and deckhouses may be
constructed of steel, other equivalent material, see
Pt 17, Ch 1, 2.1 Materials 2.1.2 or be of alternative forms
of construction, see
Pt 17, Ch 1, 2.1 Materials 2.1.3.
3.2.2 The structure
in way of Category A' machinery spaces, galleys containing
appliances of significant fire risk and other high risk areas is to
be protected such that the material by itself or due to insulation
provided can maintain its required strength at the end of 60 minutes
exposure to the standard fire test.
3.2.4 For aluminium
alloy structures, the insulation is to be such that the temperature
of the structural core does not rise more than 200oC above
the ambient temperature at any time during the specified fire exposure.
3.2.5 For composite
structures, the insulation is to be such that the temperature of the
laminate does not rise more than the minimum temperature of deflection
under load of the resin at any time during the specified fire exposure.
The temperature of deflection under load is to be determined as in Ch 14, 3.7 Tests for specific materials of the Rules for Materials.
3.3 Forms of construction Fire divisions
3.3.2 Fire divisions
using steel equivalent, or alternative forms of construction, may
be accepted if it can be demonstrated that the material by itself
due to insulation provided, has the fire resistance properties equivalent
to A' or B' Class divisions.
3.3.3 Insulation
required by Pt 17, Ch 3, 3.3 Forms of construction Fire divisions 3.3.2 is to be such
that the temperature of the structural core does not rise above the
point at which the structure would begin to lose its strength at any
time during the applicable exposure to the standard fire test. For
A' Class divisions, the applicable exposure is 60 minutes,
and for B' Class divisions, the applicable exposure is 30 minutes.
3.3.4 For aluminium
alloy structures, the insulation is to be such that the temperature
of the structural core does not rise more than 200oC above
the ambient temperature at any time during the applicable fire exposure.
3.3.5 For composite
structures, the insulation is to be such that the temperature of the
laminate does not rise more than the minimum temperature of deflection
under load of the resin at any time during the applicable fire exposure.
The temperature of deflection under load is to be determined as in Ch 14, 3.7 Tests for specific materials of the Rules for Materials.
3.4 Structural fire protection Main vertical zones and horizontal
zones
3.4.2 As far
as practicable, the bulkheads forming the boundaries of the main vertical
zones above the bulkhead deck are to be in line with watertight subdivision
bulkheads situated immediately below the bulkhead deck.
3.4.3 The bulkheads
mentioned in Pt 17, Ch 3, 3.4 Structural fire protection Main vertical zones and horizontal zones 3.4.2 are to extend
from deck to deck and to the shell or other boundaries.
Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces
Spaces
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
Control stations
|
(1)
|
A-0 See Note 3
|
A-0
|
A-60
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
See Note 7
|
Corridors
|
(2)
|
|
C See Note 4
|
'B-0 See Note 4
|
A-0 See Note
1 B-0 See Note 4
|
'B-0 See Note 4
|
A-60
|
A-0
|
A-15
A-0 See Note 6
|
See Note 7
|
Accommodation spaces
|
(3)
|
|
|
C See Note 4
|
A-0 See Note
1 B-0 See Note 4
|
B-0 See Note 4
|
A-60
|
A-0
|
A-15
A-0 See Note 6
|
See Note 7
|
Stairways
|
(4)
|
|
|
|
A-0 See Note
1 B-0 See Note 4
|
A-0 See Note
1 'B-0 See Note 4
|
A-60
|
A-0
|
A-15
A-0 See Note 6
|
See Note 7
|
Service spaces (low risk)
|
(5)
|
|
|
|
|
C See Note 4
|
A-60
|
A-0
|
A-0
|
See Note 7
|
Machinery spaces of Category A and
spaces containing vehicles or craft with fuel in their tanks or lockers
storing such fuels
|
(6)
|
|
|
|
|
|
A-60 See Note 2
|
A-0
|
A-60
|
See Note 7
|
Other machinery spaces
|
(7)
|
|
|
|
|
|
|
'A-0 See Note 2
|
A-0
|
See Note 7
|
Service spaces (high risk)
|
(8)
|
|
|
|
|
|
|
|
A-0 See Note 2
|
See Note 7
|
Open decks
|
(9)
|
|
|
|
|
|
|
|
|
|
Note
2. Where spaces are of the same numerical
category and Note 2 appears, a bulkhead or deck of the ratings shown
in the Table is only required when the adjacent spaces are for a
different purpose, e.g. in category (8), a galley next to a galley
does not require a bulkhead, but a galley next to a paint room
requires an A-0 Class bulkhead.
Note
3. Bulkheads separating the wheelhouse
and chartroom from each other may be B-0 rating.
Note
5. Fire insulation need not be fitted if
the machinery space of category (7) has little or no fire risk.
Note
6. Where the spaces are protected by the
sprinkler system on both sides of the division, the division may be
A-0 Class. Where the sprinkler system only protects a space on one
side of the division the rating is to be the higher of the two values
given.
Note
7. The division is to be of steel, other
equivalent material, or alternative forms of construction, but is not
required to be of A Class standard. However, where decks, except
open decks, are penetrated for the passage of electric cables, pipes
and vent ducts, such penetrations are to be made tight to prevent the
passage of flame and smoke.
|
Table 3.3.3 Fire integrity of decks separating
adjacent spaces
|
Space above
|
Space
below
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
Control stations
|
(1)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Corridors
|
(2)
|
A-0
|
See Note 3
|
See Note 3
|
A-0
|
See Note 3
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Accommodation spaces
|
(3)
|
A-60
|
A-0
|
See Note 3
|
A-0
|
See Note 3
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Stairways
|
(4)
|
A-0
|
A-0
|
A-0
|
See Note 3
|
A-0
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Service spaces (low risk)
|
(5)
|
A-15
|
A-0
|
A-0
|
A-0
|
See Note 3
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Machinery spaces of Category A and
spaces containing vehicles or craft with fuel in their tanks or lockers
storing such fuels
|
(6)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60 See Note 1
|
A-60
|
See Note 3
|
Other machinery spaces
|
(7)
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
See Note 3
|
A-0
|
See Note 3
|
Service spaces (high risk)
|
(8)
|
A-60
|
A-30
'A-0 See Note 2
|
A-30
'A-0 See Note 2
|
A-30
'A-0 See Note 2
|
A-0
|
A-60
|
A-0
|
A-0
|
See Note 3
|
Open decks
|
(9)
|
See Note 3
|
See Note 3
|
See Note 3
|
See Note 3
|
See Note 3
|
See Note 3
|
See Note 3
|
See Note 3
|
|
Note
1. Fire insulation need not be fitted if
the machinery space of category (7) has little or no fire risk.
