Section
4 Structural design loads
4.1 General
4.1.1 The requirements in this Section define the loads and load combinations
to be considered in the overall strength analysis of the unit and the design
pressure heads to be used in the Rules for local scantlings.
4.1.2 A unit’s modes of operation are to be investigated using realistic
loading conditions, including buoyancy, gravity and functional loadings together
with relevant environmental loadings. Due account is to be taken of the effects of
wind, waves, currents, motions (inertia), moorings, ice, and, where necessary, the
effects of earthquake, sea bed-supporting capabilities, temperature, fouling, etc.
Where applicable, the design loadings indicated herein are to be adhered to for all
types of offshore units.
4.1.4 The design environmental criteria determining the loads on the unit and
its individual elements are to be based upon appropriate statistical information and
have a return period (period of recurrence) for the most severe anticipated
environment of at least:
- 50 years for Mobile Offshore Units.
- 100 years for Floating Offshore
Installations at a Fixed Location.
For sites susceptible to cyclones, the design of units which remain
on-station during cyclones is to be based upon the most onerous of the cyclonic and
non-cyclonic environments determined at the return periods in Pt 4, Ch 3, 4.1 General 4.1.4.(a) and Pt 4, Ch 3, 4.1 General 4.1.4.(b) for the respective unit type.
If a unit is restricted to seasonal operations in order to avoid
extremes of wind and wave, such seasonal limitations must also be specified.
4.1.5 Model tests are to be carried out as necessary and the tests are to
include means of establishing the effects of green water loading and/or slamming on
the structure through video recordings of the model testing and by measurement of
the following:
4.1.6 When carrying out model tests, account is to be taken of the
following:
- The test programme and the model test facilities are to be to
LR’s satisfaction.
- The relative directions of wind, wave and current are to be
varied as required to ensure that the most critical loadings and motions are
determined.
- The tests are to be of sufficient duration to establish low
frequency motion behaviour.
4.2 Definitions
4.2.1
Still water condition is defined as an ideal condition when no environmental
loads are imposed on the structure, e.g., no wind, wave or current, etc.
4.2.2
Gravity and functional loads are loads which exist due to the unit’s weight,
use and treatment in still water conditions for each design case. All external
forces which are responses to functional loads are to be regarded as functional
loads, e.g., support reactions and still water buoyancy forces.
4.2.3
Environmental loads are loads which are due directly or indirectly to
environmental actions. All external forces which are responses to environmental
loads are to be regarded as environmental loads, e.g., mooring forces and inertia
forces.
4.2.4
Accidental loads are loads which occur as a direct result of an accident or
exceptional circumstances, e.g., loads due to collisions, dropped objects and
explosions, etc. See also
Pt 4, Ch 3, 4.16 Accidental loads.
4.3 Load combinations
4.3.1 The structure is to be designed for the most unfavourable of the
following combined loading conditions (as relevant to the unit):
- Maximum gravity and functional loads.
- Design environmental loads and associated gravity and
functional loads.
- Accidental loads and associated gravity and
functional loads.
- Environmental loads and associated gravity
and functional loads after credible failures or accidents, see
Pt 4, Ch 4, 1.3 Structural design 1.3.5 for redundancy
assessment of column-stabilised units and Pt 10, Ch 2, 3.4 Return periods and probability factor, fprob for assessment of ship units in the flooded
condition.
NOTE
Pt 4, Ch 3, 4.3 Load combinations 4.3.1 relates to the
loading and condition of the unit at the time of the accidental event. Pt 4, Ch 3, 4.3 Load combinations 4.3.1 relates to the
loading and condition of the unit following the accidental event and allowing for
agreed documented mitigation measures to be put in place. See also
Pt 4, Ch 3, 4.16 Accidental loads, Pt 4, Ch 4 Structural Unit Types and Pt 10 Ship Units for applicability to unit types.
4.4 Gravity and functional loads
4.4.1 All gravity loads, including static loads such as weight, outfit,
stores, machinery, ballast, etc., and live functional loads from operating derricks,
cranes, winches and other equipment are to be considered. All practical combinations
of gravity and functional loads are to be included in the design cases.