Note
2. Where the spaces are protected by the
sprinkler system on both sides of the division, the division may be
A-0 Class. Where the sprinkler system only protects a space on one
side of the division the rating is to be the higher of the two values
given.
Note
3. The division is to be of steel, other
equivalent material, or alternative forms of construction, but is not
required to be of A Class standard. However, where decks, except
open decks, are penetrated for the passage of electric cables, pipes
and vent ducts, such penetrations are to be made tight to prevent the
passage of flame and smoke.
|
3.5 Structural fire protection of bulkheads within a main vertical
zone
3.5.1 All such
divisions may be faced with combustible materials.
3.5.2 When continuous
B' Class ceilings and/or linings are fitted on both sides of
the bulkhead, the portion of the bulkhead behind the continuous ceiling
or lining is to be of material which in thickness and composition
is acceptable the construction of B' Class divisions but which
may meet B' Class standards only insofar as is reasonable and
practicable.
3.5.3 All bulkheads
required to be B' Class divisions, except corridor bulkheads
prescribed in Pt 17, Ch 3, 3.5 Structural fire protection of bulkheads within a main vertical zone 3.5.2 are to
extend from deck to deck and to the shell or other boundaries unless
continuous B' Class ceilings or linings fitted on both sides
of the bulkhead are at least of the same fire resistance as the bulkhead,
in which case the bulkhead may terminate at the continuous ceiling
or lining.
3.6 Structural fire protection Fire integrity of bulkheads
and decks
3.6.2 For determining
the appropriate fire integrity standards to be applied to divisions
between adjacent spaces, such spaces are classified in Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces according to their fire-risk
as shown in space categories
(1)
to
(9)
. The title of each category is intended to be typical
(general) rather than restrictive. The number in parentheses preceding
each space category refers to the applicable column or row in the
Tables.
-
Control stations:
- Spaces containing emergency sources of power and lighting.
- Wheelhouse and chartroom.
- Spaces containing the ship's radio equipment.
- Fire-extinguishing rooms, fire-control stations and fire recording
stations.
- Control room for propulsion machinery when located outside the
machinery space.
- Spaces containing centralised fire-alarm equipment.
-
Corridors:
- Guest and crew corridors and lobbies.
-
Accommodation spaces:
-
Stairways:
- Interior stairways, lifts and escalators (other than those wholly
contained within the machinery spaces) and enclosures thereto.
- In this connection, a stairway which is enclosed only at one level
is to be regarded as part of the space from which it is not separated
by a fire door.
-
Service spaces (low risk):
- Lockers and store-rooms having areas of less than 4 m2 ,
drying rooms and laundries.
-
Category A' machinery spaces, spaces containing vehicles
or craft with fuel in their tanks, or lockers storing such fuels:
-
Other machinery spaces:
-
Service spaces (high risk):
- Galleys, pantries containing cooking appliances, paint and lamp
rooms, lockers and store-rooms having areas of 4 m2 or
more, spaces for the storage of flammable liquids, bonded stores and
workshops other than those forming part of the machinery spaces.
-
Open decks:
- Open deck spaces and enclosed promenades having no fire-risk.
Air spaces (the space outside superstructures and deckhouses).
3.6.3 Continuous
B' Class ceilings or linings, in association with the relevant
decks or bulkheads, may be accepted as contributing, wholly or in
part, to the required insulation and integrity of a division.
3.7 Structural fire protection Protection of stairways and
lifts in accommodation and service spaces
3.7.1 All stairways
are to be of steel construction except where the use of other equivalent
material is specially approved, and are to be within enclosures formed
of A' Class divisions, with positive means of closure at all
openings, except that:
-
A stairway connecting
only two decks need not be enclosed, provided that the integrity of
the deck is maintained by proper bulkheads or doors at one level to
at least B-0' Class. When a stairway is closed at one level,
the stairway enclosure is to be protected in accordance with Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces; and
-
Stairways may be
fitted in the open in a public space, provided that they lie wholly
within such public space.
3.7.2 Stairway
enclosures are to have a direct access to the corridors and to be
of sufficient area to prevent congestion, having in view the number
of persons likely to use them in an emergency. Within the perimeter
of such stairway enclosures, only toilets and lockers of non-combustible
material providing storage for safety equipment are permitted. Only
public spaces, corridors, other escape stairways required by Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.1.(e), pantries containing
cooking appliances with an insignificant fire risk, see
Pt 17, Ch 3, 2.4 Structural fire protection 2.4.2, and external areas are to have
direct access to these stairway enclosures. Small corridors or lobbies
may be used to separate an enclosed stairway from other spaces.
3.7.3 Lift trunks
are to be so fitted as to prevent the passage of smoke and flame from
one 'tween deck to another and are to be provided with means of closing
so as to permit the control of draught and smoke.
3.8 Structural fire protection Openings in A' Class
divisions
3.8.1 The construction
of all doors and door frames in A' Class divisions, with the
means of securing them when closed, is to provide resistance to fire
as well as to the passage of smoke and flame, as far as practicable,
equivalent to that of the bulkheads in which the doors are situated.
Such doors and door frames are to be constructed of steel or other
equivalent material. Steel watertight doors need not be insulated.
3.8.2 It is
to be possible for each door to be opened and closed from each side
of the bulkhead by one person only.
3.8.3 Fire doors
in main vertical zone bulkheads and stairway enclosures are to satisfy
the following requirements:
-
The doors shall
be self-closing and be capable of closing with an angle of inclination
of up to 3,5° opposing closure. The approximate time of closure
for hinged fire doors is to be no more than 40 s and not less than
10 s from the beginning of their movement with the ship in the upright
position. The approximate uniform rate of closure for sliding fire
doors is to be no more than 0,2 m/s and no less than 0,1 m/s with
the ship in the upright position.
-
Remote-controlled
sliding or power-operated doors are to be equipped with an alarm that
will sound not less than 5 s but no more than 10 s before the door
begins to move and will continue to sound until the door is completely
closed. Doors designed to re-open upon contacting an object in its
path are to re-open sufficiently to allow a clear passage of at least
0,75 m but not more than 1 m.
-
All doors are to
be capable of remote and automatic release from the continuously manned
central control station, either simultaneously or in groups and also
individually from a position at both sides of the door. Indication
is to be provided at the fire control panel in the continuously manned
central control station whether each of the remotely-controlled doors
are closed. The release mechanism is to be so designed that the door
will automatically close in the event of disruption of the control
system or central power supply. Release switches shall have an on-off
function to prevent automatic resetting of the system. Hold-back devices
not subject to central control station release are not permitted.
-
Local power accumulators
for power-operated doors are to be located in the immediate vicinity
of the doors. They are to have a capacity to enable the doors to be
fully opened and closed at least 10 times using local controls.
-
Double-leaf doors
dependent on a latch to maintain their fire integrity are to be arranged
so that the latch is automatically activated by the action of the
closing doors.
-
Doors which are
power-operated and automatically closed, giving direct access to special
category spaces need not be equipped with the alarms and remote release
mechanism required by Pt 17, Ch 3, 3.8 Structural fire protection Openings in A' Class divisions 3.8.3.(b) and Pt 17, Ch 3, 3.8 Structural fire protection Openings in A' Class divisions 3.8.3.(c).
-
The components of
the local control system are to be accessible for maintenance and
adjusting.
3.8.4 Where
A' Class divisions are penetrated for the passage of electric
cables, pipes, trunks, ducts, etc. or for girders, beams or other
structural members, arrangements are to be made to ensure that the
fire resistance is not impaired.
3.9 Structural fire protection Openings in steel outer boundaries
3.10 Structural fire protection Openings in 'B' Class divisions
3.10.1 Doors
and door frames in B' Class divisions and means of securing
them are to provide a method of closure which has resistance to fire
as far as practicable equivalent to the divisions they serve, except
that ventilation openings may be permitted in the lower portion of
such doors. Where such openings are in or under a door the total net
area of any such opening or openings is not to exceed 0,05 m2 .
When such an opening is cut in a door it is to be fitted with a grill
made of non-combustible material. Bridging ducts are not allowed in
fire divisions.
3.10.2 Cabin
doors in B' class divisions are to be self-closing. Hold-backs
are not permitted.
3.10.3 Where
B' Class divisions are penetrated for the passage of electric
cables, pipes, trunks, ducts, etc. or for the fitting of ventilation
terminals, lighting fixtures and similar devices, arrangements are
to be made to ensure that the fire resistance is not impaired.
3.11 Structural fire protection Windows and side scuttles
3.11.2 Glass
is not to be installed as an interior main vertical zone or stairway
enclosure bulkhead.
3.11.3 For
yachts having a freeboard length of 85 m and over, windows and side
scuttles situated in the yacht's side shell below the life raft and
escape slide embarkation areas and below lifeboat embarkation areas,
are to have fire integrity of at least equal to A-0' Class.
3.12 Structural fire protection Details of construction
3.12.1 In accommodation
and services spaces, control stations, corridors and stairways, air
spaces enclosed behind ceilings, panelling or linings are to be suitably
divided by close-fitting draught stops not more than 7 m apart. In
the vertical direction, such spaces, including those behind linings
of stairways, trunks, etc. are to be closed at each deck.
3.12.2 The
draught stops are to be non-combustible and are to form a continuation
above the ceiling of the bulkhead below or the other side of the panelling
or lining to the bulkhead, as far as possible.
3.12.3 Where
the structure or A' Class divisions are required to be insulated,
it is to be ensured that the heat from a fire is not transmitted through
the intersections and terminal points of the divisions or penetrations
to uninsulated boundaries. Where the insulation installed does not
achieve this, arrangements are to be made to prevent this heat transmission
by insulating the horizontal and vertical boundaries or penetrations
for a distance of 450 mm.
3.13 Structural fire protection Materials
3.13.1 Except
in cargo spaces, mail rooms, baggage rooms, or refrigerated compartments,
of service spaces, all insulation (e.g. fire and comfort) is to be
of non-combustible materials. Partial bulkheads or decks used to subdivide
a space for utility or artistic treatment are to have a non-combustible
core.
3.13.2 The
use of combustible materials is to be kept to a minimum.
3.13.3 Pipes
penetrating A' or B' Class divisions are to be of approved
materials having regard to the temperature such divisions are required
to withstand.
3.13.4 Pipes
conveying oil or combustible liquids through accommodation and service
spaces are to be of approved materials having regard to the fire risk.
3.13.5 Materials
readily rendered ineffective by heat are not to be used for overboard
scuppers, sanitary discharges and other outlets which are close to
the waterline and where the failure of the material in the event of
fire would give rise to danger of flooding.
3.13.7 Vapour
barriers and adhesives used in conjunction with insulation, as well
as insulation of pipe fittings for cold service systems need not be
non-combustible, but they shall be kept to the minimum quantity practicable
and their exposed surfaces shall have low flame spread characteristics.
3.13.8 All
waste receptacles are to be constructed of non-combustible materials
with no openings in the sides or bottom.
3.13.9 Furniture
in the stairway enclosures is to be limited to seating. If required,
it is to be fixed, limited to four seats on each deck in each stairway
enclosure and is not to obstruct the escape route. Additional seating
may be permitted in the main reception area within a stairway enclosure
provided it is fixed and does not obstruct the escape route. Furniture
is not permitted in corridors forming escape routes in cabin areas.
Lockers for the storage of safety equipment may be permitted.
3.14 Structural fire protection Surface of insulation
3.14.1 In spaces
where penetration of oil products is possible, the surface of insulation
is to be impervious to oil or oil vapours. Insulation boundaries are
to be arranged to avoid immersion in oil spillages so far as is practicable.
3.15 Structural fire protection Means of escape
3.15.1 Stairways
and ladders are to be arranged to provide ready means of escape to
the survival craft embarkation deck from all guest and crew spaces
and from spaces in which the crew is normally employed, other than
machinery spaces. In particular, the following provisions are to be
complied with:
-
Below the bulkhead
deck, two means of escape, at least one of which is to be independent
of watertight doors, are to be provided for each watertight compartment
or similarly restricted space or group of spaces. One of these means
of escape may be dispensed with, due regard being paid to the nature
and the location of spaces concerned, and to the number of persons
who normally might be accommodated or employed there.
-
Above the bulkhead
deck, there are to be at least two practical means of escape from
each main vertical zone or similarly restricted space or group of
spaces, at least one of which is to give access to a stairway forming
a vertical escape.
-
If a radio-telegraph
station has no direct access to the open deck, two means of escape
from or access to such station are to be provided, one of which may
be a porthole or window of sufficient size or other satisfactory means
to provide an emergency escape.
-
A corridor, lobby,
or part of a corridor from which there is only one route of escape
is not to exceed 7 m. Where accommodation arrangements are such that
access to compartments is through another compartment, as is often
the case with an Owner's suite, a second means of escape is to be
provided. The second escape route is to be as remote as possible from
the main escape route. The second means of escape may be through portholes
or hatches of adequate size, leading to the open deck.