4.5 Buoyancy loads
4.5.1 Buoyancy loads on all underwater parts of the structure, taking account
of heel and trim when appropriate, are to be considered.
4.6 Wind loads
4.6.1 Account is to be taken of the wind forces acting on that part of the
unit which is above the still water level in all operating conditions and of the
following:
- Consideration is to be given to wind gust velocities which are
of brief duration and sustained wind velocities which act over intervals of
time equal to or greater than one minute, including squalls where relevant.
Different wind velocity averaging time intervals applicable to different
structural categories to be used in design calculations are shown in Pt 4, Ch 3, 4.6 Wind loads 4.6.1.
- Wind velocities are to be specified relative to a standard
reference height of 10 m above still water level for each operating
condition.
- The variation of wind velocity with height and averaging time
interval for each applicable condition may be determined from the following
expression:
VHT |
= |
|
where
C |
= |
0,0573(1+0,148VR)0,5 |
lU |
= |
|
and
VR |
= |
wind velocity at specified reference height
HR and reference time period
T0, in m/s |
H |
= |
specified height above sea level, in meters |
HR |
= |
reference height, in metres |
T |
= |
wind speed averaging time interval, in seconds |
T0 |
= |
reference time period, 1 hour, in seconds |
Table 3.4.1 Structural parts to be
considered for wind loading
Wind speed
averaging time interval
|
Structural
category
|
3 second gust
|
Individual members and
equipment secured to them. Wind loads need not be combined with
current and wave loads.
|
5 second mean
(sustained)
|
Part or whole of a structure
whose greatest horizontal or vertical dimension does not exceed 50
m. Wind loads need not be combined with current and wave
loads.
|
15 second mean
(sustained)
|
Part or whole of a structure
whose greatest horizontal or vertical dimension exceeds 50 m. Wind
loads need not be combined with current and wave loads.
|
1 minute mean
(sustained) see Note
|
Part or whole structure of the
unit regardless of dimension for use with the maximum wave and
current loads.
|
NOTE
|
In no case is the one minute mean value to be taken as less than
25,8 m/s (50 knots).
However, for unrestricted
service the following wind criteria are also to be applicable
for structural design considerations:
- for all modes of operation, whether afloat
or supported by the sea bed, a sustained one minute mean
wind velocity of not less than 36 m/s (70 knots)
- for the survival condition, a sustained one
minute mean wind velocity of not less than 51,5 m/s (100
knots)
The factors of safety are to comply
with Table 5.2.1 Factors of safety for the
combined load cases loadcase
(b).
|
4.6.2 The wind force is to be calculated for each part of the structure and is
not to be taken less than:
where
F |
= |
net force acting on any member or part of the unit. This
includes the effect of any suction on back surfaces |
|
= |
0,613 (0,0625) |
A |
= |
projected area of all exposed surfaces in upright or heeled
position, in m2
|
Table 3.4.2 Values of coefficient
Shape
|
|
Spherical
|
0,40
|
Cylindrical
|
0,50
|
Large flat surface (hull,
deckhouse, smooth underdeck areas)
|
1,00
|
Drilling derrick
|
1,25
|
Wires
|
1,20
|
Exposed beams and girders under
deck
|
1,30
|
Small parts
|
1,40
|
Isolated shapes (cranes,
booms, etc.)
|
1,50
|
Clustered deckhouses or
similar structures
|
1,10
|
NOTE
|
Shapes or
combinations of shapes which do not readily fall into the specified
categories will be subject to special consideration.
|
4.6.3 When calculating wind forces the following procedures should be
considered:
- Shielding may be taken into account when a member or structure
lies closely enough behind another to have a significant effect. Procedures
for determining the shielding effect and loading are to be acceptable to
LR.
- Areas exposed due to heel, such as underdecks, etc., are to be
included using the appropriate shape coefficients.
- If several deckhouses or structural members, etc., are located
close together in a plane normal to the wind direction, the solidification
effect is to be taken into account. The shape coefficient may be assumed to
be 1,1.
- Isolated houses, structural shapes, cranes, etc., are to be
calculated individually, using the appropriate shape coefficient.