-
At least one of the means of escape required by Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.1 and Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.1.(b) is to be by means of a readily accessible
enclosed stairway, which will provide continuous fire shelter from the level of
its origin to the appropriate survival craft embarkation decks, or the uppermost
weather deck if the embarkation deck does not extend to the main vertical zone
being considered. In the latter case, direct access to the embarkation deck by
external open stairways and passageways is to be provided and is to have emergency
lighting and slip-free surfaces underfoot. Boundaries facing external open
stairways and passageways forming part of an escape route and boundaries in such a
position that their failure during a fire would impede escape to the embarkation
deck, are to have fire integrity and insulation values in accordance with Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces. The widths, number and continuity of escape
routes are to be as follows:
-
Stairways are to be not less than 900 mm clear
width between handrails. Stairways are to be fitted with handrails
on each side. The minimum clear width of stairways is to be increased
by 10 mm for every person provided for in excess of 90 persons. The
maximum clear width between handrails where stairways are wider than
900 mm is to be 1800 mm. The total number of persons to be evacuated
by such stairways is to be two-thirds of the crew and total number
of passengers in the areas served by such stairways.
-
Stairways with a clear width in excess of
900 mm are to be aligned in a fore-and-aft direction.
-
Doorways, corridors and intermediate landings
included in the means of escape are to have widths sized in the same
manner as the stairways.
-
Stairways are not to exceed 3,5 m vertical
rise without the provision of a landing and are not to have angle
of inclination greater than 45° to the horizontal.
-
With the exception of intermediate landings,
landings at each deck level shall not be less than 2 m2 in
area and shall increase by 1 m2 for every 10 persons provided
for in excess of 20 persons but need not exceed 16 m2,
except for those landings serving public spaces having direct access
onto the stairway enclosure. Intermediate landings shall be sized
in accordance with paragraph (iii).
-
Protection of access
from the stairway enclosures to the survival craft embarkation areas
are to comply with the requirements of Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces.
-
Where public spaces
span three or more open decks, contain combustibles such as furniture
and give access to other enclosed spaces, each level within the space
is to have two means of escape, one of which is to give direct access
to an enclosed vertical means of escape meeting the requirements of Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.1.(e).
-
Where a dispensation
has been granted under the provisions of Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.1, a safe means of escape is
to be provided. Stairways are to be provided with handrails on both
sides and are to have a clear width between handrails of not less
than 800 mm.
3.15.2 Two
means of escape are to be provided from each machinery space. In particular,
the following provisions are to be complied with:
-
Where the space
is below the bulkhead deck the two means of escape are to consist
of either:
-
Two sets of steel ladders and walkways as
widely separated as possible, leading to doors in the upper part of
the space similarly separated and from which access is provided to
the appropriate survival craft embarkation decks. One of these ladders
is to provide continuous fire shelter from the lower part of the space
to a safe position outside the space. This shelter is to be of steel
or equivalent material, insulated where necessary, and provided with
a self closing door of steel or equivalent material at the lower end.
If access is provided at other levels each level is to be provided
with a steel or equivalent material; or
-
One steel ladder leading to a door in the
upper part of the space from which access is provided to the embarkation
deck and additionally, in the lower part of the space and in a position
well separated from the ladder referred to, a steel or equivalent
material door capable of being operated from each side and which provides
access to a safe escape route from the lower part of the space to
the embarkation deck.
-
Where the space
is above the bulkhead deck, the two means of escape are to be as widely
separated as possible and the doors leading from such means of escape
are to be in a position from which access is provided to the appropriate
survival craft embarkation decks. Where such means of escape require
the use of ladders these are to be of steel.
3.15.3 One
of the means of escape from any such space required by Pt 17, Ch 3, 3.15 Structural fire protection Means of escape 3.15.2 may be dispensed with, so
long as either a door or a steel ladder and walkways provides a safe
escape route to the embarkation deck, due regard being paid to the
nature and location of the space and whether persons are normally
employed in that space.
3.15.4 Two
means of escape are to be provided from a machinery control room located
inside a machinery space, at least one of which is to provide continuous
fire shelter to a safe position outside the machinery space.
3.15.5 Adequate
deck area is to be provided at muster stations and embarkation areas
having due regard to the expected number of persons.
3.16 Ventilation systems
3.16.1 Ventilation
ducts are to be of steel or another non-combustible material subject
to the other material having passed a standard fire test in accordance
with Annex 1: Part 3 of the FTP Code as a non-load bearing structure
for 30 minutes following the requirements for testing B
class divisions. Short lengths of ducts not exceeding 2 m in length
and with a cross-section not exceeding 0,02 m2 need not
be non-combustible, subject to these ducts being:
-
of a material that
has low flame spread characteristics;
-
used at the end
of the ventilation device; and
-
situated not less
than 600 mm, measured along the duct, from an opening in an A'
or B' Class division including continuous B' Class ceilings.
3.16.2 Where the ventilation ducts with a free cross-sectional area exceeding 0,02
m2 but not more than 0,075 m2 pass through Class 'A' bulkheads
or decks, the openings are to be lined with a steel sheet sleeve unless the ducts
passing through the bulkheads or decks are of steel in the vicinity of passage through
the deck or bulkhead and the ducts and sleeves are to comply in this part with the
following:
-
Steel ducts, or
sleeves lining such ducts are to have a thickness of at least 3 mm
and a length of at least 900 mm. When passing through bulkheads, this
length is to be divided preferably into 450 mm on each side of the
bulkhead. These ducts, or sleeves lining such ducts, are to be provided
with fire insulation. The insulation is to have at least the same
fire integrity as the bulkhead or deck through which the duct passes.
-
Steel ducts with a free cross-sectional area exceeding 0,075
m2 are to be fitted with fire dampers in addition to the
requirements of Pt 17, Ch 3, 3.16 Ventilation systems 3.16.2. The fire damper is to operate automatically but
is also to be capable of being closed manually from both sides of the bulkhead or
deck. The damper is to be provided with an indicator which shows whether the
damper is open or closed. Fire dampers are not required, however, where ducts pass
through spaces surrounded by A' Class divisions, without serving those spaces,
provided those ducts have the same fire integrity as the divisions which they
penetrate.
-
Compliance with Pt 17, Ch 3, 3.8 Structural fire protection Openings in A' Class divisions 3.8.4.
3.16.3 Ventilation
ducts with a free cross-sectional area exceeding 0,02 m2 passing
through B' Class bulkheads are to be lined with steel sheet,
or other equivalent material, sleeves of 900 mm in length divided
preferably into 450 mm on each side of the bulkheads unless the duct
is of steel for this length, see also
Pt 17, Ch 3, 3.10 Structural fire protection Openings in 'B' Class divisions.