- Open truss work commonly used for derrick towers, booms and
certain types of masts may be approximated by taking 30 per cent of the
projected block area of each side, e.g., 60 per cent of the projected block
area of one side for double-sided truss work. An appropriate shape
coefficient is to be taken fromPt 4, Ch 3, 4.6 Wind loads 4.6.2.
4.6.4 For slender structures and components, the effects of wind-induced
cross-flow vortex vibrations are to be included in the design loading.
4.6.5 For slender structures sensitive to dynamic loads, the static gust wind
force is to be multiplied by an appropriate dynamic amplification factor.
4.7 Current loads
4.7.1 In storm conditions, the current has two main components: the tidal and
wind driven components. Submitted information on currents is to include tidal and
wind induced components and the variation of their profiles with water depth,
see
Pt 4, Ch 3, 4.9 Wave loads 4.9.6 and Pt 4, Ch 3, 4.9 Wave loads 4.9.7. In addition, the effects of general
circulation and loop currents are to be included where appropriate.
4.8 Orientation and wave direction
4.8.1 Loadings are to be assessed using sufficient wave headings and crest
positions to determine the most severe loading on the unit. In addition to the
design wave height and period, the unit is to be designed to withstand shorter
period waves of less height when these can induce more severe loading on parts or
the whole unit due to dynamic effects, etc.
4.8.2 Where a unit is required to operate at locations exposed to wind waves
and swell waves acting simultaneously then this is to be taken into account when
determining the wave loads.
4.9 Wave loads
4.9.1 Design wave criteria specified by the Owner/designer may be described
either by means of design wave energy spectra or deterministic design waves having
appropriate shape, size and period. The following should be taken into account:
- The maximum design wave heights specified for each operating
condition should be used to determine the maximum loads on the structure and
principal elements. Consideration is to be given to waves of less than
maximum height, where due to their period, the effects on various structural
elements may be greater.
- Wave lengths are to be selected as the most critical ones for
the response of the structure or element to be investigated.
- An estimate is to be made of the probable wave encounters that
the unit is likely to experience during its service life in order to assess
fatigue effects on its structural elements.
- When units are to operate in intermediate or shallow water, the
effect of the water depth on wave heights and periods and of refraction due
to sea bed topography is to be taken into account.
4.9.2 The forces produced by the action of waves on the unit are to be taken
into account in the structural design, with regard to forces produced directly on
the immersed elements of the unit and forces resulting from heeled positions or
accelerations due to its motion. Theories used for the calculation of wave forces
and selection of relevant coefficients are to be acceptable to LR.
4.9.4 Wave theories used for the calculation of water particle motions are to
be acceptable to LR and when using acceptable wave theories for wave force
determination, reliable values of and which have been obtained experimentally for use in conjunction
with the specific wave theory are to be used. Otherwise published data are to be
used.
4.9.5 Consideration is to be given to the possibility of wave impact and wave
induced vibration in the structure, including superstructures.
4.9.6 Where sea current acts simultaneously with waves, the effect of the
current is to be included in the load estimation. In those cases this superposition
is deemed necessary, the current velocity should be added vectorially to the wave
particle velocity. The resultant velocity is to be used to compute the total
force.
4.9.7 The following methods may be used for load estimation:
- The forces on structural elements with dimensions less than 0,2
of the wave length subject to drag/inertia loading due to wave and current
motions can be calculated from the Morison’s equation:
where
F |
= |
force per unit length of member |
|
= |
drag coefficient |
A |
= |
projected area of member per unit length |
u |
= |
component of the water particle velocity at the axis
of the member and normal to it (calculated as if the member were
not there) |
|
= |
inertia coefficient |
V |
= |
volume of water per unit length |
a |
= |
component of the water particle acceleration at the
axis of the member and normal to it (calculated as if the member
were not there) |
- Overall loading on an offshore structure is determined from the
summation of loads on individual members at a particular time. The proper
values of and for individual members to use with Morison’s equation
will depend on a number of variables, for example: Reynolds number,
Keulegan-Carpenter number, inclination of the member to local flow and
effective roughness of marine growth. Therefore, fixed values for all
conditions cannot be given. Typical values for circular cylindrical members,
will range from 0,6 to 1,4 for and 1,3 to 2,0 for . The values selected are not to be smaller than the lower
limits of these ranges. For inclined members, the drag forces in Morison’s
equation are to be calculated using the normal component of the resultant
velocity vector.
- General values of hydrodynamic coefficients may be used in the
Morison’s equation for the calculation of overall loading on the structure,
namely:
- For circular cylinders covered by hard marine growth, is to be not less than 0,7.
- For circular cylinders not covered by hard marine
growth, is to be not less than 0,6.
- For circular cylinders, is to be not less than 1,7.
- The recommended CD and
CM for the members of a lattice leg are given
in Pt 4, Ch 4, 3.9 Unit in the elevated position.
- Diffraction theory is normally appropriate to determine wave
loads where the member is large enough to modify the flow field.
4.9.8 Account is to be taken of the increase of overall size and roughness of
submerged members due to marine growth when calculating loads due to wave and
current, see
Pt 4, Ch 3, 4.13 Marine growth 4.13.1.
4.10 Inertia loads
4.10.1 Dynamic loads imposed on the structure by accelerations due to the
unit’s motion in a seaway are to be included in the structural design calculations.
The dynamic loads may be obtained from model test results or by calculation. The
methods of calculation are to be acceptable to LR.
4.11 Mooring loads
4.11.1 Mooring loads are to be considered for units operating afloat with
positional mooring systems, see
Pt 3, Ch 10 Positional Mooring Systems. The following are to be considered:
- The overall strength of the structure.
- The local strength where the mooring line forces are transmitted
to the hull.
4.12 Snow and ice loads
4.12.1 Consideration is to be given to the extent to which snow and ice may
accumulate on the exposed structure under any particular weather conditions. The
wind resistance of exposed structural elements will be increased by the growth of
ice. Details of the thickness and distribution of accumulation are to be established
and taken into account in the design, see also
Pt 3, Ch 6 Units for Transit and Operation in Ice.
4.12.2 The increased loading caused by the accumulation of snow and ice on any
part of the structure is to be taken into account.
4.12.3 Values for the thickness, density and variation with height of
accumulated snow and ice are to be derived from meteorological data acceptable to
LR.
4.12.5 It may be assumed that there is no increase of drag coefficient in the
presence of ice.
4.12.6 The appropriate combinations of snow and ice loadings with other design
environmental loads are to be specially considered and agreed with LR. In general,
extreme snow and ice loads are to be combined with other environmental loads
corresponding to the design five-year return criteria for the unit.
Figure 3.4.1 Assumed distribution of ice on
individual members for calculation purposes
4.13 Marine growth
4.13.1 Marine growth will increase the weight and the overall dimensions of
submerged members and alter their surface characteristics. These effects will
increase the loads applied to the structure. The thickness of marine growth taken
into account in the design is to be stated in the Operations Manual and the design
limit is not to be exceeded in service. Unless more accurate data is available from
the marine fouling study, the density of marine growth in air is to be taken as 1325
kg/m3.
4.14 Hydrostatic pressures
4.14.1 The hydrostatic pressure head to be used as the basis for the design of
internal spaces is to be the greatest of the following:
- For tanks, the maximum head during normal operation.
- For shell boundaries, the hydrostatic head due to external sea
pressure.
- For watertight boundaries, the head measured to the worst damage
waterline, see
Pt 4, Ch 7 Watertight and Weathertight Integrity and Load Lines.
The minimum design pressure heads for local strength are to be in
accordance with Chapter 6.
4.14.2 Where testing the tank involves pressure heads in excess of those
derived in Pt 4, Ch 3, 4.14 Hydrostatic pressures 4.14.1, the excess may be taken into account by the
use of a load factor applied to the design head. Where this is done, it is to be
clearly stated in the calculations.
4.15 Deck loads
4.15.1 The maximum design uniform and concentrated deck loads for all areas of
the unit in each mode of operation are to be taken into account in the design. The
minimum design deck loads for local strength are to be in accordance with Pt 4, Ch 6 Local Strength.
4.16 Accidental loads
4.16.1 The following credible failures and accidents are to be considered in
the design as applicable to the function of the unit:
- Collision.
- Dropped object.
- Blast.
- Accidental flooding.
- Loss of primary bracing (column-stabilised unit).
- Emergency helicopter landings.
- Abnormal metocean.