3.16.4 Ducts
provided for the ventilation of Category A' machinery spaces,
galleys, spaces containing vehicles or craft with fuel in their tanks
or lockers storing such fuels, are not to pass through accommodation
spaces, service spaces or control stations unless the ducts are:
-
either:
-
constructed of steel having a thickness of at least 3 mm for
ducts with a free cross-sectional area of less than 0,075 m2, at
least 4 mm for ducts with a free cross-sectional area of between 0,075
m2 and 0,45 m2, and at least 5 mm for ducts with a
free cross-sectional area of over 0,45 m2;
-
suitably supported
and stiffened;
-
fitted with
automatic fire dampers close to the boundaries penetrated; and
-
insulated to
A-60' Class standard from the machinery spaces, galleys, spaces
containing vehicles or craft with fuel in their tanks or lockers storing
such fuels, to a point at least 5 m beyond each fire damper;
-
or:
-
constructed of
steel in accordance with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4 and Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4.(a).(ii); and
-
insulated to
A-60' Class standard throughout the accommodation spaces, service
spaces or control stations;
except that penetrations of main zone divisions are also to
comply with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.8.
3.16.5 Ducts
provided for ventilation to accommodation spaces, service spaces or
control stations are not to pass through such spaces, unless, where
they pass through Category A' machinery spaces, galleys, spaces
containing vehicles or craft with fuel in their tanks, or lockers
storing such fuels, the ducts:
-
either:
-
are constructed of steel in accordance with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4 and Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4.(a).(ii);
-
are fitted with automatic fire dampers close
to the boundaries penetrated; and
-
have the integrity of boundaries of the machinery space,
galley, spaces containing vehicles or craft with fuel in their tanks, or
lockers storing such fuels, maintained at the penetrations; are insulated to
A 60 class standard from the boundaries of the spaces they serve to a
point at least 5 m beyond each fire damper.
-
or:
-
are constructed of steel in accordance with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4 and Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4.(a).(ii); and
-
are insulated to A-60' Class standard
within the machinery space, galley or spaces containing vehicles or
craft with fuel in their tanks or lockers storing such fuels;
except that penetration of main zone divisions is also to comply
with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.8
3.16.6 Such
measures as are practicable are to be taken in respect of control
stations outside machinery spaces in order to ensure that ventilation,
visibility and freedom from smoke are maintained, so that in the event
of fire the machinery and equipment contained therein may be supervised
and continue to function effectively. Alternative and separate means
of air supply are to be provided; air inlets of the two sources of
supply are to be so disposed that the risk of both inlets drawing
in smoke simultaneously is minimised. Such requirements need not apply
to control stations situated on, and opening on to, an open deck,
or where local closing arrangements would be equally effective.
3.16.7 Where
they pass through accommodation spaces or spaces containing combustible
materials, the exhaust ducts from galley ranges are to comply with Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4. Such exhaust ducts are to
be fitted with:
-
a grease trap readily
removable for cleaning;
-
an automatically and remotely operated fire damper located in the
lower end of the duct at the junction between the duct and the galley range hood
and, in addition, a remotely operated fire damper in the upper end of the duct
close to the outlet of the duct;
-
arrangements, operable from within the galley, for shutting off the
exhaust and supply fans; and
-
fixed means for
extinguishing a fire within the duct.
3.16.8 Where it is necessary that a ventilation duct passes through a main
vertical zone division, a fail-safe automatic closing fire damper is to be fitted
adjacent to the division. The damper is also to be capable of being manually closed from
each side of the division. The operating position is to be readily accessible and be
clearly and prominently marked. The duct between the division and the damper is to be of
steel or other equivalent material and, if necessary, insulated to comply with Pt 17, Ch 3, 3.8 Structural fire protection Openings in A' Class divisions 3.8.4. The damper is to be fitted on at least one side of
the division with a visible indicator showing the operating position of the damper.
3.16.9 Where
public spaces span three or more open decks and contain combustibles
such as furniture and other enclosed spaces, the space is to be equipped
with a smoke extraction system. The smoke extraction system is to
be activated by the smoke detection system required by Pt 17, Ch 4, 2 Fixed fire detection and fire-alarm systems and is to be capable of manual
control. The fans are to be capable of exhausting the entire volume
within the space in not more than 10 min.
3.16.10 The
main inlets and outlets of all ventilation systems are to be capable
of being closed from outside the spaces being ventilated.
3.16.11 Power
ventilation of accommodation spaces, service spaces, control stations
and machinery spaces is to be capable of being stopped from an easily
accessible position outside the space being served. This position
should not be readily cut off in the event of a fire in the spaces
served. The means provided for stopping the power ventilation of the
machinery spaces is to be entirely separate from the means provided
for stopping ventilation of other spaces, see also
Pt 16, Ch 2, 17.6 Fire safety stops.
3.16.13 Ducts provided for exhaust ventilation from laundries are to be fitted
with:
- filters readily removable for cleaning purposes;
- a fire damper located in the lower end of the duct which is automatically and
remotely operated;
- remote-control arrangements for shutting off the exhaust fans, and
supply fans from within the space and for operating the fire damper mentioned in (b);
and
- suitably located hatches for inspection and cleaning.
3.16.14 Where a ventilation room serves only an adjacent machinery space of Category A and there
is no fire division between the ventilation room and the machinery space, the means for
closing the ventilation duct or ducts serving the machinery space shall be located
outside of the ventilation room and machinery space.
3.16.15 Where a ventilation room serves a machinery space of Category A as well as other spaces
and is separated from the machinery space by a A-0 class division, including
penetrations, the means for closing the ventilation duct or ducts for the machinery
space can be located in the ventilation room.
3.16.16 Fire dampers required by Pt 17, Ch 3, 3.16 Ventilation systems 3.16.2, Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4, Pt 17, Ch 3, 3.16 Ventilation systems 3.16.5, Pt 17, Ch 3, 3.16 Ventilation systems 3.16.7 upper end fire damper only, Pt 17, Ch 3, 3.16 Ventilation systems 3.16.8 and Pt 17, Ch 3, 3.16 Ventilation systems 3.16.13, including relevant means of operation are to be fire tested.
Reference is also to be made to IMO FTP Code, Annex 1, Part 3 - Test for A, B and F Class Divisions.
The lower end fire damper required by Pt 17, Ch 3, 3.16 Ventilation systems 3.16.7 must be of steel and capable of stopping the
draught.
3.17 Fuel oil arrangements
3.17.1 In a
yacht in which fuel oil is used, the arrangements for the storage,
distribution and utilisation of the fuel oil are to be such as to
ensure the safety of the yacht and persons on board. For details, see
Pt 15, Ch 3 Machinery Piping Systems.
3.17.2 As far
as practicable, fuel oil tanks are to be part of the yacht's structure
and are to be located outside Category A' machinery spaces.