4.16.2 Collision loads imposed by attending vessels which may be approaching,
mooring or lying alongside the unit are to be considered in the design. The unit is
to be designed to withstand accidental impacts between attending vessels and the
unit and be capable of absorbing the impact energy.
Recommended practice is given in LR's Guidance Notes for Collision
Analysis to assist in identifying potential collision scenarios,
establishing representative collision loads and assessing the impact of these loads
on structural integrity.
4.16.3 The kinetic energy to be considered is normally not to be less than:
- 14 MJ for sideway collision;
- 11 MJ for bow or stern collision;
corresponding to an attending vessel of 5000 tonnes displacement with
impact velocity 2 m/s.
4.16.4 A reduced impact energy may be accepted upon special consideration,
taking into account the environmental design criteria.
4.16.5 The energy absorbed by the unit during a collision impact will be less
than or equal to the total impact kinetic energy, depending on the relative
stiffnesses of the relevant parts of the unit and the impacting ship/unit and also
on the mode of collision and ship/unit operation. These factors may be taken into
account when considering the energy absorbed by the unit, see also
Pt 4, Ch 4, 1 Column-stabilised units and Pt 4, Ch 4, 3 Self-elevating units for column-stabilised and
self-elevating units respectively.
4.16.6 Collision is to be considered for all elements of the unit which may be
hit by sideway, bow or stern collision. The vertical extent of the collision zone is
to be based on the depth and draught of attending ships/units and the relative
motion between the attending ships/units and the unit.
4.16.7 The accidental impact loads caused by dropped objects from cranes are to
be considered in the design of the unit when the arrangements of the unit are such
that the failure of a vital structure member could result in the collapse of the
structure.
4.16.8 Critical areas for dropped objects are to be determined on the basis of
the actual movement of crane loads over the unit.
4.16.9 The structural bulkheads protecting accommodation areas, and other
structures that may be subject to blast pressures, are to be designed for accidental
blast loading, where applicable. The design blast pressures are to be defined by the
Owners/designers, see
Pt 7, Ch 3, 2.4 Fire and Explosion Evaluation (FEE) 2.4.2 and are to comply with National
requirements. Blast loads are to be combined with the still water loads.
Environmental loads need not be considered. Design calculations are to be submitted
which may be based on elastic analysis or elastoplastic design methods, see
also
Pt 4, Ch 3, 4.16 Accidental loads 4.16.11.
4.16.10 Accidental flooding of a single hull compartment is to be considered in
the design of the unit. As a minimum, the compartments to be addressed are to
include those set out in Chapter 3 - Subdivision, Stability and Freeboard as applicable to the unit
type. Special consideration will be given to unit types not addressed by the 2009
IMO MODU Code.
4.16.11 Units with slender members where the failure of a single member could
result in the overall collapse of the unit’s structure are to be considered for
credible failure of such members, see
Pt 4, Ch 4 Structural Unit Types.
4.16.13 Abnormal metocean with a return period of 1000 ~ 10000 years are to be
considered in the design of the floating structure. Unless the upper hull structure
is designed for wave impact, the unit is to be designed to have a positive air gap
in abnormal metocean.
4.16.15 When a National Administration in the country in which the unit is
registered and/or in which it is to operate has additional requirements for
accidental loads these are to be taken into account in the design loadings.
4.17 Fatigue design
4.17.1 Fatigue damage due to cyclic loading must be considered in the design of
all unit types.
4.17.2 Fatigue design calculations are to be carried out in accordance with the
analysis procedures and general principles given in Pt 4, Ch 5, 5 Fatigue design or other acceptable method.
4.18 Other loads
4.18.1 If attending ships/units are to be moored to the unit, the forces imposed
by the moorings on the structure are to be taken into account in the design.
4.18.2 Other local loads imposed on the structure by equipment and mooring and
towing systems are to be considered in the design of the structure.
4.18.3 When partial filling of tanks is contemplated in operating conditions,
the risk of significant loads due to sloshing induced by any of the vessel motions
is to be considered. An initial assessment is to be made to determine whether or not
a higher level of sloshing investigation is required, using the procedure given in
Pt 3, Ch 3, 5 Design loading of the Rules for Ships.
|