3.17.3 Where
fuel oil tanks, other than double bottom tanks, are necessarily located
adjacent to or within Category A' machinery spaces, at least
one of their vertical sides is to be contiguous to the machinery space
boundaries, and is preferably to have a common boundary with the double
bottom tanks, and the area of the tank boundary common with the machinery
spaces is to be kept to a minimum. Where the vertical boundary of
a tank directly exposed to a machinery space meets the yacht's side
plating at an acute angle, a small horizontal surface at the base
of the tank, necessary to accommodate practical constructional considerations
may be permitted. If the arrangement of the machinery is such that
a tank with a large horizontal surface at the base is necessary then
a cofferdam with suitable ventilation arrangements, to protect the
base of the tank from the effect of a machinery space fire, will be
specially considered. See also
Pt 15, Ch 3 Machinery Piping Systems. Fuel oil tanks situated within the boundaries of
Category A' machinery spaces are not to contain fuel oil having
a flashpoint of less than 60°C. The use of free-standing fuel
oil tanks is prohibited.
3.18 Lubricating oil arrangements
3.18.1 The
arrangements for the storage, distribution and utilisation of oil
used in pressure lubrication systems are to be such as to ensure the
safety of the yacht and persons on board, see also
Pt 15, Ch 3 Machinery Piping Systems.
3.19 Arrangements for other flammable oils
3.19.1 The
arrangements for the storage, distribution and utilisation of other
flammable oils employed under pressure in power transmission systems,
control and activating systems and heating systems are to be such
as to ensure the safety of the ship and persons on board, see
also
Pt 15, Ch 3 Machinery Piping Systems.
3.20 Prohibition of carriage of flammable oils in forepeak tanks
3.20.1 Fuel
oil, lubricating oil and other flammable oils are not to be carried
in forepeak tanks.
3.21 Special arrangements in Category A' machinery spaces
3.21.1 Openings
are to be provided with closing appliances constructed so as to maintain
the fire integrity of the machinery space boundaries.
3.21.2 Doors
other than power operated watertight doors, are to be so arranged
that positive closure is assured in case of fire in the space, by
power-operated closing arrangements or by the provision of self-closing
doors capable of closing against an inclination of 3,5° opposing
closure and having a fail-safe hook-back facility, provided with a
remotely operated release device.
3.21.3 Windows
are not to be fitted in machinery space boundaries. This does not
preclude the use of glass in control rooms within the machinery spaces.
3.21.4 Means
of control are to be provided for:
-
closure of openings
which normally allow exhaust ventilation, and closure of ventilator
dampers;
-
permitting the
release of smoke;
-
closing power-operated
doors or actuating release mechanism on doors other than power-operated
watertight doors;
-
stopping ventilating
fans; and
-
stopping forced
and induced draught fans, fuel oil transfer pumps, fuel oil unit pumps
and other similar fuel pumps.
3.21.6 When
access to any Category A' machinery space is provided at a
low level from an adjacent space there is to be provided near the
watertight door, a light steel fire-screen door operable from each
side.
3.22 Arrangements for gaseous fuel for domestic purposes
3.22.1 Where
gaseous fuel is used for domestic purposes, the arrangements for the
storage, distribution and utilisation of the fuel is to be such that,
having regard to the hazards of fire and explosion which the use of
such fuel may entail, the safety of the yacht and the persons on board
is preserved. The installation is to be in accordance with recognised
National or International Standards.
3.22.2 Storage
lockers for gas cylinders are to be provided with:
-
effective ventilation;
-
an outward-opening
door accessible directly to the open deck; and
-
gas-tight boundaries,
including doors and other means of closing any openings therein, which
form boundaries between such lockers and adjoining enclosed spaces.
3.23 Space heaters
3.23.1 Space
heaters, if used, are to be fixed in position and so constructed as
to reduce fire risks to a minimum. The design and location of these
units is to be such that clothing, curtains or other similar materials
cannot be scorched or set on fire by heat from the unit.
3.24 Fixed fire detection and fire-alarm systems
3.24.2 A fixed
fire detection and fire-alarm system is to be fitted in all stairways
(including lift and dumbwaiter trunks), service spaces, control stations
and accommodation spaces (except toilets, bathrooms, void spaces,
etc.). The fixed fire detection and fire-alarm system is to be installed
in accordance with Pt 17, Ch 4, 2 Fixed fire detection and fire-alarm systems.
3.24.3 All
yachts at all times when at sea, or in port (except when out of service),
are to be so equipped as to ensure that any initial fire-alarm is
immediately received by a responsible member of the crew.
3.24.4 A special
alarm, operated from the navigating bridge or fire-control station,
is to be fitted to summon the crew.
3.24.5 For
yachts having a freeboard length of 85 m or more, a public address
system is to be available throughout the accommodation and service
spaces and control stations and open decks. The arrangements are to
comply with Pt 16, Ch 2, 18.3 Public address system.
3.25 Fire pumps and fire main system
3.25.1
Application. Every yacht is to be provided with fire pumps in accordance
with this Section. Fire mains, hydrants and hoses are also to be provided
as required by this Section.
3.25.2
Capacity
of fire pumps:
-
The fire pumps
required are to be capable of delivering for fire-fighting purposes
a quantity of water, at the pressure specified in Pt 17, Ch 3, 3.25 Fire pumps and fire main system 3.25.5 of not less than two-thirds
of the quantity required to be dealt with by the bilge pumps when
employed for bilge pumping. For number and capacity of bilge pumps, see
Pt 15, Ch 2 Ship Piping Systems
-
As an alternative
to (a) the capacity of fire pumps may be determined by hydrostatic
calculations based on the requirement of Pt 17, Ch 3, 3.25 Fire pumps and fire main system 3.25.5.
-
Where more pumps
than the minimum number of required pumps are installed the capacity
of such additional pumps will be specially considered.
3.25.3
Fire
pumps:
-
In yachts of 4000
tons gross or more, at least three independently driven fire pumps
are to be provided and, in yachts of less than 4000 tons gross, at
least two such fire pumps.
-
Sanitary, ballast,
bilge or general service pumps may be accepted as fire pumps, provided
that they are not normally used for pumping oil, and that, if they
are subject to occasional duty for the transfer or pumping of fuel
oil, suitable changeover arrangements are fitted.
-
In yachts classed
for navigation in ice, the fire pump sea inlet valves are to be provided
with clearing arrangements, see
Pt 1, Ch 2, 3.8 Other hull notations 3.8.1.
-
The arrangement
of sea connections, fire pumps and their sources of power are to be
such as to ensure that in the event of a fire in any one compartment,
all the fire pumps will not be put out of action.
-
The arrangements
for the ready availability of water supply are to be as follows:
-
In yachts of 1000 gross tons or more, or any
yacht of an alternative form of construction, the arrangements are
to be such that at least one effective jet of water is immediately
available from any hydrant in an interior location and so as to ensure
the continuation of the output of water by the automatic starting
of a required fire pump.
-
Yachts not provided with arrangements complying
with (i), but to which a UMS notation is to be assigned, are to have
remote starting of a required fire pump from the navigating bridge
and fire-control station, if any.
-
Relief valves are
to be provided in conjunction with any fire pump if the pump is capable
of developing a pressure exceeding the design pressure of the water
service pipes, hydrants and hoses. These valves are to be so placed
and adjusted as to prevent excessive pressure in any part of the fire
main system.
-
Where centrifugal
pumps are provided in order to comply with this sub-Section, a non-return
valve is to be fitted in the pipe connecting the pump to the fire
main.
3.25.4
Fire
main:
-
The diameter of
the fire main is to be based on the required capacity of two fire
pumps, and the diameter of the water service pipes are to be sufficient
to ensure an adequate supply of water for the simultaneous operation
of at least two fire-hoses. In general, the diameter of the fire main
is to be not less than:
but need not exceed 180 mm in yachts, and in no case
to be less than 50 mm
-
The wash deck line
may be used as a fire main provided that the requirements of this
sub-Section are satisfied.
-
All exposed water
pipes for fire-extinguishing are to be provided with drain valves
for use in frosty weather. The valves are to be located where they
will not be damaged.
3.25.6
Number
and position of hydrants:
-
The number and
position of the hydrants are to be such that at least two jets of
water not emanating from the same hydrant, one of which is to be from
a single length of hose, may reach any part of the yacht normally
accessible to the guests and crew while the yacht is being navigated.
In yachts of 1000 tons gross or more, at least two hydrants are to
be provided in the machinery spaces; in smaller yachts one hydrant
will be accepted.
-
In the accommodation,
service and machinery spaces, the number and position of hydrants
are to be such that the requirements of (a) may be complied with when
all watertight doors and all doors in main vertical zone bulkheads
are closed.
-
Where access is
provided to a machinery space of Category A' at a low level,
two hydrants are to be provided external to, but near the entrance
to that machinery space.
3.25.7
Pipes
and hydrants:
-
Materials readily
rendered ineffective by heat are not to be used for fire mains. Where
steel pipes are used, they are to be galvanised internally and externally.
Cast iron pipes are not acceptable. The pipes and hydrants are to
be so placed that the fire-hoses may be easily coupled to them. The
arrangement of pipes and hydrants shall be such as to avoid the possibility
of freezing. Unless one hose and nozzle is provided for each hydrant
in the yacht, there is to be complete interchangeability of hose couplings
and nozzles.
-
A valve is to be
fitted at each fire hydrant so that any fire-hose may be removed while
the fire pump is at work.
-
Isolating valve(s)
to isolate the section of the fire main within the Category A'
machinery space containing the main fire pump(s) from the rest of
the fire main are to be fitted in an easily accessible and tenable
position outside the Category A' machinery space. The fire
main is to be so arranged that when the isolating valve(s) is shut,
all the hydrants on the yacht, except those in the Category A'
machinery space referred to above, can be supplied with water by a
fire pump not located in this Category A' machinery space through
pipes which do not enter this space.
3.25.8
Fire-hoses:
-
Fire-hoses are
to be of approved non-perishable material. The hoses are to be sufficient
in length to project a jet of water to any of the spaces in which
they may be required to be used. Their length, in general, is not
to exceed 18 m. Each hose is to be provided with a nozzle and the
necessary couplings. Fire-hoses, together with any necessary fittings
and tools, are to be kept ready for use in conspicuous positions near
the water service hydrants or connections.
-
There is to be
at least one fire-hose for each of the hydrants required by Pt 17, Ch 3, 3.25 Fire pumps and fire main system 3.25.6.
3.25.9
Nozzles:
-
For the purpose
of this Chapter, standard nozzle sizes are to be 12 mm, 16 mm or 19
mm, or as near thereto as possible, so as to make full use of the
maximum discharge capacity of the fire pumps.
-
For accommodation
and service spaces, the nozzle size need not exceed 12 mm.
-
For machinery spaces
and exterior locations, the nozzle size is to be such as to obtain
the maximum discharge possible from two jets at the pressure indicated
in Pt 17, Ch 3, 3.25 Fire pumps and fire main system 3.25.5 from the smallest
pump, however a nozzle size greater than 19 mm need not be used.
-
All nozzles are
to be of an approved dual purpose type (i.e. spray/jet type) incorporating
a shut-off.
3.25.10
Location
and arrangement of water pumps, etc. for other fire-extinguishing
systems. Pumps required for the provision of water for other
fire-extinguishing systems required by this Chapter, are to have their
sources of power and their controls installed outside the space or
spaces protected by such systems and are to be so arranged that a
fire in the space or spaces protected will not put any such system
out of action.
3.25.11
International
shore connection. At least one is to be provided.
3.26 Fire-extinguishing arrangements in spaces containing internal
combustion machinery
3.26.1 Category
A' machinery spaces containing internal combustion machinery
are to be provided with:
-
one of the fire-extinguishing
systems described in Pt 17, Ch 4, 3 Fixed fire-extinguishing systems in machinery spaces;
-
at least one set
of portable air-foam equipment complying with Pt 17, Ch 3, 3.29 Automatic sprinkler, fire detection and fire-alarm system;
-
in each such space
approved foam type fire-extinguishers, each of at least 45 litres
capacity or equivalent, sufficient in number to enable foam or its
equivalent to be directed on to any part of the fuel and lubricating
oil pressure systems, gearing and other fire hazards; and
-
a sufficient number
of portable foam extinguishers or equivalent are to be located so
that no point in the space is more than 10 m walking distance from
an extinguisher and that there are at least two such extinguishers
in each such space.
3.27 Fire-extinguishing arrangements in spaces containing fuel oil
units
3.27.2 There
are to be at least two portable foam extinguishers or equivalent in
each space in which a part of the fuel oil unit is situated.
3.28 Limitations on the use of oil as a fuel
3.29 Automatic sprinkler, fire detection and fire-alarm system
3.29.1 A fixed
automatic sprinkler, fire detection and fire-alarm system, or equivalent
system (e.g. watermist), is to be fitted in all stairways, service
spaces, control stations and accommodation spaces except spaces which
afford no fire risk such as void spaces.
3.30 Fixed fire-extinguishing systems not required by this Section
3.30.1 Where
a fixed fire-extinguishing system not required by this Section is
installed, the arrangement is to comply with the relevant requirements
of this Chapter.
3.31 Portable foam applicator
3.31.1 A portable
foam applicator unit is to consist of an air foam nozzle of an inductor
type capable of being connected to the fire main by a fire-hose, together
with a portable tank containing at least 20 litres of foam-making
liquid and one spare tank. The nozzle is to be capable of producing
effective foam, suitable for extinguishing an oil fire, at the rate
of at least 1,5 m3 /min
3.32 Portable fire-extinguishers
3.32.2 The
extinguishers are to be stowed in readily accessible positions.
3.32.3 One
of the portable fire-extinguishers, or the portable fire-extinguisher,
dedicated for use in any space is to be stowed near the entrance to
that space.
3.32.4 At least
one portable fire-extinguisher is to be located so that it can easily
be reached from the main steering position of the yacht.
3.32.5 Accommodation
spaces, service spaces and control stations are to be provided with
a sufficient number of portable fire-extinguishers to ensure that
at least one extinguisher will be readily available for use in every
compartment. In any case, their number is to be not less than five.
3.32.6 Where
cooking facilities are provided, a portable fire-extinguisher of a
type appropriate to the energy source used is to be located in a position
readily accessible for use in the event of a fire.
3.33 Fire blanket
3.33.1 A fire
blanket is to be installed in all galleys.
3.34 Protection of spaces containing vehicles or craft with fuel in
their tanks, or lockers storing such fuels
3.34.1 Spaces
containing vehicles or craft with fuel in their tanks, or lockers
storing such fuels, are to be provided with the following:
-
A fixed fire detection
and fire-alarm system complying with the requirements of Pt 16, Ch 1, 2.8 Fire detection and fire alarm systems.
-
A manually-operated
water spray deluge system having a water application rate of 5 litres
per square metre of deck area per minute. Where the deck height does
not exceed 2,5 m, an application rate of 3,5 litres per square metre
of deck area per minute will be accepted. Adequate drainage of the
protected spaces is to be provided generally in accordance with the
requirements for vehicle or cargo space, see
Pt 3, Ch 4, 9.4 Scupper arrangements 9.4.4. The drainage piping
and connections for the space are to be non-combustible. Other fixed
fire-extinguishing systems may be permitted, provided they are not
less effective in controlling the type of fire likely to occur.
-
At least two portable
foam extinguishers, or equivalent;
-
An independent
mechanical ventilation system, which is entirely separate from other
ventilation systems, providing at least six air changes per hour.
The ducted air is not to pass through other spaces, except as allowed
under Pt 17, Ch 3, 3.16 Ventilation systems 3.16.4, or vent into
areas where it could be drawn into accommodation areas or cause undue
hazard.
-
Electrical equipment
of a safe type is to be provided, see
Pt 16, Ch 2, 14 Electrical equipment for use in explosive atmospheres
-
Prominently displayed
'No Smoking' signs; and
-
Structural fire protection as required by Table 3.3.2 Fire integrity of bulkheads
separating adjacent spaces and Table 3.3.3 Fire integrity of decks separating
adjacent spaces.
3.34.2 Such
spaces are not to give access to any space other than the fuel store
or lockers for use within the space. Lockers storing fuel are to be
accessed from an exterior location, unless the locker is within the
space containing the vehicles or craft. Exceptionally, where the engine
room escape cannot be routed elsewhere, it may exit into the space
providing that:
-
the connecting
door is self-closing;
-
no door hold-back
devices are fitted;
-
an audible and
visual alarm is fitted on the bridge to signify when the door is open;
and
-
a notice is posted
at the door stating that the door is to remain closed and that the
area beside the door is an escape route and is to be kept clear.
3.35 Protection of paint lockers and flammable liquid lockers
3.35.1 Paint
lockers and flammable liquid lockers of deck area 4 m2 or
more are to be provided with a fixed fire-extinguishing system enabling
the crew to extinguish a fire without entering the space. One of the
following systems is to be provided:
- A carbon dioxide system designed for 40 per cent of the gross
volume of the space.
- A dry powder system designed to discharge 0,5 kg powder per cubic
metre of gross volume of the space.
- A water spray system designed to give a coverage of 5 litres per
square metre of deck area per minute. Water spray systems may be connected
to the fire main.
3.35.2 Consideration
will be given to the acceptance of other arrangements which provide
equivalent protection.
3.35.3 Lockers
having a deck area of less than 4 m2 may be protected by
carbon dioxide or dry powder portable extinguishers located near the
entrance to the locker.
3.36 Arrangements where deep fat cooking equipment is installed
3.36.1 Where
deep-fat cooking equipment is installed, all installations are to
fitted with:
-
an automatic or
manual fixed extinguishing system type approved in accordance with
ISO 15371, Ships and marine technology-Fire extinguishing systems
for protection of galley deep-fat cooking equipment-Fire tests,
or an acceptable alternative National or International Standard, for
protection of the deep-fat cooking equipment;
-
a primary and back
up thermostat with an alarm to alert the operator in the event of
failure of either thermostat;
-
arrangements for
automatically shutting off the deep-fat cooking equipment electrical
power upon activation of the fire-extinguishing system;
-
an alarm for indicating
operation of the fire-extinguishing system in the galley where the
equipment is installed; and
-
controls for manual
operation of the fire-extinguishing system which are clearly labelled
for ready use by the crew.
Control and electrical engineering arrangements are to be in
accordance with the requirements of Pt 16, Ch 1 Control Engineering Systems and Pt 16, Ch 2 Electrical Engineering, as applicable.
3.36.2 For
fryers of up to 15 litres cooking oil capacity, the provision of a
suitably sized extinguisher of a suitable type located for specific
use on the cooking equipment together with manual isolation of the
electrical power supply may be considered an acceptable alternative
to Pt 17, Ch 3, 3.36 Arrangements where deep fat cooking equipment is installed 3.36.1 provided the arrangements
are to the satisfaction of the National Administration.
3.37 Helicopter decks
3.38 Fireman's outfit
3.38.1 Each
yacht is to carry at least two fireman's outfits complying with Pt 17, Ch 4, 4 Fireman's outfits. Additional fireman's outfits are
to be provided as applicable to ensure that at least two fireman's
outfits are stored in each main vertical zone.
3.38.2 The
fireman's outfits are to be so stored as to be easily accessible and
ready for use. Where more than two fireman's outfits are required,
they are to be located in widely separated positions. At least two
fireman's outfits are to be available at any one position.
3.38.3 Additional
sets of personal equipment and breathing apparatus may be required,
having due regard to the size of the yacht.
3.39 Fire-control plans
|